Description Of Controls
43
Icon
Description
Auto
Mode
This button places the module into its
Auto Mode
. This mode allows the
module to control the function of the generator automatically. The module
monitors the
remote start
input and once a start request is made, the set is
automatically started and placed on load
(‘
Close Generator
’ and ‘
Delayed Load
Output 1, 2, 3 & 4
’
become active in order from lowest to highest (if used))
.
Upon removal of the starting signal, the module removes the load from the
generator and shut the set down observing the
stop delay
timer and
cooling
timer
as necessary
(‘
Close Generator
’ and ‘
Delayed Load Output 1, 2, 3 & 4
’
become
inactive at once (if used))
. The module then awaits for next start event.
For further details, please see section entitled ‘Operation’ elsewhere in this
manual.
Alarm Mute / Lamp Test
This button de-activates the audible alarm output (if configured) and illuminates all
of the LEDs on the module’s facia.
Start
This button is only active in the
Stop/Reset Mode
,
Manual
Mode
and
Test Mode
.
Pressing the
Start
button in
Stop/Reset Mode
powers the ECU but does
not start the engine. This can be used to check the status of the CAN
communication and to prime the fuel system.
Pressing the
Start
button in
Manual
Mode
or
Test Mode
starts the
generator and run it off load in
Manual
Mode
or on load in
Test Mode
.
Содержание DSE7110 MKII
Страница 34: ...Installation 34 4 2 1 DSE7110 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Страница 35: ...Installation 35 4 2 2 DSE7120 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE ...
Страница 36: ...Installation 36 4 3 ALTERNATE TOPOLOGY WIRING DIAGRAMS 4 3 1 GENERATOR ...
Страница 37: ...Installation 37 4 3 2 MAINS DSE7120 MKII ONLY ...
Страница 99: ...This Page is Intentionally Left Blank 99 ...
Страница 100: ...This Page is Intentionally Left Blank 100 ...