Step 1 - Define all Partitions

When the panel is first powered up the 16 zones on the
main panel are assigned to Partition 1. Any additional
zones enrolled to the system are NOT assigned to any
Partition.

Any zones from 1 through 16 that are required on a
different Partition must be DELETED from Partition 1
before they are ADDED to another Partition. Any zones
above Zone 16 must be ADDED to the proper Partition.
See “Zone Assignment” in the Programming Manual for
the procedure to add and delete zones.

When you ADD each zone to the proper Partition it will
save time if you also program the Zone Label, Zone
Type, Zone Options and Reporting codes for the zone.
All of this information may be entered in the
Programming Work Sheets located in Book 2 and in the
program sheets included with each Zone Expansion
module.

Step 2 - Assign User Codes

From default the panel comes with one User Code
assigned as a Grand Master, code ‘1234’. The other 127
User Codes are assigned as Partition 1 codes.

If more than one Partition is being utilized it will be
necessary to assign User Codes to the additional
Partition(s). Since there are no available User Codes
(they are all assigned to Partition 1) it will be necessary
to first delete User Codes from Partition 1. Once codes
are deleted from Partition 1 they will be available to be
assigned to another Partition or as System Masters.

See “Code Assignment” in the Programming Manual.

Step 3 - Program the System

Now that the Partitions have been defined, zones
programmed and access codes assigned you are
ready to program the rest of the system. It is best to
follow the Programming Work Sheets starting at the
beginning and carefully programming each section.
Having the required information entered ahead of time
will speed up this process considerably.

Once the Installer Programming is complete you can
program access codes ([

][5][Master Code]). Next,

features on each partition can be enabled. Go to a
keypad assigned to the desired partition and enable the
features through [

][6][Master Code] commands.

Step 4 - Testing the System

See “Bell/Comm Test” under [

][6] User Functions or do

the following. Contact the monitoring station to request a
transmission test. Plug the telephone cord into the RJ31-
X jack. If a DTS-1 is being used to monitor communicator
transmissions, connect it to the telephone line and place
the DTS-1 in the line mode by pressing the red “LINE/

LOCAL” button. Arm the panel, wait for the exit delay to
expire and trip a detector on an instant circuit. Wait for
the communication to complete. Disarm the panel and
check with the monitoring station to confirm acceptance
of the transmission. Perform additional transmissions
required by the monitoring station.

Check the “TROUBLE” light on the keypad. If it is on,
press [

] then [2] to determine the trouble. The “Trouble

Display” section in “Keypad Functions” gives a
description of the different trouble conditions.

Step 5 - Instructing the End User

Describe system operation to authorized users.

Provide user with the instruction manual and instruct
them to read it to become familiar with the system
operation.

Instruct the user to test the system on a regular basis
as described in the Instruction Manual. The Master
Code should be changed from the default setting and
recorded.

There is a wide range of possible uses for the [

][4]

and [

][7] commands which are not described in the

instruction manual. Be sure to explain the functions of
the [

][4] Sensor Reset and the [

][7] Utility Output to

the user if they are incorporated into the system.

Hardware Reset of Memory to Factory
Defaults

If the installer’s code is lost through inadvertent
programming, the only means of reprogramming the
system is by a hardware reset. If the installer’s lockout
is enabled, there is no way to reprogram the system
without entering the correct installer’s code.

The PC4000 can also be reset through software in the
installer’s programming. See “Factory Default” in the
Programming Guide.

NOTE: Panels returned to DSC with the Installer’s
Lockout feature enabled and no other apparent
problems will be subject to an additional service charge.

To reset the panel to factory default conditions:
1.Power the system down by removing both AC and

battery power to the main panel.

2.Short the zone 1 terminal and the pgm terminal on the

main panel.

3.Restore power to the main panel.
4.Wait for 20 seconds then remove the short between

the pgm and zone 1.

5.The system will have reloaded the memory with

factory defaults. All modules will have to be enrolled
again. The event buffer is the only part of memory that
is retained during a factory default.

Содержание SYSTEM MASTER PC4000

Страница 1: ...SYSTEM MANUAL PC4OOO Book 4 Jan 11 1993 Software Version 1 3 ...

Страница 2: ...anges or modifications not expressly approved by Digital Security Controls Ltd could void your authority to use this equipment This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generat...

Страница 3: ...04 relay output module is available for installations requiring additional power beyond the 500 mA supplied by the PC4000 main panel This module comprises a 12 volt DC power supply of 1 5 Amp capacity and four 12 volt relays with form C contacts which will provide switched outputs under any of the 23 options available in the list of programmable outputs The PC4204 connects to the COMBUS via four w...

Страница 4: ...indicators 8 4216 modules with 16 outputseach Switched Auxiliary Output Programmable for 1 of 23 options Supervised Alarm Output Bell Output 700 mA fused at 5 Amps 12 VDC unregulated Steady or Pulsed Output Programmable for 1 of 23 options Event Buffer 512events Date and time stamp 8 True Partitions Separate or shared zones from other partitions Individual keypads per partition minimum 1 keypad In...

Страница 5: ... to an on site printer that will record the identity of the system description of the occurrence alarm trouble etc arm disarm by user date and time The PC4216 module provides up to 16 programmable outputs each of which may be programmed to trigger on up to 21 different options It is also used to display zones on a graphic annunciator When used in this manner all 16 outputs must be used to display ...

Страница 6: ...ition 1 Enroll every module to the system Make sure you put down the number of each module enrolled Refer to the ProgrammingManualfortherequiredprocedure When enrolling any PC4108 or PC4116 zone expander module make sure to note the zones which you assigned to the module This information is very important if it becomes necessary to Add or Delete zones to or from a Partition Zones 1 through 16 are ...

Страница 7: ...elephone cord into the RJ31 X jack If a DTS 1 is being used to monitor communicator transmissions connect it to the telephone line and place the DTS 1 in the line mode by pressing the red LINE LOCAL button Arm the panel wait for the exit delay to expire and trip a detector on an instant circuit Wait for the communication to complete Disarm the panel and check with the monitoring station to confirm...

Страница 8: ......

Страница 9: ... frequency Switched Auxiliary Supply Output Programmable for several options Battery 12 volt 4 Ah minimum rechargeable gel cell or sealed lead acidbattery Transformer 16 5 VAC 40VA Output Voltage Typically with normal AC on and a fully charged battery the output voltage will be 13 8 VDC With AC off and the battery discharging the voltage will go below 10 volts and then battery cutoff will occur pr...

Страница 10: ......

Страница 11: ...d 1 5 Amp output PC4216 Low Current Output Module 16 output low current module Up to 9 modules on system 1 module programmable for all 16 outputs 1 of 23 options for each 8 modules programmable as alarm annunciators or zone followers Four wire QUAD hook up to COMBUS Nominal current draw of 35 mA Provides Tamper and Trouble Reporting Codes Low COMBUS supervision to PC4000 Main Board PC4400 RS 232 I...

Страница 12: ......

Страница 13: ...11 ...

Страница 14: ...12 ...

Страница 15: ... is a 3A maximum switch to ground A small relay a buzzer or other DC operated device may be connected between the 12 VDC AUX positive terminal and the PGM switched negative terminal to interface with controlled devices COMBUS Terminals RED BLK YEL and GRN Connect the red wire of the COMBUS to the RED terminal the black wire to the BLK terminal the yellow wire to the YEL terminal and the green wire...

Страница 16: ......

Страница 17: ...Codes are used for arming and disarming the control panel for viewing the armed disarmed status of the partitions for programming additional security codes and for entering user functions In the disarmed state entering a Master Code will cause a nine selection menu to be displayed as follows 0 Arm Partition 1 Arm Diff Part 2 Disarm Diff Part 3 View Partitions 4 Set System Time 5 Set System Date 6 ...

Страница 18: ...ad buzzer will stop The correct security code must be entered before the allowed entry time expires To change the entry time see Installers Programming Command 8 If an alarm occurred while the panel was armed the View Memory message will be on the display with the zone name for the zone that caused the alarm The display will keep those messages on for two minutes or until the key is pressed to ret...

Страница 19: ...tored Initiating a bell comm test will check the battery voltage AC Trouble There is no audible annunciation on AC power failure The system Trouble light will come ON but the audible indication will not sound until there is a low battery condition Transmission delay can be programmed for 000 to 255 minutes Aux Supply Troub An Aux trouble is generated if the aux fuse on the main panel opens or if t...

Страница 20: ...o program additional access codes of any type The PC4000 has 128 access codes In the Installer s Programming Section these codes are divided up and assigned to partitions or are turned into System Master Codes which have control over all partitions This must be done before the user can program the access code and the code type The first code is the System Grand Master Code Only the Installer can c...

Страница 21: ...de When selected the keypad will display Enter Digits and what is currently programmed for that access code Enter in the 4 digit code Do not press or while entering the access code If you do not wish to change the code use the keys to exit When you have finished entering the code if you are programming System Master codes the keypad will return to selecting which System Master code to program If y...

Страница 22: ...Auto Arm Upon selecting the Auto Arm Control function the Auto Arm Control menu will appear on the LCD keypad 0 Auto Arm 1 Auto Arm Time Auto Arm toggles Y or N to enable or disable the Auto Arm function Auto Arm Time is the time the partition will automatically arm itself every day NOTE The Auto Arm time is a 24 hour clock and times must be entered as two digit numbers E g HH 01 02 10 11 23 24 MM...

Страница 23: ...long the outputs are activated and see Util Req Code for programming whether a utility output requires an access code to be activated Installers Programming Commands 8 Installer sCode The PC4000 is completely programmed from the keypad by using commands in the 8 section The commands are described in detail in the Programming Manual At home Arming 9 AccessCode Entering 9 before the arming code arms...

Страница 24: ......

Страница 25: ...r end into the DB 25 modular jack adapter Connect the DB 25 modular jack into the RS232 serial port of the printer See the PC4400 wiring diagram Power up the printer then the PC4000 and PC4400 If the PC4400 is already enrolled and the printer is on line the PC4400 will begin transmitting to the printer The following is a sample of a printout from the serial printer Partition Label Date Time Event ...

Страница 26: ...emory until they are ready to be printed When the printer is brought back on line the PC4400 will send the new events to the printer If 384 new events occur before the printer is brought back on line 384 events 75 of the buffer the PC4000 will send the Buf Near Full reporting code to the monitoring station See Maint Rep Codes in the Programming Flow Charts for programming the Buf Near Full reporti...

Страница 27: ...nected to the tip and ring terminals on the panel A DTS 1 must be connected to the lines and in the local mode Program the downloading access code and panel I D code Program a zone for Forced Answer See Zone Type in the Programming Guide This zone is only meant to be temporary to initiate downloading It can later be changed back to the required zone type Make sure the access code and panel I D cod...

Страница 28: ...is and shall be in lieu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Digital Security Controls Ltd This warranty contains the entire warranty Digital Security Controls Ltd neither assumes nor authorizes any other person purporting to act on its behalf to modify or to change this warranty nor to assume for it any other warra...

Страница 29: ... 1993 Digital Security Controls Ltd Toronto Canada Tel 800 387 3630 FAX 905 760 3034 ...

Страница 30: ...29000223R0 ...

Страница 31: ...amming Work Sheets Used by the installer to record installer s programming and system layout Book 3 PC4000 Programming Manual Explains each section of installer s programming Book 4 PC4000 System Manual Introduces the PC4000 explains the hookup and wiring and user s programming and functions 1 PC4000 Main Control Board 1 LCD4500 Remote Keypad 1 Main Control Cabinet 1 Hardware Package EOL Resistors...

Страница 32: ...icated with the monitoringstation 10 European Pulse Dialing Page 24 An option to use American pulse dialing or European pulse dialing 11 Second Master Reporting Codes Page 27 The Second Grand Master Access Code now has its own opening and closing reporting codes when it is used to arm and disarm 12 PC4216 Zone Follower Option Page 30 The PC4216 can follow any group of 16 zones When a zone is open ...

Отзывы: