![DSC Power608 Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/dsc/power608/power608_installation-manual_2534729009.webp)
G e t t i n g S t a r t e d :
2 . 5 K e y p a d A s s i g n m e n t
5
•
PC59X1EXT/R Door Box Audio Station: 35mA
•
PC5904 Central Station Talk/Listen Module: 30mA
standby, 130mA max.
Other Devices
Please read the manufacturer’s literature carefully to deter-
mine the maximum current requirements for each device—
during activation or alarm—and include the proper values for
loading calculations. Connected devices must not exceed
system capabilities during any possible operational mode.
2.5
Keypad Assignment
There are eight available addresses for keypads. LED key-
pads by default are always assigned to address 1. LCD5500Z
keypads are always assigned to address 8. You will need to
assign each keypad to its own address (1 to 8). Keypad
assignment is required, as it tells the panel which addresses
are occupied. The panel can then generate a fault when a
keypad supervisory is not present.
NOTE: One LCD keypad must be assigned to address 8 in
order to upload keypad programming using DLS-1 software.
How to Assign Keypads
Do the following at each keypad installed on the system:
1. Enter [*][8][installer’s code] to go to installer programming
2. Enter [000] for Keypad Programming
3. Enter [0] for Address Assignment
4. Enter a two digit number (11-18) to specify which supervi-
sory address the keypad will occupy.
5. Press [#] twice to exit installer programming.
After assigning all keypads, perform a supervisory reset by
entering section [902] in installer’s programming. The panel
will now supervise all assigned keypads and enrolled modules
on the system.
How to Program Function Keys
By default, the 5 function keys on each keypad are pro-
grammed as Stay Arm (03), Away Arm (04), Chime (06), Sen-
sor Reset (14) and Quick Exit (16). You can change the
function of each key on every keypad:
1. Go to the keypad where you want to change the function
key programming and enter Installer Programming.
2. Press [000] for Keypad Programming.
3. Enter [1] to [5] to select a function key to program.
4. Enter the 2 digit number, [00] to [21] to select the feature
you want the function key to have. For a complete list of
Function Key options see section 3.5
5. Continue from step 3 until all function keys are pro-
grammed.
6. To exit Installer Programming, press [#] twice.
2.6
Supervision
By default, all modules are supervised upon installation.
Supervision is enabled at all times so that the panel can indi-
cate a trouble if a module is removed from the system.
To check on which modules are currently connected and
supervised, enter programming section [903] from installer’s
programming. The LCD keypad will allow you to scroll through
the display of connected modules. A connected module
which does not show as being present will appear as a trouble
condition and the Trouble light on the keypad will turn ON.
This condition may be due to one or more of the following rea-
sons:
•
the module is not connected to the Keybus
•
there is a Keybus wiring problem
•
the module is more than 1,000'/305m from the panel
•
the module does not have enough power
For more information regarding module supervision troubles,
please refer to
“[*][2] Trouble Display” on page 8.
2.7
Removing Modules
The panel must be instructed to no longer supervise a module
being removed from the system. To remove the module, dis-
connect it from the Keybus and reset the supervision field by
entering [902] in the installer’s programming. The panel will be
reset to recognize and supervise all existing modules on the
system.
2.8
Zone Wiring
For a complete description of the operation of all zone types,
please refer to section 5.2
“Zone Programming” on page 14.
There are several different ways in which zones may be wired,
depending on which programming options have been
selected. The panel can be programmed to supervise nor-
mally closed, End of Line, or Double End of Line loops. Please
refer to the following diagrams to study each type of individu-
ally supervised zone wiring.
NOTE: Any zone programmed for Fire or 24 Hour Supervisory
must be wired with a single End of Line (EOL) resistor regard-
less of the type of zone wiring supervision selected for the
panel (section [013]: [1] -[2]). See section 5.2
NOTE: If you change the zone supervision options from DEOL
to EOL or from NC to DEOL (section [013], options [1] or [2]),
you should power down the system completely, and then
power it back up. If you do not, the zones may not work cor-
rectly.
Normally Closed (NC) Loops
To enable normally closed loops, programming section [013],
option [1] must be ON.
NOTE: This option should only be selected if Normally Closed
(NC) detection devices or contacts are being used.
Single End Of Line (EOL) Resistors (5600
Ω
)
To enable panel detection of single end of line resistors, pro-
gramming section [013], options [1] and [2] must be OFF.
Содержание Power608
Страница 4: ...ii PC5008 Wiring Diagram...
Страница 50: ...46 NOTES...