24

If the 

AC/DC Inhibit Arming

 option is disabled, the panel will

not do an automatic battery test when arming is attempted
and the user will not be prevented from arming the system
when there is an AC or battery trouble.
If you enable the 

Unidentified Wireless Key Disarming

option, the disarm button 

will work on wireless keys which

have not been assigned access codes. Wireless keys can
only be assigned access codes when used with PC5132 v3.0
or higher. 
To prevent disarming by wireless keys which don’t have
access codes, 

disable this option. (Please see your PC5132

manual for more information on programming wireless keys.)

NOTE:This option must be enabled when using a PC5132 v2.1 
or earlier. 

Quick Arm Enable . . . . . . . . . . . . . . . . . . . . Section [015]: [4] 
Quick Exit Enable  . . . . . . . . . . . . . . . . . . . . Section [015]: [3]
Arm/Disarm Bell Squawk. . . . . . . . . . . . . . . Section [014]: [1]
Closing Confirmation . . . . . . . . . . . . . . . . . . Section [381]: [4]
Opening After Alarm Keypad Ringback . . . Section [381]: [1]
Opening After Alarm Bell Ringback  . . . . . . Section [381]: [2]
Bypass Status Displayed While Armed. . . . Section [016]: [7]
AC/DC Inhibit Arming  . . . . . . . . . . . . . . . . . Section [701]: [3]
Unident. Wkey Disarm Enabled  . . . . . . . . . Section [017]: [1]

5.18 Entry/Exit Delay Options

Two different 

Entry Delays

 can be programmed: the first entry

delay will be enabled for Delay 1 type zones and the second
for Delay 2 type zones. Only one 

Exit Delay

 can be pro-

grammed.

NOTE:When the panel is armed, the entry delay will follow the 
entry delay time programmed for the delay zone which is vio-
lated first.

Upon arming, the panel will begin the exit delay. If the 

Audible

Exit Delay with Urgency

 option is enabled, the keypad will

beep at one second intervals until the exit delay expires. The
keypad will beep rapidly for the last 10 seconds of exit delay
to warn the user that the system is about to arm. If this option
is disabled, the keypad will not beep during the exit delay.
The 

Audible Exit Fault

, as explained in section 3.1 

“Arming

and Disarming” on page 7, will notify the user if they failed to
secure the premises upon arming. This option can be enabled
or disabled according to the user’s needs.
For commercial applications, the 

Bell Squawk on Exit Delay

option may be enabled. The panel will squawk the alarm out-
put once every second when the exit delay is initiated and
three times per second for the last 10 seconds until the exit
delay expires.

NOTE:The bell will not squawk when the panel is Stay or No-
entry armed.

Upon entry, if a Delay type zone is violated, the panel will
begin the entry delay. The keypad will emit a steady tone. The
keypad will pulse the keypad sounder during the last 10 sec-
onds to warn the user the system is about to go into alarm. If
there was an alarm during the armed period, the keypad will
pulse for the entire entry delay to warn the user of the previous
alarm.
For commercial applications 

Bell Squawk on Entry Delay

may be enabled. The panel will squawk the alarm output once
every second until the entry delay expires or the system is dis-
armed. 

If the 

Bell Squawk During Auto Arm

 option is enabled, the

bell will squawk once every 10 seconds for one minute during
the Auto-arm pre-alert. This will notify anyone on the premises
that the system is being armed.
If the 

Exit Delay Termination

 option is enabled, the panel will

monitor the Delay zones during exit delay. During the exit
delay, if a Delay type zone is violated and then secured, the
exit delay will be terminated and the panel will be armed
immediately.

Entry Delay 1 and 2 (System Times). . . . . . . . .  Section [005]
Exit Delay (System Times)  . . . . . . . . . . . . . . . .  Section [005]
Audible Exit Delay with Urgency  . . . . . . . . Section [014]: [6]
Audible Exit Fault Enabled/ Disabled . . . . . Section [013]: [6]
Bell Squawk Options. . . . . . . . . . . . . .  Section [014]: [2] - [4]
Exit Delay Termination. . . . . . . . . . . . . . . . . Section [014]: [7]

5.19 Swinger Shutdown

The swinger shutdown feature is designed to prevent a “run-
away” communicator from tying up the central station. After
the panel has communicated the programmed number of
transmissions for an event, it will no longer report that event
until the swinger shutdown is reset. Different swinger shut-
down levels can be set for zone alarms, zone tampers and
maintenance signals.
By default, each swinger shutdown limit is set to [003]. The
panel will not send more than three signals for each zone until
the swinger shutdown is reset.
The Bell output will not be activated for alarms on zones that
have exceeded the limit of alarms set in the Swinger Shut-
down counter.
Swinger shutdown will be reset every day at midnight or when
the panel is armed. Once reset, the panel will again communi-
cate normally.

Swinger Shutdown  . . . . . . . . . . . . . . . . . . . . . .  Section [370] 

5.20 Event Buffer

The panel will store the last 128 events which occurred on the
system. The event buffer will contain the name, time and date
of each event, along with the zone number, access code num-
ber or any other information pertaining to the event.
If the 

Event Buffer Follows Swinger Shutdown

 option is

enabled, the Event Buffer will not store events after the
Swinger Shutdown level has been reached. This will prevent
the panel from overwriting the entire buffer if a problem exists.
The event buffer can be viewed in three different ways: from
an LCD keypad (se

“[*][6] User Functions” on page 9),

printed on-site using the PC5400 printer module, or it can be
uploaded using DLS software.

Event Buffer Follows Swinger Shutdown. . . Section [013]: [7]

5.21 Keypad Lockout Options

The panel can be programmed to “lock out” keypads if a series
of incorrect access codes are entered. Once the 

Number of

Invalid Codes Before Lockout

 limit has been reached, the

panel will lock out all keypads for the lockout duration and log
the event to the event buffer. For the duration of the lockout, the
panel will sound an error tone when any key is pressed.

NOTE: The Invalid Code Counter will be reset every hour.

Содержание Power608

Страница 1: ...manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC5008...

Страница 2: ...ces or passing traffic Audible warning devices however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are used to transmit alarms they may be out of service or b...

Страница 3: ...5 Program Descriptions 14 5 1 Programming Security Codes 14 5 2 Zone Programming 14 5 3 Zone Attributes 15 5 4 Assigning Keypad Zones 16 5 5 Communicator Dialing 16 5 6 Communicator Account Numbers 17...

Страница 4: ...ii PC5008 Wiring Diagram...

Страница 5: ...t in piezoelectric buzzer Digital Communicator Specifications Supports major communication formats including SIA and Contact ID Event initiated personal paging Three programmable telephone numbers Two...

Страница 6: ...the PC5928 Audio Interface Module PC5921 EXT Door Box Audio Station Used in conjunction with the PC5928 Audio Interface Module PC5921 EXT R Door Box Audio Station Used in conjunction with the PC5928...

Страница 7: ...out the Programming Worksheets completely before attempt ing to program the system Step 10 Testing the System Test the panel thoroughly to ensure that all features and func tions are operating as pro...

Страница 8: ...These lines may incorporate a voice filter which dis connects the line if anything other than fax signals are detected resulting in incomplete transmissions 2 3 Keybus Operation and Wiring The Keybus...

Страница 9: ...les are supervised upon installation Supervision is enabled at all times so that the panel can indi cate a trouble if a module is removed from the system To check on which modules are currently connec...

Страница 10: ...one input to which a device such as a door contact can be connected This eliminates the need to run wires back to the control panel for every device To install the keypad open the keypad plastic by re...

Страница 11: ...ing Stay arming please see section 3 5 Function Keys on page 10 3 3 Automatic Arming The system can be programmed to Auto Arm at a specific time every day if it is in the disarmed condition In order f...

Страница 12: ...odule being powered by a PC5204 you must also remove and then restore power to the PC5204 and any connected modules This ensures that any troubles present on the module are correctly logged and or ann...

Страница 13: ...ult These settings can be changed Access Code Attributes There are three access code attributes which can be pro grammed for each code To program each attribute enter 5 Master Code 9 to enter the attr...

Страница 14: ...the panel will ignore only one activation of a Delay zone When the Delay zone is secured the panel will end the two minute quick exit delay If a second Delay zone is tripped or if the zone is not res...

Страница 15: ...anual NOTE This function key cannot be programmed for PC55XX LED keypads with software version 1 0 19 7 3 Command Output Option 3 A valid access code may need to be entered 20 For future use 21 7 4 Co...

Страница 16: ...the key to exit the section Select that section again and re enter the information correctly NOTE There must be one digit in each box in the program ming section in order for the change to be valid 4...

Страница 17: ...y pad When a programming section is entered the keypad will immediately display the first digit of information programmed in that section The keypad displays the information using a binary format acco...

Страница 18: ...ry time expires no alarm will be generated 02 Delay 2 Zone The Delay 2 entry delay time can be set independently of Delay 1 in programming section 005 System Times 03 Instant Zone This zone type will...

Страница 19: ...e trouble 23 Maintained Keyswitch Arm Zone When this zone is violated the system will arm When this zone is secured the system will disarm Tampers and faults will not arm disarm the system but only ac...

Страница 20: ...in and search for a dial tone for 5 seconds d the panel will then dial regardless of the presence of dial tone If there is no initial handshake recognized within 40 seconds the panel will then hang up...

Страница 21: ...ed to report events to the central station by sending the Reporting Code programmed for a par ticular event Reporting codes can be one or two digits and can use HEX digits A through F For a complete d...

Страница 22: ...Section 361 to 368 The following is a description of each reporting format Pulse Formats Depending on which pulse format is selected the panel will communicate using the following specifications 3 1 3...

Страница 23: ...e pager once Once the appro priate telephone number is dialed the panel will send the account number and Reporting Code followed by the key Hex C The panel has no way of confirming if the pager was ca...

Страница 24: ...ted Call Up option is enabled the user can have the panel initiate a call to the downloading computer by pressing 6 Master Code 6 The Download Access Code and Panel Identifier Code are for security an...

Страница 25: ...ed to indicate that an alarm has occurred before entering the premises The PGM attributes for this option programmed in Sections 141 to 154 differ from the standard selection of attributes Program whi...

Страница 26: ...outputs PGM attributes return to their default settings when you change PGM output options Please see the programming worksheets for a list of the default settings for each PGM out put type Care shou...

Страница 27: ...me expires Communication of the signal to central station is immediate If the A Key is pressed and held for two seconds the panel will sound the keypad beeps three times to verify activa tion The pane...

Страница 28: ...al applications Bell Squawk on Entry Delay may be enabled The panel will squawk the alarm output once every second until the entry delay expires or the system is dis armed If the Bell Squawk During Au...

Страница 29: ...estoral Reporting Codes Section 338 System Tampers Req Installer Reset Section 701 4 NOTE After enabling keypad tampers it is recommended to tamper and restore all keypads to ensure proper functioning...

Страница 30: ...5 31 Installer s Lockout If Installer s Lockout is selected a hardware default cannot be performed If a software default is performed all program ming will restore to factory default If Installer s L...

Страница 31: ...________________________________________________________________________________________________I Keypad 7 I_____________________________________________I I____________________________________________...

Страница 32: ...Keypads must be installed to use 24 hour Buzzer zones 001 Zone 1 8 Definitions Section 5 2 Zone Programming on page 14 Default Default 01 I_______I_______I Zone 1 04 I_______I_______I Zone 5 03 I____...

Страница 33: ...Status 05 System Armed Status 18 Stay Armed Status 06 Ready To Arm 19 Command Output 1 7 1 07 Keypad Buzzer Follow Mode 20 Command Output 2 7 2 08 Courtesy Pulse 21 Command Output 3 7 3 09 System Tro...

Страница 34: ...Arm Disarm Bell Squawk disabled 5 17 23 OFF I________I 2 Bell Squawk During Auto Arm No Bell Squawk During Auto Arm 5 18 24 OFF I________I 3 Bell Squawk On Exit Delay No Bell Squawk On Exit Delay 5 1...

Страница 35: ...Contact I D Partial Close Identifier is 5 Partial Close Identifier is 4 5 9 18 OFF I________I 5 8 For future use 020 Keypad Zone Assignments Section 2 11 Keypad Zones on page 6 NOTE Only one keypad m...

Страница 36: ...ion 001 Attribute 1 2 3 4 5 6 7 8 ON Audible Steady Chime Bypass Force Swing Tx Delay Wireless Zn OFF Silent Pulsed No No No No No No Zone Type 00 Null Zone N N N N N N N N 01 Delay 1 Y Y Y Y N Y N N...

Страница 37: ...1 11 I________I I________ I________ I________ I________ I________ I________ I________I 152 12 I________I I________ I________ I________ I________ I________ I________ I________I 153 13 I________I I_____...

Страница 38: ...nd Telephone Number 32 Digits Section 5 7 Communicator Telephone Numbers on page 17 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_...

Страница 39: ..._____I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I 342 Code 25 Code 26 Code 27 Code 28 Code 29 Code 30 Code 31 Code 32 I_______I_______I I_______I...

Страница 40: ..._____I General Zone Trouble Alarm I_______I_______I General Zone Trouble Restore I_______I_______I For future use 352 Test Transmission Reporting Codes Section 5 8 Communicator Reporting Codes on pg 1...

Страница 41: ...5 23 030 I_______I_______I_______I AC Failure Communication Delay 001 255 minutes 5 8 17 003 I_______I_______I_______I TLM Trouble Delay No of checks required valid entries 003 255 5 12 22 030 I______...

Страница 42: ...indow OFF I_______I 3 Call Back Enabled Call Back Disabled OFF I_______I 4 User initiated Call up Enabled User initiated Call up Disabled OFF I_______I 5 8 For future use 402 Downloading Computer s Te...

Страница 43: ...line Test Transmission in minutes Land line Test Transmission in days 5 14 23 OFF I_______I 4 1600 Hz Handshake Standard Handshake 5 9 18 OFF I_______I 5 ID Tone enabled ID Tone disabled 5 5 16 OFF I_...

Страница 44: ...BAD 3 Beeps Squawks 990 Installer Lockout Enable Section 5 31 Installer s Lockout on page 26 991 Installer Lockout Disable Section 5 31 Installer s Lockout on page 26 993 Restore LINKS2X50 Factory De...

Страница 45: ...der Supervisory Alarm Rest panel loses restores supervisory transmission over the Keybus from enrolled PC5132 module or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm t...

Страница 46: ...T 00 UJ 00 352 Periodic Test periodic system test transmission T 6 A2 RP 00 352 System Test 6 bell communications test T 6 A1 RX 00 352 LINKS Test LINKS test transmission T 6 A3 TX 00 353 Wireless Dev...

Страница 47: ...one 5 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default Zone 6 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default...

Страница 48: ...bled ON I_______I 2 A uxiliary Keys enabled A uxiliary Keys disabled ON I_______I 3 P anic Keys enabled P anic Keys disabled OFF I_______I 4 8 For future use 65 Fourth User Display Mask Default Option...

Страница 49: ...Label Broadcast All LCD programming is done per keypad If more than one LCD keypad are present on the system and the PC5400 receives labels labels pro grammed at one keypad can be broadcast to all oth...

Страница 50: ...46 NOTES...

Страница 51: ...6 of the Telecommunications Act 1981 6 It is important that the installer verifies the correct operation of stored telephone numbers subsequent to their entry 7 The connection to this equipment consis...

Страница 52: ...e 18 New PGM Output Type 26 Battery Test See 5 11 PGM Output Options on page 20 New Zone Types 27 Push to Set 28 24 Hr Bell Buzzer See 5 2 Zone Programming on page 14 New Options Troubles are Latching...

Отзывы: