P r o g r a m m i n g Z o n e D e f i n i t i o n s i n t h e P a n e l
15
5.2 Programming Zone Definitions in the Panel
In addition to programming the zone definitions in each PC5502Z2 keypad, you must
also program a zone definition in the main control panel so that the system can effec-
tively monitor each PC5502Z2.
1. At the system keypad (
not the PC5502Z2 keypad
), enter Installer’s programming
([*][8][Installer’s code]).
2. Enter one of programming sections [001] - [004], depending on the zone number of
the PC5502Z2 keypad:
Enter section:
For system zones:
[001]
01 - 08
[002]
09 - 16
[003]
17 - 24
[004]
25 - 32
3. In each zone programming section there are eight data entry sections, one for each
system zone. For each PC5502Z2 zone, enter a 2-digit zone definition. We recom-
mend that you program each PC5502Z2 keypad zone as a 24 Hour Burglary zone
(11). This will ensure that alarm information from the PC5502Z2 keypad will cause
an instant system alarm.
To skip a data entry section, press both
keys (LED keypad), or scroll using the [>]
key (LCD keypad).
For example, to program system zone 03 in section [001], press [>] or both
keys
to skip the first two data entry sections. Enter the zone definition in the next section.
To exit, press [#].
NOTE
: If you program 24-hour Supervisory Buzzer zones, then when the supervisory
buzzer sounds users will not be able to arm the PC5502Z2 until a valid access code is
entered on the system keypad.
4. When you are finished programming system zone definitions, press [#] to exit.
Record your programming choices in the Programming Worksheets.