4.1 Program Zones and Partitions
Now that you have enrolled the wireless devices, you should complete all zone
programming on the system. Although the exact programming required varies
depending on which control panel the PC5132-RS is connected to, you should
check that the following programming areas are completed correctly for each
wireless zone:
• Enable zones and/or assign zones to one or more partitions (programming
sections [201]-[209]).
• Program the definition for each zone(programming sections [001]-[004]).
NOTE: WLS906 wireless smoke detectors must be assigned to zones defined
as Delay 24-hr fire (wireless) [87] or Standard 24-hr fire (wireless) [88] for proper
supervision.
• Enable the wireless zone attribute for each wireless zone (PC585, PC1565,
PC5008, PC5010 v2.0 and up, PC5015 v2.2 and up only)(programming
sections [101]-[132]).
See your system Installation Manual, for more information on each of the above
programming sections.
4.2 Enable PC5132-RS Supervision
The control panel will automatically supervise the PC5132-RS receiver via the
Keybus one-minute after at least one device has been enrolled on the module.
The system will generate a General System Supervisory trouble if the module is
removed from the Keybus. If you need to remove the PC5132-RS module from
an existing system, you will have to disable supervision of the PC5132-RS.
To disable PC5132-RS supervision:
1. Disconnect the PC5132-RS from the Keybus
2. Enter [
✱
][8][Installer Code]
3. Enter [902]. The control panel will clear all supervision and re-scan the
system for connected modules. The scan will take approximately one
minute.
4. To exit press [#].
To review which modules the control panel is currently supervising:
1. Enter [
✱
][8][Installer’s Code]
2. Enter [903] to display all modules. On LED keypads, light [17] will
indicate that the PC5132-RS is present on the system. On keypads, scroll
until the module name appears on the display.
3. To exit press [#].
If the PC5132-RS module does not show on the keypad, one of the following
conditions may be present:
• the module is not connected properly to the Keybus
• there is a problem with the Keybus wiring run
• the module does not have enough power
• no devices have been enrolled on the PC5132-RS