20
PC1500 and PC1550 Control Panels
The DSC PC1500 or PC1550 must be equipped with software version 4.0 or later.
Section [24]
Programmable Output Options. Program “0C” in this section to enable LINKS operation. When
“0C” is programmed, Zone 6 will be automatically configured for LINKS operation.
Section [35]
LINKS1000 Test Reporting Code. Program a 2-digit reporting code in the range of “00” through
“FF” in this section. Cellular communications through the LINKS module will be tested
periodically according to the Test Transmission Cycle Time and Test Transmission Time of Day
programmed in Sections [17] and [19].
PC1575 and PC1580 Control Panels
The DSC PC1575, PC1580 control panel must be equipped with software version 1.0 or later.
Section [01]
Choose a zone for LINKS supervisory and program in Zone Definition ‘09’.
Section [06]
Programmable Output Options. Enter ‘16’ in this section to enable LINKS operation for PGM1.
If Downloading via cellular is to be used, then enter ‘30’ for PGM2, otherwise program PGM2
as desired or hit ‘#’ to exit. Only PGM1 supports LINKS operation and only PGM2 supports
LINKS answer.
Section [36]
Program the Alarm Reporting Code for the LINKS Supervisory Zone. The restoral code is in
section 37.
Section [43]
Program reporting code for TLM (telephone line monitor). The restoral code is in section 44.
The restoral will not be sent via LINKS.
Section [46]
Program Test Transmission Reporting Code.
Section [51]
Program Call Direction for sending alarms. Minimal setting for LINKS operation is option 3 ‘ON’.
Section [52]
Program Call Directions for tamper alarm and restorals. Default is ‘Disabled’.
Section [53]
Program Call Directions for Openings and Closings. Default is ‘Disabled’
Section [54]
Program Call Directions for System Maintenance Alarms. Default is ‘Disabled’
Section [55]
Program Call Directions for System Test Transmission. Minimum setting for LINKS operation
is option 3 ‘ON’.
Section [61]
Program Second Communicator Option Code. Default is ‘LINKS used as land-line back-up
communications only’.
Section [62]
LINKS Test Transmissions will follow System Test depending on programming in section
- [63]
[46] & [55].
Section [67]
Program LINKS1000 Preamble. See Preamble section of manual page 15. Section [68] &
[69] used for second and third Preamble numbers.
PC2525 Control Panel
The DSC PC2525 control panel must be equipped with software version 1.0 or later.
Section [01]
Zone Definitions. Program the second digit for the zone connected to the LINKS RING terminal
as “B” to enable the Forced Answer feature. This will allow downloading functions to be
performed through the LINKS module.
Section [06]
Programmable Output Options. Program the Programmable Output Option as [09].
Section [41]
LINKS Maintenance Reporting Codes. Program two 2-digit codes in this section. The first
code is the Telephone Line Monitor Code, and the second code is the LINKS Test
Transmission Code.
Section [47]
LINKS Preamble (First Telephone Number). See preamble section for programming information.
Program all unused digits with hexadecimal “F”.
Section [48]
LINKS Preamble (Second Telephone Number).
Section [76]
LINKS Preamble (Downloading Telephone Number).