SIA Feature
Programming Section
Comments
Range/Default
Requirement
Cancel Annunciation
Panel Settings>Panel Con-
figuration>System Configuration>
> Reporting
Access to the reporting code for Alarm
Canceled
Annunciate that a Cancel
was transmitted. Default:
Enabled
Required
Duress Feature
Do not derive code from an existing
Master/User code (e.g., Master code is
1234, the duress code should not be
1233 or 1235)
No automatic derivative of
another user code. No
duplicates with other user
codes
Default: Disabled
Allowed
Cross Zone Timer
Panel Settings>Panel Con-
figuration>Partition Configuration
>Cross Zone Delay
Access to the programmable Cross Zone
timer
May program Range: 001-
255 seconds. Default: 0
seconds
Allowed
Swinger Shutdown for Alarms
Panel Settings>Zones> Swinger
Shutdown
Access to the swinger shutdown limit for
zone alarms.
For all non-fire zones shut-
down at 1 or 6 trips
Default: 2 trips
Required
(programmable)
24 hour auto verified Fire
Access to 24 hour auto verified Fire
Activates If a restore is Not
received within the spe-
cified time Default: dis-
abled
Required
System Test:
Panel Settings> Dia-
gnostics> Sys-
tem>System Test
The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn
on. Refer to the User Manual.
Panel Settings> Dia-
gnostics> System>
Device> Begin Walk
Test
This mode is used to test each zone on the system for proper functionality.
For SIA CP-01 compliant installations, the minimum configuration is:
1) Control Panel: Model WS900-29, WS900-19
2) Annunciators for progress: Model WS900-29, WS900-19, PG9901, PG9911
3) Off Premise Transmission: Model WS900-29, WS900-19
4) Local alarm bell: WS900-29, WS900-19, PG9901, PG9911
5) Smoke Detector: Model PG9926, PG9916
6) Arming Device: Model WS900-29, WS900-19, PG9929, PG9939, PG9949
- 60 -