HSPA(3G)/Dual Alarm Communicator Installation Manual

4. Move the extension antenna to various locations while observing the two green LEDs on the

panel. 

a. Continue to reposition the extension antenna until you receive an acceptable (minimum one

green LED ON solid) signal strength.

NOTE: 

Minimum strength is: 

 green LED 1 flashing and 

 yellow LED off. If green LED 1 is 

flashing, relocation should be considered.

b. Mount the supplied antenna extension bracket at the location that provides the best signal

strength.

5. Alternately, reposition the panel to improve signal strength. Dismount the panel and move it to

another location to achieve the required signal strength. If the panel is relocated to improve sig-

nal strength, mount it in the new location.

6. When final panel/antenna location is determined, continue at the 

Initial Panel Programming-

section.

NOTE: 

If the SIM card is not activated, placement test will indicate the signal strength of the 

nearest cellular tower.

NOTE: 

In between displaying signal strength, the signal strength LEDs will flash alternately if an 

inactive SIM card is used. The flashing indicates that the module is attempting to attach to 

the cellular network and will only last briefly. 

 



Domain Name Service (DNS) programming is not permitted in UL/ULC listed systems.

HS2016/2032/2064/2128 Initial Programming

For detailed information, refer to panel manual section ‘Alternate Communicator Set-up’.
1. In panel section [

377

] ‘Communication Variables’, subsection 

[002]

 ‘Communication Delays’,

sub-subsection 

[1]

 ‘Communication Delay’, program 

060

 (seconds).

2. In panel section [

382

] ‘Communicator Option 3’ set option [

5

] ON.

3. In panel sections [300] subsections [001] to [004], program the subsection with 02 to 06.

NOTE: 

Refer to panel manual for additional information 

4. In panel section [350] ‘Communication Formats’, program the communication format as: CID

(03) or SIA FSK (04). 

5. In panel sections [311] - [318] ‘Partition Call Directions’, program the call direction options for

the system.

6. In panel section [401] ‘DLS/SA Options’, set toggle option [2] ‘User Enable DLS’ to 

ON

 in

order to perform panel DLS session through cellular or Ethernet.

NOTE: 

Before leaving the premises, the installer should verify all programmed communications 

paths. See programming options section [851][901] to send immediate test transmissions.

Communicator Troubles displayed on a HS2016/2032/2064/2128

The communication trouble is the only trouble that will appear on the keypad Liquid Crystal Dis-

play (LCD) when encountered by a communicator installed in a HS2016/2032/2064/2128. For

I

NITIAL

 P

ANEL

 P

ROGRAMMING

Table 5: Communicator Path Programming

Value

Communication Method

02

Auto Routing

03

Ethernet 1

04

Ethernet 2

05

Cellular 1

06

Cellular 2

Содержание 3G2080

Страница 1: ...HSPA Dual Path Alarm Communicator North America INSTALLATION GUIDE V4 1 For installation manual visit www dsc com Warning This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer ...

Страница 2: ... occupants or their belongings Motion Detectors Motion detectors can only detect motion within the designated areas as shown in their respective installation instructions They cannot discriminate between intruders and intended occupants Motion detectors do not provide volumetric area protection They have mul tiple beams of detection and motion can only be detected in unob structed areas covered by...

Страница 3: ...G R and 3G2080 R throughout this manual apply to all specified models unless stated differently Models ending in R include a built in RS 422 interface for connecting to third party applications The 3G2080 R TL2803G R supports integration over IP and is available with licensed 3rd party product solutions Specific programming for the related programming sections is to be provided by the 3rd party A ...

Страница 4: ...eats sent via cellular and Internet Command and Control via SMS Technical Specifications The input voltage to the Communicator can be drawn from an Underwriters Laboratories Under writers Laboratories Canada UL ULC listed control panel or compatible power supply module such as HSM2204 or HSM2300 NOTE Power supply must be Class 2 power limited UL ULC Installation Requirements NOTE For equipment use...

Страница 5: ...mmercial Burglary applications the TL2803G R can be used as dual signalling line communication system cellular and Ethernet channels used in redundant configuration standard line security and as encrypted line security The supervision heartbeat shall be enabled panel section 851 005 toggle option 1 Ether net and or toggle option 2 cellular shall be ON toggle option 3 supervision type shall be ON a...

Страница 6: ...3G R Only A Category 5 CAT 5 Ethernet cable must be run from a source with Internet connectivity to the communicator module inside the panel The communicator end of the cable must be terminated with an RJ45 plug which will connect to the communicator s RJ45 jack after the communicator is installed All requirements for installation of CAT5 Ethernet cable must be observed for correct operation of th...

Страница 7: ... Reconnect the backup battery and telephone line apply AC power to panel and replace the panel cover Running the RS 422 Cable R models only When installing the communicator for use with 3rd party applications an RS 422 cable must be connected between the 3rd party device and the communicator module NOTE Maximum cable length for RS 422 cable is 1 000 ft 305 m Please refer to the installation manual...

Страница 8: ...See Figure 2 screw Line up the assembled communicator with the right side wall of the panel and using the screw provided secure the mount ing bracket to the panel f Attach the other end of the PC LINK cable to the communicator red wire goes on the right hand pin of the communicator PC LINK header See Figure 3 g Using light pressure finger tight only attach the supplied white quad band whip antenna...

Страница 9: ...her during initialization Do not continue to next step until the red and yellow LEDs have stopped flashing If only the yellow LED is flashing there is a communicator trou ble and the green LEDs are not valid for communicator placement test Correct trouble indicated by flashes on yellow LED before continuing See Table 8 for troubleshooting assistance 7 Perform the communicator placement test below ...

Страница 10: ...nal Strength on page 10 Cellular Signal Strength Display LCD Keypad only The cellular network signal strength can be checked on the keypad LCD screen by entering installer programming section 850 The LCD will indicate the SIM card activation status fol lowed by up to five bars of signal strength This display will automatically update every three sec onds For the relationship between signal strengt...

Страница 11: ...not permitted in UL ULC listed systems HS2016 2032 2064 2128 Initial Programming For detailed information refer to panel manual section Alternate Communicator Set up 1 In panel section 377 Communication Variables subsection 002 Communication Delays sub subsection 1 Communication Delay program 060 seconds 2 In panel section 382 Communicator Option 3 set option 5 ON 3 In panel sections 300 subsectio...

Страница 12: ...n LED will be ON if any of the following occur Ethernet cable is not connected DHCP configuration times out unit fails to get an IP address from the cellular network or Cellular connection has been reset Green LED 1 Green LED 2 and Yellow LED Signal Strength NOTE If the yellow LED is flashing signal strength in table below is not valid See Table 8 for troubleshooting flashing yellow LED COMMUNICAT...

Страница 13: ... RJ45 jack of the com municator and the hub router switch Check the link light on the hub router switch is ON If link light is OFF start the hub router switch If DHCP is used ensure that the unit has an assigned IP address from the server In Section 851 992 verify a valid IP address is programmed If not contact the network administrator If problem persists replace the Ethernet cable and RJ45 conne...

Страница 14: ..._ 003 Ethernet Gateway IP Address Default 000 000 000 000 ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ 004 Receiver Supervision Interval Default 0087 135 Valid range 0000 FFFF ____ ____ ____ ____ 005 System Toggle Options ____ 1 Ethernet Receiver 1 Supervised Default OFF ____ 2 Cellular Receiver 1 Supervised Default OFF ____ 3 Supervision Type Default OFF ____ 4 Primary Communicatio...

Страница 15: ...____ 035 Panel Firmware Update Begin Default FF Program 00 disable or FF enable ____ ____ 036 Panel Firmware Update Successful Default FF Program 00 disable or FF enable ____ ____ 037 Panel Firmware Update Fail Default FF Program 00 disable or FF enable ____ ____ 095 SA Incoming Local Port Default 0000 Valid range 0000 FFFF ____ ____ ____ ____ 096 SA Outgoing Local Port Default 0000 Valid range 00...

Страница 16: ... Receiver 1 Port Default 0BF5 3061 Valid range 0000 FFFF ____ ____ ____ ____ 205 Cellular Receiver 1 APN Default 32 ASCII characters ____________________________________ 206 Cellular Receiver 1 Domain Name Default Programming not permitted on UL ULC listed system 32 Character ASCII characters ____________________________________ Cellular Receiver 2 Options 211 Cellular Receiver 2 Account Code Defa...

Страница 17: ...______________________________ 327 SMS Phone Number 17 ______________________________________________ 328 SMS Phone Number 18 ______________________________________________ 329 SMS Phone Number 19 ______________________________________________ 330 SMS Phone Number 20 ______________________________________________ 331 SMS Phone Number 21 ______________________________________________ 332 SMS Phone ...

Страница 18: ...___ ____ ____ ____ ____ ____ ____ ____ ____ ____ 990 Boot Loader Version ____ ____ ____ ____ ____ ____ ____ ____ 991 Firmware Version ____ ____ ____ ____ ____ ____ ____ ____ 992 Ethernet IP Address ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ 993 Ethernet Gateway Address ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ 994 Cellular IP Address ____ ____ ____ ____ ____ ____...

Страница 19: ...ials any upgrades and this EULA and provided the recipient agrees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT Termination Without prejudice to any other rights DSC may ter minate this EULA if You fail to comply with the terms and condi tions of this EULA In such event You must destroy all copies of the SO...

Страница 20: ...f war ranty Under no circumstances shall Digital Security Controls be liable for any special incidental or consequential damages based upon breach of warranty breach of contract negligence strict liability or any other legal theory Such damages include but are not limited to loss of profits loss of the product or any associated equipment cost of capital cost of substitute or replacement equipment ...

Отзывы: