speedy
Installation
continued...
Weight:
Standard-19g(0.7oz). w/ DIN rail & terminals - 28g(1.0oz)
Power requirements:
Regulated 24VDC ±10%, 40mA. Do not
connect to a distributed DC power network.
Serial port
EIA485(RS485) 0.1 to 500Kbps. Unisolated, power
and serial circuits must have compatible common-mode Voltages.
Ethernet port
MDI 8P8C, “RJ45” jack, 100baseTX, 10BaseT,
Full Duplex, Auto Negotiation, Auto-MDIX, IEEE 802.3ab.
USB port
Peripheral-type Micro-B jack.
Ethernet LEDs
For setup, troubleshooting and monitoring:
100
Green LED indicates 100BaseTX Ethernet connection.
Link / Activity
Yellow LED. On for Link, flashing for activity.
Adhesive Mounting.
Clean adhering surfaces with alcohol first.
Use caution, bond is permanent. Adhere on or near the drive
or EIA485 device. Do not obstruct air vents, access points or
product labels. Do not attach
speedy
near hot spots such as
heatsinks, cooling fans, etc., nor near to AC power lines.
DIN rail option.
Use 35x7.5mm rail per IEC 60715, EN50022.
Terminal wiring:
Strip 7mm(0.28”) or use ferrules. Use
0.2mm
2
(AWG24) minimum. One wire, 2.5mm
2
(AWG12)
maximum. Two wires, 1.5mm
2
(AWG14) maximum. Two
wires with ferrules, 1mm
2
(AWG18) maximum.
Terminal tightening torque:
0.5 Nm (4.4 in
⋄
lbs)
Signal wiring notes. Use twisted-pair wiring.
All wiring
outside of the metal enclosure should be shielded cable with
individually shielded twisted-pairs such as
Belden 8163
.
Ground the shield at only one end with a 360° clamp where
the shield enters your metal enclosure. Separate all wiring
from RF noise sources and AC power cabling.
drive.web automation
speedy
HG503206beta2
www.driveweb.com
Page 5/20