19
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
VAPOR-LOGIC DISPLAY
If your display is factory-mounted and connected to the Vapor-logic board,
proceed to installing the next device required by your system .
If your display was shipped loose, mount the display in a location so that the
provided cable is long enough to connect the display to the Vapor-logic board .
To connect a Vapor-logic display to the Vapor-logic board, insert one end of the
provided cable into the Vapor-logic board at Terminal P10 (labeled Display)
until you hear a click sound (see also the wiring diagram on the next page) .
Plug the other end of the cable into the display . This connection provides DC
power and communication to the display .
See Caution at right before routing cable .
If a longer display cable is needed, order a replacement cable from DriSteem
(see the replacement parts section of this manual), or use a four-conductor
straight-through cable or a six-conductor, crossover, twisted pair cable
connected to an RJ11 jack .
Note required operating conditions listed on Page 3 .
Terminal P10:
Display
INSTALLATION
CAUTION
Touchscreen display cable
Maximum cable length is 500’ (152 m) .
When routing display cable, route
cable away from all power wiring .
Step 1 – Field wiring: Communication connections
FIGURE 19-1: TERMINAL P10
FIGURE 19-2: MOUNT THE TOUCHSCREEN DISPLAY ON A WALL
USING THE WALL PLATE