39
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Table 39-1:
Status screen
Note: Your system might not have all of the items listed in this table (Pages 39 and 42) .
Menu item
Default value
Minimum
value
Maximum
value
Units
Notes
Mode
Standby
--
--
--
Operating mode of humidifier . Choose from Auto, Standby, or Drain .
• In
Auto mode,
the humidifier operates normally . All humidifier
components are monitored and controlled . If there is a call for
humidification, the system reacts .
• In
Standby mode,
the humidifier is offline . All humidity control inputs
appear but are not acted upon; however, if the tank temperature falls
below the freeze protect set point, the drain valve opens .
• In
Drain mode,
the automatic drain valve (if so equipped) opens and
the tank drains . All humidifier operation is suspended, and the drain
valve remains open until the unit is taken out of Drain tank mode .
• See the Diagnostics section for information about
Test outputs
and
Test
run
modes .
Space RH
--
0
100
%
RH set point
35
0
100
%
Input signal
--
0
10
VDC
--
0
20
mA
Dew point
--
0
100
°F
--
-17
37
°C
Dew point set point
50
20
80
°F
10
-6
26
°C
Inlet pressure switch
--
No water
Water
--
Steam demand
--
0
100
%
Displays steam demand as a percent of capacity
Steam output
--
0
100
%
Displays steam output as a percent of capacity
Steam production
--
0
100,000
lbs/hr
--
0
100,000
kg/h
Duct RH
--
0
100
%
Duct HL switch
--
Open
Closed
--
Duct HL set point
80
5
95
%
Duct HL signal
--
0
20
mA
Tank temperature
--
-30
275
°F
--
-34
135
°C
Tank temp signal
--
0
2200
Ohms
Aux temperature
--
-20
160
°F
--
-29
71
°C
Aux temp signal
--
0
26
mA
Continued
Status screen
OPERATION