SETUP AND CONFIGURATION
BACnet
®
communication with DriSteem humidistats
SUPPORTED STANDARD BACNET® APPLICATION SERVICES
• ReadProperty
• ReadPropertyMultiple
• WriteProperty
• DeviceCommunication. Needs a password which is “Vector” (case sensitive
and without the quotes).
• I-Am
• I-Have
• TimeSynchronisation
• UTCTimeSynchronisation
• ReinitializeDevice (“cold” or “warm”). Needs a password which is “Vector”
(case sensitive and without the quotes).
SUPPORTED STANDARD OBJECT TYPES
• Device
• Analog input
• Analog value
• Binary value
• Multi-state Value
LED INDICATORS
The BACnet interface features a green LED and a red LED for indication of
traffic on the RS-485 bus. The green LED is lit when an incoming packet is
received, and the red LED is lit when an outgoing packet is transmitted to the
bus. At power-up, both LED blink twice simultaneously as a sign of the boot
process being completed. A constantly lit LED serves as an indication of a fault
condition in the reception or sending process.
14
DRISTEEM TCI AND TRI2 HUMIDISTAT INSTALLATION, OPERATION, AND MAINTENANCE MANUAL