SETUP AND CONFIGURATION
Object list (continued)
Table 18-1:
Object List (continued)
Property
Description / Property Description
Range/Type
R/W
Analog Input Object
Object_Identifier
AI number
8bit
R
Object_Name
Name of the input, Assembled from template plus number
String
R
Description
Description of the input
16 Bytes
R/W
Preset_Value
Current value of input, writable only if out of service is set
Floating Point
R
Status_Flags
In_Alarm, Fault, Overridden, Out_Of_Service
Flags
R
Event_State
Always NORMAL
Flags
R
Reliability
NO_FAULT_DETECTED, NO_SENSOR, OVER_RANGE, UNDER_RANGE,
OPEN_LOOP, SHORTED_LOOP, COMMUNICATION_FAILURE,
UNRELIABLE_OTHER
List
R
Out_Of_Service
Writing to Out_Of_Service property is not supported
Flag
R
Units
Describes the units used. Degree Celsius or Fahrenheit has to be set by
MV02.
8bit
R
Analog Value Object
Object_Identifier
AV number
8bit
R
Object_Name
Name of the value, Assembled from template plus number
String
R
Description
Description of the input
16 Bytes
R/W
(1)
Preset_Value
Current value of input, writable only if out of service is set
Floating Point
R/W
(2)
Status_Flags
In_Alarm, Fault, Overridden, Out_Of_Service
Flags
R
Event_State
Always NORMAL
Flags
R
Out_Of_Service
Writing to Out_Of_Service property is not supported
Flag
R
Units
Describes the units used. Degree Celsius or Fahrenheit has to be set by
MV02.
Coded Value
R
Binary Value Object
Object_Identifier
BV number
8bit
R
Object_Name
Name of the input, Assembled from template plus number
String
R
Description
Description of the input
16 Bytes
R/W
(3)
Preset_Value
True or False, writable only if out of service is set
ON, OFF
R/W
Status_Flags
In_Alarm, Fault, Overridden, Out_Of_Service
Flags
R
Event_State
Always NORMAL
Flags
R
Out_Of_Service
Writing to Out_Of_Service property is not supported
Flag
R
(1)
Writable for objects with writable Present Value property only. (AVxx > AV11)
(2)
Writable for AV indexes greater than 11.
(3)
Writable for objects with Instance Number greater than 100.
18
DRISTEEM TCI AND TRI2 HUMIDISTAT INSTALLATION, OPERATION, AND MAINTENANCE MANUAL