4
CRUV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Capacities, electrical specifi cations, and weights
OVERVIEW
Table 4-2:
Steam connection sizes
CRUV model
Steam outlet
2, 4, 6, 8
1 ½
" hose or
NPT connection
10, 12, 14 ,16
1 ½
" or 2" hose or
NPT connection
21, 25, 30, 34
2" hose or
NPT connection
mc_052410_1705-CRUV
DC-1168
Hose clamp (for steam hose)
mc_052510_1531-CRUV
The steam outlet is designed to connect to a steam hose
or NPT connection. Tap/softened water CRUV shown.
Table 4-1:
CRUV capacities, electrical specifications, and weights
CRUV
model
Maximum
steam
capacity**
Current draw (amps)
Shipping
weight***
Operating
weight***
Single-phase
Three-phase
kW
lbs/hr
kg/h 120V
208V
240V
277V
480V
600V
208V
240V
277V
480V
600V
lbs
kg
lbs
kg
2
6
2.7
16.7
9.6
8.3
7.2
4.2
3.3
—
—
—
—
—
25
11
45
20
4
12
5.4
33.3
19.2
16.7
14.4
8.3
6.7
16.7* 14.4*
12.5
7.2*
5.8*
27
12
47
21
6
18
8.2
—
28.8
25.0
21.7
12.5
10.0
25.0* 21.7*
18.8
10.8*
8.7*
37
17
75
34
8
24
10.9
—
38.5
33.3
28.9
16.7
13.3
33.3* 28.9*
25.0
14.4* 11.5*
37
17
75
34
10
30
13.6
—
—
41.7 36.1* 20.8
16.7
29.1* 25.3*
21.9
12.6* 10.1*
39
18
90
41
12
36
16.3
—
—
—
43.3
25.0
20.0
33.3
28.9
25.0
14.4
11.5
39
18
90
41
14
42
19.1
—
—
—
—
29.2
23.3
38.9
33.7
29.2
16.8
13.5
39
18
90
41
16
48
21.8
—
—
—
—
33.3
26.7
44.4
38.5
33.3
19.2
15.4
39
18
90
41
21
63
28.6
—
—
—
—
43.8
35.0
—
—
43.8
25.3
20.2
43
20
104
47
25
75
34.0
—
—
—
—
—
41.7
—
—
—
30.1
24.1
43
20
104
47
30
90
40.9
—
—
—
—
—
—
—
—
—
36.1
28.9
48
22
109
49
34
102
46.3
—
—
—
—
—
—
—
—
—
40.9
32.7
48
22
109
49
*
For wire sizing, the highest leg draw is shown due to current imbalance.
**
Total humidifi er load = load to meet design cond load to compensate for steam loss from the dispersion assembly and interconnecting
piping. If total humidifi er load is more than the humidifi er’s maximum capacity, design conditions will not be met. For steam loss data see the
DriSteem Design Guide available for downloading and printing at www.dristeem.com
*** Depending on confi guration, add up to 28 lbs (13 kg) for weight of control cabinet, subpanel, and other electrical control components.
mc_071210_1440
FIGURE 4-1: STEAM OUTLET CONNECTIONS