CRUV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
Drane-kooler
Check valve
Note:
Use a condensate pump rated for your application. Pumps are rated by
fl uid temperature, head (pressure), and fl ow (gpm). Contact your local
DriSteem representative for pump selection.
Inlet drain water piping
(by installer)
Discharge piping
(by installer)
Condensate pump
DC-1117
mc_022410_1155
DC-1120
Drane-kooler
Part No. 902205 (NPT connections)
Part No. 902206 (BSP connections)
Floor
3/8" NPT (DN10) cold water inlet;
water pressure 25 to 80 psi (172 to 552 kPa);
maximum temperature 70 °F (21 °C)
Water supply shut-off valve
Union
Vacuum breaker
Field piping
3/4" NPT (DN20) hot drain water inlet.
For runs longer than 10' (3 m), increase to
1" NPT (DN25).
Union
Union
Tempered water outfl ow
12 gpm (45.4 L/m)
at 140 °F (60 °C)
2" NPT (DN50)
tempered water outlet
Notes:
• Dashed lines indicate provided by installer
• Total length of pipe between humidifi er and Drane-kooler not to exceed 10' (3 m)
mc_050610_1335-no-frame-drain
Piping:
FIGURE 11-1: FIELD PIPING CONNECTIONS, DRANE-KOOLER
™
WATER TEMPERING DEVICE
FIGURE 11-2: LIFTING DRAIN WATER