HCC-11 Heating current and circuit monitoring module 
 

Application 

The heating circuit monitoring module HCC-11 is designed to monitor electric circuits in the range 1.25A 
to 40A which are switched by solid-state relays (SSR). The HCC-11 system is primarily intended for 
monitoring heating circuits and also for detecting and localizing faults in single heating elements. The 
failure of a single heating element is reliably monitored. The module detects over- and undercurrents in 
the heating circuit beyond 

±

15% nominal current. Blown fuses, failed and interrupted SSR as well as 

those in half-wave operation are also registered. An adjustable alarm response delay of 2 to 40 secs 
rules out fault messages generated by voltage drops. 
 
Malfunctions are indicated by a red light-emiting diode (LED) on the HCC-11 and must be  
localized systematically. 
 
The alarm output allows up to 100 HCC-11 modules to be connected to a collective alarm           (load 

2kOhm). 

 
The module is designed for installation directly on the SSR. A DIN-rail mounting set is available.  
 
A plastic enclosure ensures shock hazard protection according to VBG 4. 

 

         

Safety regulations 
 

The HCC-11 monitoring module is 
designed for installation in a switch cabinet 
and should be installed so as to provide 
protection against humidity and severe 
contamination. It is also important to ensure 
that the permissible ambient temperature 
range (0 to 60°C;  21 to 140°F) is not 
exceeded. The module must be used only 
for this intended purpose. 
 
The module  must be connected by a 
qualified electrician according to the 
relevant VDE directives in Germany and in 
compliance with local regulations. 
The signal and auxiliary supply cables must 
not be laid together with the power supply 
cables (power current). 
 

Before assembly and before opening 
the housing, the system must be 
disconnected from the mains. 

Wiring diagram HCC-11

 

7

Содержание HCC 11

Страница 1: ...schreibung und Bedienungsanleitung Description and Operating Manual Heizstrom und Heizkreis ber wachungsmodul Heating current and circuit monitoring module Module de surveillance du courant et du circ...

Страница 2: ...g 4 Inbetriebnahme 4 Fehlersuche 5 Technische Daten 6 Application 7 Safety regulations 7 Assembly instructions 8 Starting up 8 Troubleshooting 9 Technical date 10 Application 11 Mesures de s curit 11...

Страница 3: ...ttet die Zusammenschaltung von bis zu 100 St ck HCC 11 auf einen Sammelalarm Last 2kOhm Die direkte Montage des Moduls auf das SSR reduziert Montageaufwand und Montagefl che Ein Montagesatz zur Hutsch...

Страница 4: ...r kleinstm gliche Me bereich zu w hlen Beispiel Heizstrom 16A Me bereich 20A Schalter 1 2 ON Schalter 3 OFF Montageanleitung Die Montage des HCC 11 erfolgt auf das bereits montierte Halb leiterrelais...

Страница 5: ...l und Betriebsspannung power supply m ssen anliegen Die gr ne LED leuchtet und best tigt das Anliegen des Steuersignals wenn die Betriebsspannung anliegt Der Trimmer Strom berwachungssollwert current...

Страница 6: ...ichfenster leuchtet innerhalb eines Bereiches von 2 bezogen auf den Nennstrom Anzeigeelement 3 LED rot leuchtet zeitverz gert wenn der Strom um mehr als 15 vom Nennstrom abweicht leuchtet unverz gert...

Страница 7: ...systematically The alarm output allows up to 100 HCC 11 modules to be connected to a collective alarm load 2kOhm The module is designed for installation directly on the SSR A DIN rail mounting set is...

Страница 8: ...es Select the smallest possible measuring range to obtain optimum current measuring Example heating current 16A measuring range 20A Sw1 ON Sw2 ON Sw3 OFF Assembly instructions The HCC 11 is mounted on...

Страница 9: ...be present The green LED comes on to confirm the presence of the control signal and auxiliary power supply Slowly adjust the current adjust trimmer for monitoring the setpoint until the yellow LED co...

Страница 10: ...rent setpoint check comes on within range of 2 referred to nominal current Indicator element LED 3 red comes on after delay when current deviates from nominal value by more than 15 comes on straight a...

Страница 11: ...n maximum de 100 unit s de modules HCC 11 sur une alarme de groupe charge 2 kOhm Le montage direct du module sur le relais semi conducteurs r duit les co ts ainsi que la surface de montage Un set de m...

Страница 12: ...r 3 OFF Commutateur 4 Surveillance de la valeur maximale du courant Pour des consommateurs avec courant d enclenchement accru par ex des metteurs infra rouge et des lampes incandescence la surveillanc...

Страница 13: ...n de service est appliqu e Tourner lentement le potentiom tre de r glage de valeur assign e de la surveillance du courant Ajustement de courant jusqu ce que la DEL jaune s allume Le r glage se rapport...

Страница 14: ...a valeur de consigne du courant fen tre de r glage S allume dans une plage de 2 par rapport au courant nominal El ment d affichage 3 DEL rouge S allume avec temporisation lorsque le courant s carte de...

Страница 15: ...15...

Страница 16: ...96 31 0 Fax 00 49 2842 96 31 99 eMail drews drews electronic de www drews electronic de DREWS Electronic GmbH Robert Bosch Stra e 3 47475 Kamp Lintfort Germany Phone 00 49 28 42 96 31 0 Fax 00 49 2842...

Отзывы: