Supplement operating manual for DREHMO i-Matic actuators with integrated  

MODBUS fieldbus interface  

 

 
Wenden, 21.03.12 

 

Page 3 of 18 

Prepared by: Ste 

1  Introduction 

 
This document describes the expansion of modbus RTU functionality for i-Matic actuator. 
 
 

2  Interface technology 

 

2.1  Physical interface 

 
The physical interface is in accordance to the MODBUS over Serial Line Specification & Implementation guide 
that can be found on the following web site: 

http://www.modbus.org/ 

 
The physical interfaces uses 2-wire RS485. 
 
The following parameters are possible for the communication configuration: 
 
Baud rates: 
 
38400 bit/s 
19200 bit/s 
9600 bit/s 
4800bit/s 
2400bit/s 
1200bit/s 
600bit/s 
300bit/s 
 
The parity can be configured as follows: 
 
parity none, with two stop bits, 
parity even, with one stop bit, 
parity odd, with one stop bit 
 
 
The interface card has two separate 2-wire RS485 modbus channels. The baud rate and parity settings are 
common for both channels. Each of the channels can be assigned an individual slave address in the range of 
1 to 247 (different addresses are possible for test-purposes on a single master). 

 
Broadcast messages are not supported. 
 

In case of a redundant connection, the slave device decides itself about the channel priority. Only the 
commands of the high priority channel are executed. For maintenance reasons there is a feedback bit for the 
channel quality of each channel and a command bit to change the channel priority. 
 
The physical connection is done on a separate interface board mounted in the compact plug. The shield of the 
cables have to be fixed on the according strain relieves on this interface board. For each channel there exists 
separate screw-terminals for the incoming and outgoing signals and a dipswitch for the optional termination of 
the lines. Furthermore there are dipswitches for the shield connection of incoming or outgoing cables to 
ground potential. 
 
 

Содержание i-matic

Страница 1: ...for actuators with MODBUS interface part number 166 671 Installation Manual Version 03 Operating Manual Date Oct 18 th 2006 INFORMATION This installation manual should only be used in conjunction with...

Страница 2: ...2 4 2 Number of channels bus profile 10 2 4 3 Redundancy modes line redundant vs master redundant 10 2 4 4 Function Fail Safe Timeout setting 10 2 4 5 Fault messages 11 2 5 Electrical connection 12 2...

Страница 3: ...ate 2 wire RS485 modbus channels The baud rate and parity settings are common for both channels Each of the channels can be assigned an individual slave address in the range of 1 to 247 different addr...

Страница 4: ...rce Single Coil write single bit of master output data command FC 06 Preset Single Register write single data of master output data command FC 15 Force Multiple Coils write multiple bit of master outp...

Страница 5: ...travel message only acc to position 11 28 Drive in end of travel position CLOSED End of travel message only acc to position 12 29 Drive in end of travel position OPEN Drehmo End of travel message onl...

Страница 6: ...xceeded 7 56 Actuator is served Logged in user is specialist or manufacturer for service reasons 8 57 Regulating time too long Regulating time longer than max running time 9 58 Max valve stroke exceed...

Страница 7: ...word feedback Request C8 04 02 00 00 08 E1 ED Checksum number of data high lowbyte database address decimal 512 function code 04 slave address 200 in example Response C8 04 10 03 C4 00 0F 42 84 50 A0...

Страница 8: ...V01 05 0048 9 15 26 32 unused unused 0x203 0x220 33 512 In order to access the command signals the function codes FC 05 Force Single Coil or FC 06 Preset Single Register are recommended to be used The...

Страница 9: ...00 00 00 00 00 00 00 00 00 00 00 00 00 A6 6D Checksum discrete coil command check information 0 lowbyte highbyte order number of databytes function code 01 read coil status command check slave address...

Страница 10: ...possible to set up two different redundancy modes The different modes have a different reply behaviour For line redundant mode it is possible to block the reply of the inactive channel by setting the...

Страница 11: ...25 5 seconds In case of fail safe the actuator action can be parameterised as explained in the i Matic instruction manual 2 4 5 Fault messages Fault messages can be reset depending on the active faul...

Страница 12: ...en below 1 Optional external 24 VDC supply of i Matic unit input with tolerance 10 5 and less than 500mA load Optional auxiliary 24 VDC supply output for external use allows 60mA load Mounting plate f...

Страница 13: ...e to be wired to the output terminals labeled OUT The connection of the shielding for incoming or outgoing cables has to be done in the same manner Mounting plate with electric assembly front side vie...

Страница 14: ...S3 S4 on DiM 19 connection board channel 1 without termination bus connection forward to next device channel 2 termination activated last device on bus segment 2 5 1 3 Grounding of the cables shields...

Страница 15: ...The core of the optical fibres might be of diameter 50 m or 62 5 m To connect the fibre optic cables open the cover of the extended compact plug Using the maximum of four cable glands M20x1 5 the cab...

Страница 16: ...available double terminals A1 B1 A2 B2 which are electrically connected A bridge between incoming and outgoing bus signals has to be made to achieve the required T piece The bus terminator always has...

Страница 17: ...ant to keep the size of the breakout small enough to be able to push it through a cable gland of the size M20 The standard connector is of type F SMA The following pictures show the inside of the wiri...

Страница 18: ...ground are galvanically isolated from the electronic potential by optocouplers The nominal current of the discrete inputs is 12 mA for an input voltage of 24 V DC The following picture shows the stru...

Отзывы: