Supplement operating manual for DREHMO i-Matic actuators with integrated  

MODBUS fieldbus interface  

 

 
Wenden, 21.03.12 

 

Page 14 of 18 

Prepared by: Ste 

2.5.1.2 

Bus termination 

 
The termination of the bus line can be done individually for the channels 1, 2 by setting the 
slide switches S3, S4 on the connection board DiM-19 in the compact plug. If the 
termination on one of the channels is activated, the outgoing line of this channel is 
disconnected from the master. 
 

 

 

example for termination with slide switch S3, S4 on DiM-19 connection board 

 

- channel 1 without termination – bus connection forward to next device 

- channel 2 termination activated – last device on bus segment 

 

2.5.1.3 

Grounding of the cables´ shields in case of copper cable use 

 
To avoid high currents on the cables´ shields in systems with very different earth potentials, 
the shields of the cables connected to the inputs and those connected to the outputs can be 
grounded directly, or using a combination of resistor and capacitor using the grounding 
switches ( see 2.5.1.1) on the connection board. The resistor reduces DC-currents, 
whereas the capacitor has a low impedance for fast changes between ground potentials. 
 

 

 

High impedance grounding of shield

 

 

 
 

Содержание i-matic

Страница 1: ...for actuators with MODBUS interface part number 166 671 Installation Manual Version 03 Operating Manual Date Oct 18 th 2006 INFORMATION This installation manual should only be used in conjunction with...

Страница 2: ...2 4 2 Number of channels bus profile 10 2 4 3 Redundancy modes line redundant vs master redundant 10 2 4 4 Function Fail Safe Timeout setting 10 2 4 5 Fault messages 11 2 5 Electrical connection 12 2...

Страница 3: ...ate 2 wire RS485 modbus channels The baud rate and parity settings are common for both channels Each of the channels can be assigned an individual slave address in the range of 1 to 247 different addr...

Страница 4: ...rce Single Coil write single bit of master output data command FC 06 Preset Single Register write single data of master output data command FC 15 Force Multiple Coils write multiple bit of master outp...

Страница 5: ...travel message only acc to position 11 28 Drive in end of travel position CLOSED End of travel message only acc to position 12 29 Drive in end of travel position OPEN Drehmo End of travel message onl...

Страница 6: ...xceeded 7 56 Actuator is served Logged in user is specialist or manufacturer for service reasons 8 57 Regulating time too long Regulating time longer than max running time 9 58 Max valve stroke exceed...

Страница 7: ...word feedback Request C8 04 02 00 00 08 E1 ED Checksum number of data high lowbyte database address decimal 512 function code 04 slave address 200 in example Response C8 04 10 03 C4 00 0F 42 84 50 A0...

Страница 8: ...V01 05 0048 9 15 26 32 unused unused 0x203 0x220 33 512 In order to access the command signals the function codes FC 05 Force Single Coil or FC 06 Preset Single Register are recommended to be used The...

Страница 9: ...00 00 00 00 00 00 00 00 00 00 00 00 00 A6 6D Checksum discrete coil command check information 0 lowbyte highbyte order number of databytes function code 01 read coil status command check slave address...

Страница 10: ...possible to set up two different redundancy modes The different modes have a different reply behaviour For line redundant mode it is possible to block the reply of the inactive channel by setting the...

Страница 11: ...25 5 seconds In case of fail safe the actuator action can be parameterised as explained in the i Matic instruction manual 2 4 5 Fault messages Fault messages can be reset depending on the active faul...

Страница 12: ...en below 1 Optional external 24 VDC supply of i Matic unit input with tolerance 10 5 and less than 500mA load Optional auxiliary 24 VDC supply output for external use allows 60mA load Mounting plate f...

Страница 13: ...e to be wired to the output terminals labeled OUT The connection of the shielding for incoming or outgoing cables has to be done in the same manner Mounting plate with electric assembly front side vie...

Страница 14: ...S3 S4 on DiM 19 connection board channel 1 without termination bus connection forward to next device channel 2 termination activated last device on bus segment 2 5 1 3 Grounding of the cables shields...

Страница 15: ...The core of the optical fibres might be of diameter 50 m or 62 5 m To connect the fibre optic cables open the cover of the extended compact plug Using the maximum of four cable glands M20x1 5 the cab...

Страница 16: ...available double terminals A1 B1 A2 B2 which are electrically connected A bridge between incoming and outgoing bus signals has to be made to achieve the required T piece The bus terminator always has...

Страница 17: ...ant to keep the size of the breakout small enough to be able to push it through a cable gland of the size M20 The standard connector is of type F SMA The following pictures show the inside of the wiri...

Страница 18: ...ground are galvanically isolated from the electronic potential by optocouplers The nominal current of the discrete inputs is 12 mA for an input voltage of 24 V DC The following picture shows the stru...

Отзывы: