DataNode Specifications (continued)
5530 / 5520 / 5513 / 5510
Trigger Conditions
RMS
V and I Selectable cycles to trip and restore
Waveshape faults
V and I Selectable duration and magnitude to trigger
Transients
Voltage and current, high frequency and crest peak
Harmonics
V and I Individual and THD
Phase Shift
Fundamental
Timed Readings
1-120 minutes
Cross Triggered
From other DataNodes on RMS or transient events
1159 Classification
Yes
Impulsive transient
Yes
Oscillatory transient
up to 3KHz
Interruption
Yes
Sag
Yes
Swell
Yes
Under/overvoltage
Yes
Sustained interrupt
Yes
DC
Yes
Harmonics
Yes
Interharmonics
Yes
Notching
Yes
Trending
Min/Max/Avg on parameters at user specified interval
Communication
Serial port type
RS232/RS485 (used for diagnostic and initial setup only)
Serial baud rate
9600 baud, 8 bit, 1 stop, no parity, no flow control
Ethernet
10BaseT using UCA-2 to InfoNode
Other
AUI for fiber optic, etc.
Other
Firmware Update
Remotely uploadable
Field Calibration Certification
Yes
Mounting
Rack, Panel, DeskTop, NEMA 4X
Installation Categories
Mains Supply
Installation Category II, Pollution Degree 2
Measurement Inputs
Installation Category III, Pollution Degree 2
Physical Characteristics
Dimensions
13”W x 8”D x 5”H (330.2mm x 203.2mm x 127.0mm)
Weight
6.3 lbs (2.9 kg)
Enclosure
Painted Aluminum
5-3
5
Specifications
EPQ DataNode Series User’s Guide