Intended use
Dräger RVP 5000
23
2
Intended use
The Dräger RVP 5000 is a display for the visualisation of gas
concentrations of up to 99 channels from a Dräger REGARD
system.
2.1
Product features
z
8,4" TFT Display
z
24 V DC power supply
z
Touch-Screen
z
RS485 communication interface to the Dräger REGARD
Control System
z
CompactFlash port
z
Optional datalogger
z
Optional web interface via Ethernet port
z
Up to a maximum of 99 channels can be managed
z
Display of measured values
z
Display of alarms / alarm window
z
Tabular or bar display
z
Simple controller configuration
z
Display of gas type, unit and customer-specific TAG names
z
Graphical trend display (up to 17 minutes)
z
Acoustic and visual alarm
z
Visualisation in the event of an alarm and fault
z
Possible update of the firmware via CompactFlash memory
card
3
Operating and display elements
DANGER
Danger of explosion!
The Dräger RVP 5000 is not designed or authorised for
use in areas where flammable or explosive gas
mixtures could develop.
!
1 Menu button
This button takes you to the start screen.
2 LEDs
Red (PWR):
Flashing
Equipment started, no configuration loaded.
Continuous
CompactFlash memory card available.
Yellow:
Off
No CompactFlash memory card available.
Continuous
CompactFlash memory card available.
Rapid
flashing
CompactFlash memory card is being
checked.
Equipment is writing data to the
CompactFlash memory card.
Flashing
Incorrect CompactFlash memory card
formatted.
Green:
Flashing
At least one channel is active in the alarm
window.
Continuous
Configuration is loaded and there are no
alarms pending.