20
Technical data
en
7
Technical data
7.1
General
Dimensions
101.6 x 117 x 157 mm
(4" x 4.6" x 6.18")
Weight
Stainless Steel
2.8 kg (6.1 lb.)
Aluminium
1.3 kg (2.8 lb.)
Operating voltage
18-32 VDC
Operating temperature
+75 °C (+167 °F)
Storage temperature
+85 °C (+185 °F)
Possible number of detectors for
RS-485 communication
247
Spectral response
Dräger Flame 2000
4.4 µm
Dräger Flame 2500
4.0 µm, 4.2-4.7 µm, 5.0 µm
Dräger Flame 2700
4.0 µm, 4.2-4.7 µm, 5.0 µm, and
2.7-3.0 µm
Response time
Dräger Flame 2000/2500/2700 Typically 5 seconds
Dräger Flame 2570
1 second for 1x1 ft n-heptane fire
at 60 m (200 ft)
10 seconds for 1x1 ft n-heptane
fire at 90 m (300 ft)
Max. response time
10 seconds
Field of view
Dräger Flame 2000/2570
horizontal: 90°
vertical: 90°
Dräger Flame 2500
horizontal: 100°
vertical: +50° down, -45° up
Dräger Flame 2700
Gasoline:
horizontal: 67°
vertical: 70°
Hydrogen:
horizontal: 80°
vertical: 80°