![DPS Telecom Site Dialer G3 Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/dps-telecom/site-dialer-g3/site-dialer-g3_user-manual_2525744035.webp)
30
Timers
8.6
The
Provisioning
>
Timers
screen allows you to configure the web refresh rate, DCP poller timeout,
Web Timeout timeout, and timed ticks.
The Timers screen
Timer Settings
Web Refresh
How often web browser is refreshed when in monitor mode. Range: (1s-60s)
DCP Poller Timeout
DCP polls must be received within this time interval or the DCP poller inactive alarm will
set. Range: (1m-30m, 0s=off)
Web Timeout
Maximum idle time allowed before the web interface will automatically logout. Range:
(1m-30m)
Timed Tick
This is a 'heartbeat' function that can be used by masters who don't perform integrity
checks. Range: (0s-60m, 0s=off)
Timed Tick Variation
Used for daily or weekly timed tick. Use this format to toggle "Timed tick" system alarm
at specified time and for specified duration. "Timed tick" alarm will be in Alarm for
specified duration at a specified time.
Format: Day of Week (optional), Time of Day (military time), Duration.
For example: "Mon, 17:10, 10min" or just "17:10, 10min".