66
/
96
10.2.1.3 Input / outputs
Table 28:
Input/output parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
1-3
Inputs/outputs
-
-
Everybody
Nobody
-
1-3-1
Analog inputs
-
-
Everybody
Nobody
-
Note: To change a function, the
function first has to be removed by
changing it to 'No function'. To set a
function all pumps have to be set to
"Manual OFF" (2-2).
-
-
Everybody
Nobody
-
1-3-1-1
1-3-1-2
1-3-1-3
Input 1
Input 2
Input 3 (extension board)
No function
None
Everybody
Service
-
Pressure sensor on suction side
Pressure sensor on discharge side
Pressure sensor at tank
Setpoint
1-3-2
Analog outputs
-
-
Everybody
Nobody
-
Note: To change a function, the
function first has to be removed by
changing it to 'No function'. To set a
function all pumps have to be set to
"Manual OFF" (2-2).
-
-
-
-
-
1-3-2-1
1-3-2-2
Output 1
Output 2
None
None
Everybody
Service
-
Pump speed
Suction-side pressure
Discharge-side pressure
Tank-filling proportional valve
Tank-filling additional proportional valve
Tank level height
1-3-3
Digital inputs
-
-
Everybody
Nobody
-
Note: To change a function, the
function first has to be removed by
changing it to 'No function'. To set a
function all pumps have to be set to
"Manual OFF" (2-2).
-
-
-
-
-