47 / 96
8.2 Servicing/Inspection
8.2.1 Supervision of operation
CAUTION
Increased wear due to dry running
Damage to the pump set!
Ø
Never operate the pump set without liquid fill.
Ø
Never close the shut-off element in the suction line and/or supply line
during pump operation.
CAUTION
Impermissibly high temperature of fluid handled
Damage to the pump!
Ø
Prolonged operation against a closed shut-off element is not permitted
(heating up of the fluid).
Ø
Observe the temperature limits in the data sheet and in the section on
operating limits.
While the pump is in operation, observe and check the following:
– If activated, check the functional check run.
– Measure the actual start-up pressure and stop pressure of the pump sets with a
pressure gauge. Compare the values with the specifications on the name plate.
– Compare the pre-charge pressure of the accumulator with the recommended data.
– Check the rolling element bearings for running noises.
Vibrations, noise and an increase in current input occurring during unchanged operating
conditions indicate wear.
– Monitor the functions of auxiliary connections, if any.
Also see
2
Setting the pre-charge pressure [
8.2.2 Checklist for inspection work
In the event that you decide to conduct your own inspections, proceed according to the
following checklist at least once a year:
1.
Check the pump and drive for smooth running and the mechanical seal for integrity.
2.
Check the shut-off, drain and check valves for proper functioning and tightness.
3.
Clean the strainer in the pressure reducer (if applicable).
4.
Check the expansion joints (if any) for wear.
5.
Verify the pre-charge pressure and, if required, check the accumulator for integrity.
[