FAM SROxG Nav key rev 10-14.doc
11/14
The pipe fittings compound must be certified for gas.
The customer must install a manual shut off valve at the end of the gas supply pipe near the
appliance which is approved by the American Gas Association Standard in the United States and
with the Canadian Gas Association in Canada.
Clean the air contained in the gas supply pipe at the installation to insure a successful firing on
the first try. The gas pipe sealing compound tightness must be verified using a solution of water
and soap prior to firing the unit.
WARNING
Make sure not to obstruct the overpressure
opening on the gas regulator.
NOTE:If there's any modification done to the system or change of the type of gas used, make
sure that the regulator pressure of the burner is adjusted as recommended in this manual.
2. To the electrician
Electrical supply installation must be in accordance with the electrical rating on the nameplate.
A phase sequence and loss of phase relay is installed on 3 phases models to avoid wrong rotation
direction of the blowers. If the oven does not light up, swap two phases conductors in the supply
box and try again. Be sure that the power is really on the 3 phases wires next to the fuses in the
control compartment on the front of the oven. Check also if the control fuse located near the
main switch is not blown.
WARNING
The electrician must make sure that the supply cable does not come in contact with the oven top
which becomes hot.
3. To the plumber
This equipment is to be installed to comply with the applicable federal, state or local plumbing
codes.
Connect the water supply pipe to the oven using good quality sealing compound. Take care that
combustible water pipes do not come in contact with hot parts on the top of the oven.
Connect the steam system (1/2 NPT) to the cold water distribution network. Minimum Water
Flow required is 4.5 USGPM (0.29 l/sec).@ 50psi
We highly recommend a water softener to eliminate minerals in the water. We suggest you to use
Doyon installation kit number 50-1530 and replacement cartridges 50-1531 to achieve minimum
flow requirement.
A-8