Conduit Guidelines:

 

1) 

If wires, cabling, or conduit are coming at enclosure wire entry level, or above, always create a drip loop.

2) Please use only approved watertight electrical conduit and connectors, IP66 or better, with proper seals and fittings installed & fully seal.
3) 

Then

, after all wire and cables are installed into enclosure,  Seal wire entry ports inside of enclosure

 with any number of commercially 

available sealing putty’s, Silicone Sealant, or similar products that are approved by applicable local and relevant electrical codes.

SHOCK HAZARD!

Failure to fully seal enclosure wire and cabling entry ports 

may lead to  shock hazard,

 

unsatisfactory product performance, a possibility of damage to electronics in the Dotworkz enclosure product, 
including camera damage, and damage to integrated electronics 

due to air driven moisture traveling thru the 

conduit, condensing and collecting in the enclosure creating a short circuit hazard. 

Dotworkz does 

not 

endorse, nor has it evaluated any of these products.  Test products first, and follow all manufacturers’ instructions.  

Follow all applicable electrical and building codes and installation guidelines.  End user assumes liability for applicability of these products and 
their effectiveness and incurred liability in using these products.

Electrical Conduit Guidelines

For optimal performance, your Dotworkz Enclosure is designed to be Air & Water Tight to eliminate any 

moisture, dust, and insect damage, safety, performance,  reliability, and maintenance related issues.

Use of Electrical Conduit, 

without sealing the entry ports/ inside wire feeds

 within Camera Enclosure, will 

subject the inside of your enclosure to possibility of condensation driven moisture, dust, and insect contamination 
hazards.  

Dotworkz has provided each enclosure with two Cable Gland Strain Relief seal ports that fully seal 

enclosure to an IP68 rating, Waterproof and Airtight Seal.  To properly seal, only one round cable is used in each 
cable gland port.  (

Holes on enclosure are 7/8” diameter, ready for standard ½” I.D. NPT connector, or PG13 fittings.)

However, we realize our customers are retrofitting these connectors with electrical conduit fittings.  We 

acknowledge this industry customization and installation practice, and would like to guide customers to properly 
install these products.

 

 

 

Humid Air 

Condensing to Water

 

 

FORCES AT WORK IN ANY UNSEALED, CONDUIT WIRE FEED ENCLOSURE SYSTEM

WARM/MOIST IN UNSEALED CONDUIT MOVES THRU CONDUIT 
FEEDS EXPAND & CONTRACT WHEN CONDUIT HEATS & COOLS 
WITH OUTSIDE TEMPERATURES  

 

EXPANDING HEATED AIR IS PUSHED INTO ENCLOSURE THEN COOLS & 
CONDENSES, HUMID AIR CONDENSES ON SURFACES INSIDE 
ENCLOSURE

Electrical Putty & Putty Tapes

Silicone Sealants

Foam  Sealants (use very sparingly)

Dotworkz  supplies  two  ½”  diameter  foam  conduit  plugs,  that  when  installed,  will  assist  in 

sealing off airflow in conduit feed thru, at cable entry inside of enclosure.  Putty or Sealant can be 
used in conjunction with these plugs, to assure a full seal inside enclosure cable feed entry.

Содержание COOLDOME 12 VDC

Страница 1: ...INSTALLATION GUIDE Mounting Sealing of Housing Electrical Details COOLDOME ENCLOSURE SERIES D2 COOLDOME D3 COOLDOME S TYPE COOLDOME...

Страница 2: ...of sufficient magnitude to constitute a risk of electric shock to persons The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and...

Страница 3: ...to eliminate any moisture dust and insect damage safety performance reliability and maintenance related issues Use of Electrical Conduit without sealing the entry ports inside wire feeds within Camer...

Страница 4: ...GUIDE VENT STOPPER PLUGS for Conduit 1 Pull wires to final installed length 2 Open Vent Stop Plug and install over wire 3 Pinch Plug to compress over wire and insert into conduit feed mouth 4 Push pl...

Страница 5: ...st be installed into COOLDOME prior to entering enclosure into service Active Cooler within COOLDOME lowers temperature to at or near dew point within COOLDOME so trapped air must be dried out to elim...

Страница 6: ...cted and kept off while installing or Servicing Enclosure Follow All Local and Applicable Electrical Codes and Standards for Installation of Electrical components All Cable Ports wire feeds or Conduit...

Страница 7: ...g Tools Drill Bits For Wall Mounting Drill and Bits for user supplied fasteners for wall mounting enclosure For Pole Mounting Strapping Banding Tools for user supplied Stainless Steel Pole Straps For...

Страница 8: ...6 Low Voltage Line Drop Wire Gauge Tables See 12 VDC 24 VDC Low Voltage Wire Gage Selector Appendix Chart...

Страница 9: ...7...

Страница 10: ...8 Low Voltage Wire Gage Selector Charts Per Conductor Pair Per Cooler D3 COOLDOME uses Dual Coolers Requires Two Pair...

Страница 11: ...e current load it is best to run two pairs individually So each 12VDC paired wiring runs load of one cooler Low Voltage 12 VDC Output Terminals Color Symbol Terminals Description Red V 9 10 11 Positiv...

Страница 12: ...power and COOLDOME Voltage drop is based on fully loaded cooler engaged conditions and camera powered allowing up to 3 amps at typical ambient temperatures of 100F Inside D3 CD at rear of upper on enc...

Страница 13: ...Safety Ground Front of Power Supply with terminal strip Rear of Power Supply with Input Voltage Selector Select Input Voltage before Hooking up Power Supply 110 VAC or 220 VAC Low Voltage 12 VDC Outp...

Страница 14: ...ut Voltage 90 132VAC 176 264VAC Selected by Switch Frequency Range 47 63 HZ Input Current Full Load Typ 4A 115VAC 2A 230VAC Recommended Min Circuit Breaker for 110VAC In 10 A type C Int Electrical Wor...

Страница 15: ...13 D2 D3 Mounting Detail...

Страница 16: ...14 S Type Strong Arm Mount Wall Mounting Pattern Not to Scale...

Отзывы: