4. The flow requirement of your appliance must not exceed the Maximum Flow Capacity.
5. Select the EFV-TSO with the lowest Maximum Flow Capacity that is greater than your appliance requirement.
6. Note that different inlet and outlet configurations are offered for some EFV-TSO devices, and select an inlet and outlet
configuration that is appropriate for your application.
1) Rated Trip Flow and Max Flow Capacity values are kBTU/hr @ max. "w.c. PD (natural gas, 0.64 s.g., 1000 BTU/cu.ft.).
2) A minimum of 5" w.c. inlet pressure is required with a maximum inlet pressure of 14" w.c. (1/2 psig).
3) For more information on flow rates with a specific Dormont gas connector, contact 1-800-DORMONT.
4) Operating temperature: -20°F to 150°F (-29°C to 66°C).
5) Bypass rate: MAX 2.5 SCFH at 0.5 psi.
6) Installation orientation: Multi-poise (horizontal, vertical up, vertical down).
7) EFV Type: EFVB (Bypass with automatic reset).
8) Maximum trip flow is 1.4 times the rated trip flow.
9) Model -TS (Thermal Shutoff) Reaction Temperature Range: 350°F to 425°F (176.7°C to 218.3°C).
Installing An EFV-TSO
Examples of a Typical Appliance Installation
Your installation may vary - ALWAYS follow instructions and applicable codes and regulations.
Licensed plumbers / Qualified installers ONLY.
EFV-TSO
SIZING
TABLE
MODEL 90-1031-
V1-TS
MODEL 90-1031-
V2-TS
MODEL 90-2031-
V4-TS
MODEL 90-3041-
V5-TS
MODEL 90-303M-V6-
TS
Rated Trip Max Capacity Rated Trip Max Capacity Rated Trip Max Capacity Rated Trip Max Capacity Rated Trip Max Capacity
Horizontal
68 @ 1.05
48 @ 0.30
95 @ 1.55
60 @ 0.40
115 @ 0.70
93 @ 0.35
160 @ 0.80
125 @ 0.25
160 @ 0.80
125 @ 0.25
Vertical Up
105 @ 1.95
65 @ 0.50
115 @ 2.25
80 @ 0.60
145 @ 1.05
118 @ 0.45
185 @ 1.00
150 @ 0.40
185 @ 1.00
150 @ 0.40
Vertical Down
36 @ 0.40
30 @ 0.15
60 @ 0.70
45 @ 0.25
85 @ 0.45
60 @ 0.15
135 @ 0.60
105 @ 0.20
135 @ 0.60
105 @ 0.20
Inlet
1
⁄
2
" MNPT x
3
⁄
8
" FNPT
1
⁄
2
" MNPT x
3
⁄
8
" FNPT
1
⁄
2
" MNPT
3
⁄
4
" MNPT x
1
⁄
2
" FNPT
1
⁄
2
" MNPT
Outlet
3
⁄
8
" OD Flare
3
⁄
8
" OD Flare
1
⁄
2
" OD Flare
5
⁄
8
" OD Flare
(
15
⁄
16
"-16 Threads)
5
⁄
8
" OD Flare
(
15
⁄
16
"-16 Threads)
WARNING
!