12-2020
dormakaba Canada Inc. RAC5 Lite Installation Guide – PK3736 | 18
6 Annex A: Wiring Diagram and Tables
Figure 11 – Remote Access Controller RAC5 Lite
OR
Power Adaptor
Unswitched AC
Power Source
BLK
Diode
Electric Strike
(fail secure)
RD
5
4
3
2
1
12V
GND
Electromagnetic
Lock
BLK
Diode
Electric Strike
(fail secure)
RD
5
4
3
2
1
12V
GND
Electromagnetic
Lock
OR
OR
C
NC
(See *NOTE)
Fire Alarm
Panel
(Contact OPENS on fire alarm)
Not supplied by dormakaba
RAC5 NFC
Wall Reader
Red
Black
White
Green
1
2
3
4
1
2
3
4
1
2
3
4
J3
J7
J8
J12
J1
J15
J16
J6
J18
J19
RAC5 LITE PCB
N
O
N
C
C
O
M
G
N
D
F
IR
E G
N
D
12
V
_L
C
K
#1
G
N
D
1
2V
N
O
N
C
C
O
M
R
E_
U
N
L#
2
G
N
D
R
E_
U
N
L#
1
1 (+) 2 (-) 3 (+) 4 (-)
1
2
3
4
1
2
3
2
1
1
2
3
12
_L
C
K
#2
G
N
D
1 2 3 4
PWR GND GND PWR
RD#1
RD#2
READE R 2
READER 1
1
2
3
4
J11
R
EX
2
G
N
D
TA
M
P
ER
G
N
D
D
O
O
R
S
TA
T#
2
G
N
D
G
N
D
R
EX
#1
G
N
D
D
O
O
R
ST
A
T#
1
G
N
D
EXIT
COM NO NC
REX#2
EXIT
REX#1
EXIT
REMOTE
UNLOCK#1
EXIT
REMOTE
UNLOCK#2
COM NO NC
COM NO NC
COM NO NC
O
N
1
2
3
4
DELAY0
DELAY1
DEVICES
TEST MODE
SW2
D46
D37
D48
SW1
Reset
COM
NC
COM
NC
SW3
SW5
D2
1
D3
1
D30
D12
N
B
H
G
I
J
H
G
DOOR STATUS #1
DOOR STATUS #2
NOTE:
Connections required are dependent on system options purchased.
Part numbers are subject to change. For latest part numbers, please refer
to the latest ordering guide or contact dormakaba Canada Inc.
NOTE:
J3, J7, J8 & J11 inputs (max source current of 25mA)
are all connected to dry terminals (NC, NO) with a common
connection to the Ground terminal on each of the connectors;
dry terminals must be able to sink minimum 25mA at a
minimum of 5V rating. J1 is rated for an output of 12V @
200mA. J6 & J18 are rated for outputs of 12V @ 600mA.
Controller Board - RAC5 Peripherals
Connections
Controller Board
Peripheral
Signal
PCB
Conn.
Wire /
Conn.
Description
REM UNL
J8 pin 1
-
Remote unlock (Q) #1
GND
J8 pin 2
-
REX
J8 pin 3
-
Request to Exit (O) #1
GND
J8 pin 4
-
FIRE ALM
J18 pin 3
BLACK
Fire Alarm
GND
J18 pin 4
BLACK
12V_LOCK_
DEV#1
J18 pin 1
-
Strike (K) or Maglock (L)
Device #1
GND
J18 pin 2
-
COM
J19 pin 1
-
NC
J19 pin 2
-
NO
J19 pin 3
-
12V_LOCK_
DEV#2
J6 pin 1
-
Strike (K) or Maglock (L)
Device #2
GND
J6 pin 2
-
COM
J15 pin 1
-
NC
J15 pin 2
-
NO
J15 pin 3
-
REM UNL 2
J11 pin 1
-
Remote Unlock #2
GND
J11 pin 2
-
REX2
J3 pin 1
-
Request to Exit #2
GND
J3 pin 2
-
Number of Devices (SW3) OFF - One locking device ON - Two locking devices
Test Mode (SW4)
OFF - Normal operation
ON - Test mode
DIP SW2 Configuration
PCB Status LEDs
LED
Description
D38
12V Power
D39
3.3V Power
D48
Reader #1
D37
Reader #2
D46
Heartbeat
D31
Lock #1
D21
Lock #1
Bypass
D30
Lock #2
D12
Lock #2
Bypass
Signal
Reader Config Wire Color
Term Block
12V Batt
J1 pin 1
RED
J4 - TB-2
GND
J1 pin 2
BLACK
J4 - TB-1
GND
J1 pin 3
BLACK
J4 - TB-1
12V Batt
J1 pin 4
RED
J4 - TB-2
RD2 Data +
J12 pin 1
WHITE
J5 - TB-3
RD2 Data -
J12 pin 2
GREEN
J5 - TB-4
RD1 Data +
J12 pin 3
WHITE
J5 - TB-3
RD1 Data -
J12 pin 4
GREEN
J5 - TB-4
Controller Board RAC5 Reader Connections
Controller Board
Contactless Reader
Wire connection to back of contactless card reader
TB-1 (BLACK), TB-2 (RED), TB-3 (WHITE), TB-4 (GREEN)