107
ED50
08-2018
DL4614-140
dormakaba ED50 OHC Installation Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting Description
Upgrade card professional, extended
hold-open time
1. Once upgrade card installed, parameter value will automatically change to 2.
2. Setting range of
dd
, hold -open time is extended from 0 - 30 s to 0 - 180 s.
41
0, 2, 3
0
Upgrade card professional, nurse - bed
function (double doors only)
1. Once upgrade card installed, parameter value will automatically change to 1.
2. Function must be activated by changing parameter
F5
to 2.
3. For double doors, this function enables:
• Separate door opening (only active door, nurse)
• Both doors open (active, inactive doors, bed)
• Permanent opening?
4. The activator connected to the external detector (terminal board X4, 41 and 3)
controls the active door (nurse function). Only the active door will open.
5. The activator connected to the internal detector (terminal board X4, 42 and 1) controls
the both active and inactive doors (bed function), both doors will open.
6. If Push & Go function
PG
is activated, only the active door will open in the event of a
manual opening.
7. Night-bank inputs will only cause the active door to open.
8. Exit only program switch function is not available with
F5
activated.
42
0, 1,
2, 3
0
Upgrade card barrier free toilet
1. Once upgrade card installed, parameter value will automatically change to 1.
2. Function must be activated by changing parameter
F7
to 2.
3. Operator power reset is required; turn power switch off, wait 10 s and turn power back
on.
4. Upgrade card assigns inputs and outputs of the control unit with functions which are
required for this application.
43
0, 1,
2, 3
0
Upgrade card DCW
®
1. Once upgrade card installed, parameter value will automatically change to 2.
2. Upgrade card provides operator with DCW
®
bus connection.
3. Plug for terminal board X8 socket included with upgrade card.
4. DCW
®
bus enables connection of:
• Program switch EPS DCW
®
(max. 2)
• Motor lock controls SVP-S 2x DCW
®
(max. 2)
• Motor lock SVP 2000 (max. 1)
• RM-ED lintel mounted smoke detector
• Key switch button ST 32 DCW
®
(max. 2)
• I/O module DCW (max. 1)
44
0, 2, 3
0
COM 1 configuration interface
45
0 - 1
0
0
Interface programmed for communication with dormakaba handheld.
1
Interface programmed for use with dormakaba TMS Soft control software.
Back check when door opened manually
1. Angle after which door is braked when manually opened.
2. Back check level is automatically optimized during manual door opening cycles. This
function improves door braking behavior in end position so door does not move beyond
set opening angle
OA
(v1.7).
3. Entered value is subtracted from set opening angle
OA
.
4. Example
• Opening angle, 90°
• Parameter
bc
, 12°
• Door back check starts at 78°.
46
5 - 40
(v1.9)
°
10