64
ED50
08-2018
DL4614-140
dormakaba ED50 OHC Installation Instructions
Chapter 29
Step 1
Press
Press and hold PRG button greater
than 3 seconds to enter program
mode,
AS
parameter is displayed.
If no change required, go to step 7.
Step 2
Press
Displays "00" , factory setting.
Step 3
Press
"00" starts flashing.
Step 4
Press
Scroll to select parameter value.
"4", OHC LH shown as example.
Step 5
Press
Saves value entered. Display stops
flashing.
Step 6
Press
Returns to Installation type parameter.
29.7.1 Set parameter AS, installation type.
Installation type
Parameter
value
Parameter description
0*
Pull arm with track, wall mounting on swing
(hinge) side.
1
Push arm, wall mounting on approach (opposite
hinge) side.
2
Push arm with track, wall mounting on approach
(opposite hinge) side.
3
Overhead concealed (OHC) RH: Ref. Para. 29.6
4
OHC LH: Ref Para. 29.6
*
Factory setting
29.7 Set configuration parameters
Fig. 29.7.1 4 button keypad,
2 digit display
3
Four button keypad
4
Two digit display
4
3
> 3s Reset
< 3s Quit
> 3s
PRG
< 3s
LEARN
Fact-Setup
> 3s
> 8s
Step 7
Press
Scroll to
Tb
parameter.
Step 8
Press
Displays "10" , factory setting.
Step 9
Press
"10" starts flashing.
Step 10
Press
Scroll to select parameter value.
"9" shown as example.
Step 11
Press
Saves value entered.
Display stops flashing.
Step 12
Press
Returns to door width parameter.
Step 13
Press
Exit program mode. Display indicates
"ready for learning cycle".
29.7.2 Set parameter Tb, door width.
29.7.3 Parameter dL, door type.
TIPS AND RECOMMENDATIONS
Reference Chapter 30 for door width
parameter values.
TIPS AND RECOMMENDATIONS
Parameter
dL
factory setting is 0, single door.