TS 99 FLR EN 2-5

3

1)

  AAuPZF of the Deutsches Institut für Bautechnik, Berlin

2)

  See connection diagrams

Technical Data TS 99 FLR

Input: 

230 V AC +10% / –15% 

 

120 mA / 28 VA / 50 Hz 

Output: 

24 V DC / 460 mA / 11 W 

Type of Protection:  IP 30 

Protection class: 

II 

Smoke switch: 

24 V DC / 50 mA 

Temperature: 

–20°C / +60°C 

Rel. air humidity:  

max. 93% without condensation 

Technical Data, Hold‑open Device (EMF)

Operating voltage:   24 V DC 

Power input:  

2 W  

Duty factor:  

100% continuous duty 

  Work on electrical equipment and systems may only be 

performed by properly trained specialist personnel.

 

Check to ensure that the line power supply (230V AC) 

has been disconnected and is no longer live.

 

B‑10A / B‑16A miniature circuit breaker must be 

provided in the supply circuit. This can also be used 

as the isolator for disconnecting the FLR and making 

it dead.

 

The power cable leading to the FLR must be properly 

secured to ensure effective strain relief.

 

The power cable (NYM) conductor cross section should 

be not greater than max. 1.5 mm

2

. The PE conductor 

is not electrically utilised. The terminal (PE) should, 

however, be used where a PE conductor is provided.

 

Fire/smoke detectors controlling hold‑open systems 

must not be used to actuate any further alarm devices 

(e.g. fire alarm transmission systems).

 

+

 

1)

 

If the optional alarm module is installed, the cable 

connecting it to the smoke switch must be led over and 

across the measurement chamber in order to ensure 

that smoke penetration is in no way hindered.

 

According to the guidelines for hold‑open systems 

issued by the Institute of Building Technology, Berlin, 

it must be possible to release every hold‑open device 

by manual means. If free‑swing door closers are used, 

release must be initiated by a manual pushbutton. The 

manual release pushbutton used for this must be red 

and carry the inscription “Close Door”. The pushbutton 

must be in the immediate vicinity of the door (barrier) 

and must not be concealed when the door (barrier) 

is open.

 

À

  Integral lintel-mounted smoke detector.  

Á

  Electro-magnetic hold-open device. 

Â

  Ceiling-mounted smoke detector.  

Ã

   DORMA HT manual release pushbutton 

for hold-open devices.

 a 

  Installation arrangement of the FLR for applications 

where the bottom surface of the ceiling is less than 1 m  

above the bottom edge of the lintel on one or both 

sides of the door. 

+

 1)

 

See separate sheet for associated connection diagrams.

 b 

  If the bottom surface of the ceiling is more than 1 m 

above the bottom edge of the lintel on one or both 

sides of the door, two ceiling-mounted smoke detectors 

must be installed in addition to the lintel-mounted 

detector (FLR). 

+

 1)

 

See separate sheet for associated connection diagrams.

 1 

  Drill fixing points for closer and slide channel

 2 

  using TS 99 FLR template or as per 

dimensioned drawing.

 3 

  Drill holes of 14 mm dia. and install cabling for the 

230V AC power supply (by others), for connection to 

the manual pushbutton and for any required ceiling-

mounted detectors.

 4 

  LH (ISO 6) (as-delivered condition). 

Fix mounting backplate with smoke detector. 

For RH (ISO 5) handing, re-arrange the smoke detector 

as indicated in Figures 5, 6 and 7.

 5 

  Remove cover 

À

, smoke duct 

Á

 and smoke detector 

Â

.

 6 

  Re-assemble smoke duct 

À

 cover 

Á

 and smoke 

detector 

Â

 for RH (ISO 5) arrangement. The cotter pins 

in the mounting backplate must in this case be located 

in the two recesses of the smoke detector.

 7 

  Fix mounting backplate with smoke detector.

 8 

  Fix closer to the mounting backplate.

 9 

  Attach slide channel, align and tighten screws.

 10 

  Open door 

À

Position arm at an angle of approx. 80° to the 

doorframe 

Á

 and secure with screw 

Â

.

 11 

  Close valve for adjusting the closing speed 

À

Preload arm approx. 45° 

Á

.

 12 

  Remove arm 

À

 and, turning 90°, re-fit 

Á

 and 

tighten 

Â

.

 13 

  Connect arm to slide block.

 14 

  Adjust spring strength (closing force).

 15 

  Adjust closing speed 180° – 0° 

À

.  

Adjust latching action 7° – 0° 

Á

.

 16 

 

Terminal assignment FLR

3 GND

Connection of external-
detectors with terminal 
resistor

 2)

Total output  
rating max. 9.8 W

12 + 24 V
14

1 +

24 V DC output to 
hold-open device(s)

4 –

2

External manual release 
PB with terminal resistor

 

10

7 NO

Floating change-over contact  
(SELV) 
24 V AC/DC, 1 A

8 NC
9  C

11

Floating terminal

16

Bus

EN

Fixing Instructions 

Содержание TS 99 FLR

Страница 1: ...tell vorrichtungen a Montage der Festellanlage FLR wenn die Unterfläche der Decke auf einer oder auf beiden Seiten der Tür weniger als 1 m über der Sturzunterkante liegt 1 Entsprechende Anschlusspläne siehe separates Blatt b Ist die Unterfläche der Decke auf einer oder auf beiden Seiten der Tür mehr als 1 m über der Sturzunterkante sind zusätzlich zum Sturzmelder FLR zwei Decken melder anzubringen...

Страница 2: ...l nicht beschädigt werden DORMA Logo aufclipsen à Gleitschienenverkleidung aufclipsen Ä 24 Funktionsprüfung Anwendungs und Sicherheitshinweise auf dem Prüfgas und Sicherheitsdatenblatt beachten Türflügel öffnen À Prüfgas Hekatron 918 5 aus ca 10 15 cm Entfernung in Richtung Rauchkammer sprühen Á Die Betriebsanzeige schaltet auf Alarm rot um Ist der FLR mit dem RS Alarmmodul Option ausgestattet wir...

Страница 3: ...Á Electro magnetic hold open device  Ceiling mounted smoke detector à DORMA HT manual release pushbutton for hold open devices a Installation arrangement of the FLR for applications where the bottom surface of the ceiling is less than 1 m above the bottom edge of the lintel on one or both sides of the door 1 See separate sheet for associated connection diagrams b If the bottom surface of the ceil...

Страница 4: ...ded on the test gas container and safety datasheet Open door leaf À Spray test gas Hekatron 918 5 from a distance of approx 10 15 cm towards the smoke chamber Á After approx 4 6 short bursts the status display should switch to alarm red If the FLR is equipped with the RS smoke alarm module option an audible alarm is also sounded The hold open device is tripped and released and the door closes  St...

Страница 5: ...ekstra røgdetektoreri henhold til afsnittet i DBI Dansk Brand ogsikringsteknisk Institut Se DBI forskrift nr 231 Se separat tilslutningsskema b Hvis højden på den ene side er over 1 m anvendes røgdetektor i loftet på den høje side af døren Se DBI forskrift nr 231 Se separat tilslutningsskema 1 Afmærk befæstigelsespunkter til dørlukker 2 og glideskinne efter boreskabelonen TS 99 FLR eller efter mål...

Страница 6: ...kkerhedsanvisningerne på testgas og sikkerhedsdatabladet Åbn døren À Spray testgas Hekatron 918 5 mod røgkammeret fra en afstand på ca 10 15 cm Á Efter ca 4 6 korte pust skifter driftsindikatoren til alarm lyser rødt Hvis FLR er forsynet med et RS alarmmodul valgfrit indikeres alarmen også akustisk Strømmen til fastholdet afbrydes og døren lukkes  Driftsindikatoren blinker grønt så snart der ikke...

Страница 7: ...eden skal bestemmelserne for placering i afsnit 2 4 følges Krav til dørlukningstryk er angivet i afsnit 2 8 2 4 Røgdetektorer Der skal installeres en røgdetektor på hver side af døren hørende til samme anlæg i en vandret afstand på mindst 0 5 m og op til 6 0 m målt fra ethvert punkt i døråbningen Såfremt en røgdetektor ikke kan overvåge hele døråbningen skal der installeres yderligere røgdetektore...

Страница 8: ...TS 99 FLR EN 2 5 Änderungen vorbehalten dormakaba Deutschland GmbH DORMA Platz 1 58256 ENNEPETAL Tel 49 2333 793 0 Fax 49 2333 793 4950 www dormakaba com ...

Отзывы: