TS 99 FLR EN 2-5
—
3
1)
AAuPZF of the Deutsches Institut für Bautechnik, Berlin
2)
See connection diagrams
Technical Data TS 99 FLR
Input:
230 V AC +10% / –15%
120 mA / 28 VA / 50 Hz
Output:
24 V DC / 460 mA / 11 W
Type of Protection: IP 30
Protection class:
II
Smoke switch:
24 V DC / 50 mA
Temperature:
–20°C / +60°C
Rel. air humidity:
max. 93% without condensation
Technical Data, Hold‑open Device (EMF)
Operating voltage: 24 V DC
Power input:
2 W
Duty factor:
100% continuous duty
Work on electrical equipment and systems may only be
performed by properly trained specialist personnel.
•
Check to ensure that the line power supply (230V AC)
has been disconnected and is no longer live.
•
B‑10A / B‑16A miniature circuit breaker must be
provided in the supply circuit. This can also be used
as the isolator for disconnecting the FLR and making
it dead.
•
The power cable leading to the FLR must be properly
secured to ensure effective strain relief.
•
The power cable (NYM) conductor cross section should
be not greater than max. 1.5 mm
2
. The PE conductor
is not electrically utilised. The terminal (PE) should,
however, be used where a PE conductor is provided.
•
Fire/smoke detectors controlling hold‑open systems
must not be used to actuate any further alarm devices
(e.g. fire alarm transmission systems).
+
1)
•
If the optional alarm module is installed, the cable
connecting it to the smoke switch must be led over and
across the measurement chamber in order to ensure
that smoke penetration is in no way hindered.
•
According to the guidelines for hold‑open systems
issued by the Institute of Building Technology, Berlin,
it must be possible to release every hold‑open device
by manual means. If free‑swing door closers are used,
release must be initiated by a manual pushbutton. The
manual release pushbutton used for this must be red
and carry the inscription “Close Door”. The pushbutton
must be in the immediate vicinity of the door (barrier)
and must not be concealed when the door (barrier)
is open.
À
Integral lintel-mounted smoke detector.
Á
Electro-magnetic hold-open device.
Â
Ceiling-mounted smoke detector.
Ã
DORMA HT manual release pushbutton
for hold-open devices.
a
Installation arrangement of the FLR for applications
where the bottom surface of the ceiling is less than 1 m
above the bottom edge of the lintel on one or both
sides of the door.
+
1)
See separate sheet for associated connection diagrams.
b
If the bottom surface of the ceiling is more than 1 m
above the bottom edge of the lintel on one or both
sides of the door, two ceiling-mounted smoke detectors
must be installed in addition to the lintel-mounted
detector (FLR).
+
1)
See separate sheet for associated connection diagrams.
1
Drill fixing points for closer and slide channel
2
using TS 99 FLR template or as per
dimensioned drawing.
3
Drill holes of 14 mm dia. and install cabling for the
230V AC power supply (by others), for connection to
the manual pushbutton and for any required ceiling-
mounted detectors.
4
LH (ISO 6) (as-delivered condition).
Fix mounting backplate with smoke detector.
For RH (ISO 5) handing, re-arrange the smoke detector
as indicated in Figures 5, 6 and 7.
5
Remove cover
À
, smoke duct
Á
and smoke detector
Â
.
6
Re-assemble smoke duct
À
cover
Á
and smoke
detector
Â
for RH (ISO 5) arrangement. The cotter pins
in the mounting backplate must in this case be located
in the two recesses of the smoke detector.
7
Fix mounting backplate with smoke detector.
8
Fix closer to the mounting backplate.
9
Attach slide channel, align and tighten screws.
10
Open door
À
.
Position arm at an angle of approx. 80° to the
doorframe
Á
and secure with screw
Â
.
11
Close valve for adjusting the closing speed
À
.
Preload arm approx. 45°
Á
.
12
Remove arm
À
and, turning 90°, re-fit
Á
and
tighten
Â
.
13
Connect arm to slide block.
14
Adjust spring strength (closing force).
15
Adjust closing speed 180° – 0°
À
.
Adjust latching action 7° – 0°
Á
.
16
Terminal assignment FLR
3 GND
Connection of external-
detectors with terminal
resistor
2)
Total output
rating max. 9.8 W
12 + 24 V
14
1 +
24 V DC output to
hold-open device(s)
4 –
2
External manual release
PB with terminal resistor
10
7 NO
Floating change-over contact
(SELV)
24 V AC/DC, 1 A
8 NC
9 C
11
Floating terminal
16
Bus
EN
Fixing Instructions