![DORCHESTER DR-FC 120 Скачать руководство пользователя страница 83](http://html1.mh-extra.com/html/dorchester/dr-fc-120/dr-fc-120_installation-comissioning-and-maintenance-instructions_2521679083.webp)
Instruction manual DR-FC
81
is
14
Service interval
14.1 Introduction
A service should be carried out at least once a year, both on the water side and
on the gas side. Among other things, the service interval depends on the water
quality, the average burning time per day and the set water temperature.
Note
Regular maintenance extends the service life of the water heater.
To determine the correct service interval, it is recommended to arrange for the
service and maintenance engineer to check the water heater on both the water
and gas side three months after installation. Based on this check, the best
service interval can be determined.
14.2 Determining service
interval
See Errata.
and maintenance engineer can determine the frequency of maintenance, based
on the number of burning hours.
The service interval can be set to: 500, 1000 or 1500 burning hours. The
standard setting is 500 burning hours.
Example
In the first three months, the water heater has burnt 300 hours. During
maintenance, it is evident that one service per year will be sufficient. Therefore,
after one year, some 1200 burning hours will have elapsed. The first value below
1200 hours that can be selected is 1000 burning hours.
In this case, the service and maintenance engineer sets the interval to 1000.
In the first three months, the water heater has burned for 300 hours. During
maintenance, it is evident (perhaps due to the water quality) that service will be
required at least once every 6 months.
Therefore, after six months, some 600 burning hours will have elapsed. The first
value below 600 hours that can be selected is 500 burning hours.
In this case, the service and maintenance engineer sets the interval to 500.
Once the set number of burning hours has elapsed, the message
SERVICE REQUIRED
will appear on the display. When this message
appears, the service and maintenance engineer must be contacted.
!!!
WARNING
!!!
MAX. BURNINGHOURS:
SERVICE REQUIRED
Содержание DR-FC 120
Страница 2: ......
Страница 4: ......
Страница 6: ...4 Instruction manual DR FC gis...
Страница 10: ...Table of contents 8 Instruction manual DR FC...
Страница 30: ...Installation 28 Instruction manual DR FC 3 is Installation types IMD 0790 R0 C43 C13 C53 B23 C33...
Страница 58: ...Shutting down 56 Instruction manual DR FC 10 gis...
Страница 70: ...Service program 68 Instruction manual DR FC 12 is...
Страница 84: ...Service interval 82 Instruction manual DR FC 14 is...
Страница 89: ...Instruction manual DR FC 87 s 16 Warranty Contact your supplier for the warranty conditons of this water heater...
Страница 90: ...Warranty 88 Instruction manual DR FC 16 s...
Страница 93: ...Instruction manual DR FC 91 is...
Страница 96: ...Appendices 94 Instruction manual DR FC 17 is...
Страница 98: ...Instruction manual DR FC 96...