background image

6555-065-A-12-18

16

4404-01

0

TIME

DELAY

EXIT
LOOP

LMT

REVERSE

LOOP

REV SENSE

OPEN

REV SENSE
CLOSE

1

ON

2

3

4

1

ON

2

3

4

5

6

7

8

NC

NO

P8

P7

P6

20

19

18

17

16

15

14

13

12

11

10

987

6

5

4

3

2

1

OB

CB

OE

CE

G

G

1

ON

1477-010

SW1

2 3 4

1
2
3

P9

1
2
3

FIRE

SECTION 3 - ADJUSTMENTS

3.1 Circuit Board Description and Adjustments

The switch settings and adjustments in this chapter should be made after your installation and wiring to the operator(s) is 
complete. 

Whenever any of the programming switches on the circuit board are changed, power must be shut-off, and then 

turned back on for the new setting to take effect.

Auto-close timer 
(when turned on) 
SW 1, switch 2.

Dry relay contacts 
(terminals 11-12) can 
be set for Normally 
Open (NO) or Normally Closed 
(NC) operation by placing the 
relay shorting bar on the N.O. or 
N.C. pins respectively. SW 1, 
switches 4 and 5 must be set to 
control relay. See next 2 pages 
for descriptions.

Auto-Close Timer

AC Module
Adjustment

Single Channel

Loop Detector

Dry Relay
Contact

3-Button Control
Station Jumper 

page 23

UL 325 Terminal
and DIP Switches

See pages 24-25

Adjust reversing sensitivity for open and close 
directions.
Full counter clockwise for minimum sensitivity, 
full clockwise for maximum sensitivity.
See page 20.

Inherent Reverse Sensors

Motor Plug P6

Self-test (when 

turned on) SW 2, 

switch 1.

CAUTION

  

Do not

 run self-test with the operator 

connected to the gate. The drive chain 

MUST

 be 

disconnected before running the self-test. This 
feature is designed for bench testing 

ONLY

.

Self-Test

Power LED

94

10

9409

1

23

Adjust from 1 second 
(full counter-clockwise) 
to approximately 23 
seconds (full clockwise).

Min

Max

CLOSE

Sensitivity

OPEN

MIN

MAX

Min

Max

Speed

See page 21.

Set the DIP-switches on the circuit 
board to the desired setting. See switch 
descriptions on next 2 pages.

DIP-Switches

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

1

ON

2

3

4

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

Limit LEDs

See page 19

8

7

6

5

4

3

Main T

erminal 

Input LEDs 

See page 22

Gate Tracker

Terminal 

See page 23

Limit Sensor

Plug P2

See page 19

Exit Loop Por

Reverse Loop Por

t

Sensor Input LEDs

See page 20

LEDs 

Indicates that low voltage power is applied to the circuit board. 

Input LEDs

 should be OFF and will only illuminate 

when the input is activated (see page 22). 

Limit LEDs

 will be on when the respective limit switch is activated.

See page 26.

Dual Channel

Loop Detector

See page 26.

NO

NC

Fire Dept Open

Connect 

ONLY

 emergency access 

controls accessible by authorized 
personnel (e.g., fire, police, EMS).  
Upon activation, alarm will sound 
and the operator will go into a 

hard 

shutdown

 after reaching the open 

limit. Operator must be reset to 
resume normal operation.
See pages 23, 28-29.

Содержание 6555

Страница 1: ...ided for the gate system where the risk of entrapment or obstruction exists The operator will NOT run without one or more monitored type B1 or B2 entrapment protection devices in EACH entrapment area...

Страница 2: ...OFF ON Internal alarm will NOT sound Internal alarm will sound before gate starts and throughout gate s cycle Auto close timer is OFF Manual input required to close gate Auto close timer is ON Adjusta...

Страница 3: ...port of the circuit board Main Terminal 3 Note Exceeding 250 mA of power from this terminal may cause the circuit board transformer to overheat causing intermittent problems QUICK GUIDE Terminal Desc...

Страница 4: ...trapment Protection Device Inherent Reverse Sensor System Type A External Entrapment Protection Device Inputs Connection inputs for Non contact Sensor Photo Sensor Type B1 Monitored Inputs Connection...

Страница 5: ...tection Wiring 4 4 Loop Detector Wiring SECTION 7 OWNER OF THE GATE OPERATOR 37 37 38 39 41 7 1 Alarm Sounding and Gate WILL NOT Operate 7 2 Manual Gate Operation 7 3 Gate Operators Monthly Checkup Pr...

Страница 6: ...tection is REQUIRED for this area B C B Closed Gate With the hinge mounted on the corner of the pilaster the entrapment area is eliminated and entrapment protection is NOT required for this area Close...

Страница 7: ...CLOSE Sensor Type B2 Reverse Loop Shadow Loop Automatic Exit Loop Minimizes the potential of the gate closing when a vehicle is present Number and placement of loops is dependent on the application R...

Страница 8: ...operator clutch pressure relief valve or reduce reversing sensitivity to compensate for a damaged gate For gate operators utilizing Type D protection 1 The gate operator controls must be placed so th...

Страница 9: ...s are installed a minimum distance of 6 feet away from the gate and gate operator or in such a way that a person cannot touch the gate or gate operator while using the device If access control devices...

Страница 10: ...ct closer than 16 inches 406 mm are not required to be provided with a means of entrapment protection Horizontal Slide Vertical Lift Vertical Pivot Swing Vertical Barrier Arm A B1 B2 or D A B1 B2 C or...

Страница 11: ...for vehicular traffic flow at entrances or exits to areas such as parking garages lots or toll areas VEHICULAR HORIZONTAL SLIDE GATE OPERATOR OR SYSTEM A vehicular gate operator or system that control...

Страница 12: ...5 safety and ASTM F2200 construction standards The proper installation of the vehicular swing gate operator is an extremely important and integral part of the overall access control system Check all l...

Страница 13: ...46 15 63 32 Min 52 25 34 46 15 43 63 37 Measured Length 2 24 67 88 86 26 Connecting Arm Drive Arm Drive Arm 67 88 2 33 94 round number up 34 inches Connecting Arm 86 26 33 94 52 32 round number down...

Страница 14: ...to the concrete pad using six 6 3 8 x 3 sleeve anchors not supplied 1 5 Securing Operator to Pad Sleeve Anchor Not supplied 3 8 208 230 460 Step Down Transformer Plate Remove breather pin from gear r...

Страница 15: ...elease hub with release tool DO NOT REMOVE HUB Bolt crank arm to operator Slide elbow assembly on crank arm Bolt control arm to gate bracket Slide control arm into elbow assembly KEEP ARM ASSEMBLY LEV...

Страница 16: ...King Swing Gate Operator is shipped with two warning signs The purpose of the warning sign is to alert uninformed persons and to remind persons familiar with the gate system that a possible hazard exi...

Страница 17: ...ection of photo sensors Type B1 and or reversing edges Type B2 entrapment protection required by UL 325 standards Entrapment Protection must be provided for the gate system where the risk of entrapmen...

Страница 18: ...ent or obstruction exists less than 16 from the open gate then entrapment protection is REQUIRED for this area OPTIONAL wireless transmitter can be used Receiver MUST monitor for the presence of the t...

Страница 19: ...Disconnect Switch Route incoming high voltage power through conduit and into the operator as shown Be sure wiring is installed in accordance with local codes Be sure to color code all wiring It is re...

Страница 20: ...ee page 20 Inherent Reverse Sensors Motor Plug P6 Self test when turned on SW 2 switch 1 CAUTION Do not run self test with the operator connected to the gate The drive chain MUST be disconnected befor...

Страница 21: ...und before gate starts and throughout gate s cycle Auto close timer is OFF Manual input required to close gate Auto close timer is ON Adjustable from 1 23 seconds to close gate 6 Relay activates and L...

Страница 22: ...is installed in the EXIT loop port of the circuit board Which must be installed for the OFF setting to function Switches 4 5 These work in conjunction with each other and determine when the relay on...

Страница 23: ...TOM Limit Bracket EXIT LOOP LMT LMT Opens Counter clockwise SW 1 1 ON 2 3 4 5 6 7 8 Switch 1 ON Opens Clockwise P2 Note If P2 plug is not connected to the circuit board and AC power is turned on alarm...

Страница 24: ...nsidered a turn The number of turns through the sensing coil is dependant on the operating voltage of the operator the speed of the gate and the weight of the gate In general light weight gates may re...

Страница 25: ...i ci an us e on ly MI N MA X MIN MAX Min Max Speed 3 6 Gate Speed Description and Adjustment Knob Adjustment The 6555 models are equipped with an AC module that allows you to adjust the speed of the g...

Страница 26: ...m a plug in loop detector installed in the EXIT loop port of the circuit board Main Terminal 3 Note Exceeding 250 mA of power from this terminal may cause the circuit board transformer to overheat cau...

Страница 27: ...use a separate power source 4 Opens gate P9 1 2 3 Main Terminal 3 Note Exceeding 250 mA of power from this terminal may cause the circuit board transformer to overheat causing intermittent problems O...

Страница 28: ...ONAL Expansion Kit sold separately will allow connection for additional devices 1 2 3 4 5 6 OPEN Beam STOP Switch 1 CLOSE Beam REVERSE Switch 2 OPEN Edge Beam REVERSE Switch 3 CLOSE Edge Beam REVERSE...

Страница 29: ...apment or obstruction exists less than 16 from the open gate then entrapment protection is REQUIRED for this area Receiver MUST monitor for the presence of the transmitter Type of wiring to be used on...

Страница 30: ...C NO DoorKing Plug In Single Channel Loop Detector 9410 DoorKing Plug In Dual Channel Loop Detector 9409 LOOP 1 LOOP 2 LOOP 1 To help protect the operator from accidentally closing on vehicles in the...

Страница 31: ...just and retest the gate operator properly can increase the risk of injury or death 5 Use the emergency release only when the gate is not moving and power has been shut off 6 KEEP GATES PROPERLY MAINT...

Страница 32: ...sensed by the inherent system the gate will reverse and run back to the closed position The time clock input is still present but the gate will not re open Example 2 If the gate is closing and an entr...

Страница 33: ...t loop Activation of a close command will run the gate to the closed position Before resetting a hard shutdown determine why the shutdown occurred Inspect the gate for any obstructions along its path...

Страница 34: ...nual Release Remove release tool and place where shown Release hub Gate can now be manually operated B C Unlock the cover and rotate sliding door A CAUTION DO NOT REMOVE HUB Never attempt to manually...

Страница 35: ...should be performed anytime a malfunction is observed or suspected High cycle usage may require more frequent service checks Operator Component Maintenance Monthly Interval 6 1 12 Alarm Arms Drive Be...

Страница 36: ...to the DoorKing Loop and Loop Detector Information Manual located on DoorKing s web site 4 Check to be sure that there are no shorted or open control wires from the keying devices to the gate operato...

Страница 37: ...Section 6 2 Shutdown Conditions page 32 Check the gate and gate hardware for any binding correct where necessary Gate may be too heavy Check for any input or loop detector LED s that are ON Check that...

Страница 38: ...Single channel detector with aux relay P N 9411 010 Single channel low power draw detector P N 9416 010 Dual channel low power draw detector P N 9415 010 External Loop Detector Reno A E 12 24 VDC or...

Страница 39: ...e TWO allen screws on bottom of hub to remove the complete hub assembly Limit Sensor Assemblies Loosen set screws on plastic limit assemblies to remove them Be CAREFUL not to damage limit sensor wires...

Страница 40: ...9 8 7 6 5 4 3 2 1 Board Ground 1 ft s 5 ft s 0 ft s 2 ft s 1 5 ft s Shield Orange Black Black Shield Orange Red Black Black Black Black Black NO Black Black Black Black Green Green NO White White Whi...

Страница 41: ...on again Note The owner of the gate operator is responsible for the KEY availability SECTION 7 OWNER OF THE GATE OPERATOR AC POWER OFF RESET Gate Operator is in a Hard Shutdown Condition when Alarm is...

Страница 42: ...the cover and power switch cover on this gate operator Please read SECTION 5 OPERATING INSTRUCTIONS for more information about operating this gate operator Note The owner of the gate operator is respo...

Страница 43: ...the gate will resume opening when the beam is clear If gate does NOT respond like it should in either direction of gate travel contact a trained service technician to make adjustments or repairs Test...

Страница 44: ...6555 065 A 12 18 40 This page intentionally left blank...

Страница 45: ...of the alarm cannot be corrected shut off power and DO NOT place this operator back into service until the malfunction can be identified and CORRECTED IMPORTANT Putting this gate operator back into s...

Страница 46: ...n exists The operator will NOT run without one or more monitored type B1 or B2 entrapment protection devices in EACH entrapment area UL 325 August 2018 Standard THIS PRODUCT IS TO BE INSTALLED AND SER...

Отзывы: