Mounting
Bracket
and
Hardware
Watertight
Conduit
and
Connectors
The plastic enclosure comes with mounting brackets and hardware to mount
on enclosure.
Mount enclosure on surface using appropriate hardware (not included).
IT IS NOT RECOMMENDED DRILLING HOLES IN THE PLASTIC ENCLOSURE!
If
holes must be drilled, remove the circuit board before drilling and be sure that
mounting bolts/screws
DO NOT
touch the back of the circuit board.
Holes
must be sealed to prevent water intrusion.
If the cellular control box is installed
OUTDOORS
, watertight conduit and
connectors
MUST
be used for
ALL
field wiring connections.
Installation
Wire Runs
Wiring methods used shall be in accordance with
National Electrical Code, ANSI/NFPA 70.
Permissible wire sizes for the terminals (12-26 AWG).
Type of wiring to be used on ALL external devices:
A)
Type
CL2
,
CL2P
,
CL2R
, or
CL2X
.
B)
Other cable with
equivalent
or
better
electrical, mechanical, and flammability ratings.
Cellu
lar
System
Entr
y Syste
m
DoorKing offers an exterior 3G cellular antenna that can help in areas
with weak cellular service (P/N 1514-014 Sold separately).
Optional External
Cellular Antenna
2