Control unit LEDs

LEDs in bold type indicate the state when the door is stopped in the middle position.

LED                                    

Function                                                                           

On                                                            

Off

PWR

Motor power supply

On

Off

A (red)

Record of remote controller code

On

Off

B (yellow)

Failure (emergency)

On

Off

ST

START command

On

Off

PED

PED command

On

Off

Ph1

Photocells to close

Do not respond

Respond

Ph2

Photocells to open

Do not respond

Respond

STOP

STOP command

Out

On

Sw1

Limit switch to close

Does not respond

Responds

Sw2

Limit switch to open

Does not respond

Responds

1.3. Description of terminals of control unit

  1.  Pins to connect power supply (pin J1)

 ~220 (N, L, PE)

 — pin to connect power supply unit.

PE - protection earth.
N — power supply (neutral). 
L — power supply (phase).

  2.   Pins to connect motor (pin J2)

MOTOR (N, L1, L2)

 — to connect motor unit. Make sure that the motor is connected as shown at the diagram.

3. Pins to connect warning light (pin  J3)
LAMP

 — pin to connect warning light of 230 V, max. 40 W. Operates at any movement of the door leaf. The light flashes with

a period of 0.5-1 sec.

  4.   Pins to connect accessories (pin J4)

START — command  «Complete opening» (NO)

Closing of the contacts of the device connected to this terminal triggers the control unit for complete opening and/ or closing
of the door (the exact logic depends on the position of DIP1 switch).

DIP1 — off.

 It generates the command in cycle mode - Open-Stop-Close-Stop.

DIP1 — on.

 It generates the command in cycle mode - Open-Limit switch-Close (no stop is provided during movement).

To connect some devices , it’s necessary to connect normally open (NO) contacts of these devices in parallel.

Ped  —command Pedestrian ( pedestrian crossing) (NO)
DIP2 — off.

 Ped command results in the door opening for approximately 1 m. Repeated Ped command results in the door

closing. If Start command follows after Ped command, the control unit generates a command for complete closing of the door.
Ped command at DIP2-off in the closed position of the door opens the door for 1 m, in the opened position of the door closes
the door completely.

DIP2 — on.

 It crries out separate drive controll, i.e. Start command opens the door, Ped command closes the door. 

To connect some devices , it’s necessary to connect normally open (NO) contacts of these devices in parallel.

SW OP/SW CL

 — — limit switches signals in extreme positions of the door leaf.

Limit switch operation (opening of the contact) SW OP / SW CL means that the door leaf is in the extreme opened/ closed
position and further movement in the same direction is prohibited.

Photo Cl

 — contacts to connect safety devices to close (NC). Devices operation results in immediate reverse movement of

the door leaf for complete opening. Operation of the devices connected to these terminals has no effect on operation during
the door opening.
If the door is open and sensors connected to these terminals respond, it will prevent from the door movement to close.

To connect some devices with NC contacts, it’s necessary to connect the contacts of these devices in series.

WARNING! 

If no devices are connected to these terminals, it’s necessary to install the jumper between contact terminals

“Ph CL” and “-“ (see wiring diagram).

eLeCtRICAL InteRFACeS

Содержание PCB-SL

Страница 1: ...DoorHan 2016 Programming instructions board PCB SL Actual versions pcb v 1 0 soft v 1 0 Content ReMote ContRoLLeR PRoGRAMMInG 2 3 CONTROL BOARD PCB SL...

Страница 2: ...erminals of control unit 4 1 4 DIP switches adjustment 5 1 5 Description of mechanically operated controls 5 2 REMOTE CONTROLLER PROGRAMMING 6 2 1 Cleaning of the receiver s memory 6 2 2 Record of Doo...

Страница 3: ...nect warning light see diagram Negative terminal for accessories power supply 24 V 600 mA 24 V Positive terminal for accessories power supply 24 V 600 mA Sw Op Output contact of limit switch to open S...

Страница 4: ...To connect some devices it s necessary to connect normally open NO contacts of these devices in parallel Ped command Pedestrian pedestrian crossing NO DIP2 off Ped command results in the door opening...

Страница 5: ...to install the jumper between EMRG contact terminals see wiring diagram 7 24 V DC output terminals of power supply transformer with 24 DC max load of 600 mA 1 4 DIP switches adjustment WARNING When ch...

Страница 6: ...s in the receiver s memory 60 pcs 2 3 Remote programming for Doorhan remote controllers Perform the items 1 4 within 5 second interval 1 Press and hold down the button 2 see figure of programmed remot...

Страница 7: ......

Страница 8: ...our company and believe that you will be satisfied with its quality For information on purchasing distribution and servicing contact DoorHan central office at Kralovsky VRCH 2018 Kadan 43201 Czech Rep...

Отзывы: