5
5. Photo Op
— contacts to connect safety devices to open (NC). These connections are used to protect the door leaf when
opening. Operation of the devices reslts in immediate stop. Operation of the devices connected to these terminals has no effect
on operation during the door closing. If the door is closed and sensors connected to these terminals respond, it will prevent
from the door movement to open. To connect some devices with NC contacts, it’s necessary to connect the contacts of these
devices in series.
WARNING!
If no devices are connected to these terminals, it’s necessary to install the jumper between contact terminals
“Ph Op” and “-“ (see wiring diagram).
6. EMRG
— contacts to connect emergency stop devices (NC). These connections are used to protect the door leaf when
opening and closing. Any logic of control unit operation by signal from these devices when opening and closing the door
provides immediate stop of the door. If the door is at rest and sensors connected to these terminals respond, it will prevent
from any door movement. To connect some devices with NC contacts, it’s necessary to connect the contacts of these devices
in series.
WARNING!
If no devices are connected to these terminals, it’s necessary to install the jumper between EMRG contact
terminals (see wiring diagram).
7. 24 V DC
— output terminals of power supply transformer with 24 DC, max. load of 600 mA.
1.4. DIP-switches adjustment
WARNING!
When changing the position of DIP-switches, it’s necessary to turn off and on again supply voltage of the
drive. Otherwise, adjustment will not take place.
Switcher
Function
Implementation
of functions
Switch
position
DIP1
Reject to receive commands during the door movement
Yes
ON
No
OFF
DIP2
Separate control:
START - opens, PED - closes
Yes
ON
No
OFF
DIP3
Drive location relative to the door opening
To the right
ON
To the left
OFF
DIP4
Drive-down in front of the limit switches
Yes
ON
No
OFF
1.5. Description of mechanically operated controls
TIMER W
— of reverse time after limit switch response.
AUTO CL
— adjustment of time delay before the door automatic closing. Time delay can be adjusted within the range from 0
to 70 seconds. Automatic closing function is off in the leftmost position of the control.
FORCE
— adjustment of drive traction force (set of maximum useful current). The drive force has a maximum value in the
rightmost position of the control, and the drive is operating at its full capacity (not recommended).
Adjusting of mechanically operated controls
To increase the parameter, turn the corresponding control clockwise.
To reduce the parameter, turn the corresponding control counterclockwise.
ELECTRICAL INTERFACES