  5.  Photo Op

 — contacts to connect safety devices to open (NC). These connections are used to protect the door leaf when 

opening. Operation of the devices reslts in immediate stop. Operation of the devices connected to these terminals has no effect 
on operation during the door closing. If the door is closed and sensors connected to these terminals respond, it will prevent 
from the door movement to open. To connect some devices with NC contacts, it’s necessary to connect the contacts of these 
devices in series.

WARNING! 

 If no devices are connected to these terminals, it’s necessary to install the jumper between contact terminals 

“Ph Op” and “-“ (see wiring diagram).
 

  6.   EMRG

 — contacts to connect emergency stop devices (NC). These connections are used to protect the door leaf when 

opening and closing. Any logic of control unit operation by signal from these devices when opening and closing the door 
provides immediate stop of the door. If the door is at rest and sensors connected to these terminals respond, it will prevent 
from any door movement. To connect some devices with NC contacts, it’s necessary to connect the contacts of these devices 
in series.

WARNING! 

 If no devices are connected to these terminals, it’s necessary to install the jumper between EMRG contact 

terminals (see wiring diagram).

  7. 24 V DC 

— output terminals of power supply transformer with 24 DC, max. load of 600 mA.

1.4. DIP-switches adjustment

WARNING!

 When changing the position of DIP-switches, it’s necessary to turn off and on again supply voltage of the 

drive. Otherwise, adjustment will not take place.

Switcher

Function

 

Implementation

 of functions

Switch 

position

DIP1

Reject to receive commands during the door movement

Yes

ON

No

OFF

DIP2

Separate control:

START - opens, PED - closes

Yes

ON

No

OFF

DIP3

Drive location relative to the door opening

To the right

ON

To the left

OFF

DIP4

Drive-down in front of the limit switches

Yes

ON

No

OFF

1.5. Description of mechanically operated controls

TIMER W

 — of reverse time after limit switch response.

AUTO CL

 — adjustment of time delay before the door automatic closing. Time delay can be adjusted within the range from 0 

to 70 seconds. Automatic closing function is off in the leftmost position of the control. 

FORCE

 — adjustment of drive traction force (set of maximum useful current). The drive force has a maximum value in the 

rightmost position of the control, and the drive is operating at its full capacity (not recommended).

Adjusting of mechanically operated controls

To increase the parameter, turn the corresponding control clockwise. 

To reduce the parameter, turn the corresponding control counterclockwise.

ELECTRICAL INTERFACES

Содержание PCB-SL

Страница 1: ...DoorHan 2016 Programming instructions board PCB SL Actual versions pcb v 1 0 soft v 1 0 Content ReMote ContRoLLeR PRoGRAMMInG 2 3 CONTROL BOARD PCB SL...

Страница 2: ...erminals of control unit 4 1 4 DIP switches adjustment 5 1 5 Description of mechanically operated controls 5 2 REMOTE CONTROLLER PROGRAMMING 6 2 1 Cleaning of the receiver s memory 6 2 2 Record of Doo...

Страница 3: ...nect warning light see diagram Negative terminal for accessories power supply 24 V 600 mA 24 V Positive terminal for accessories power supply 24 V 600 mA Sw Op Output contact of limit switch to open S...

Страница 4: ...To connect some devices it s necessary to connect normally open NO contacts of these devices in parallel Ped command Pedestrian pedestrian crossing NO DIP2 off Ped command results in the door opening...

Страница 5: ...to install the jumper between EMRG contact terminals see wiring diagram 7 24 V DC output terminals of power supply transformer with 24 DC max load of 600 mA 1 4 DIP switches adjustment WARNING When ch...

Страница 6: ...s in the receiver s memory 60 pcs 2 3 Remote programming for Doorhan remote controllers Perform the items 1 4 within 5 second interval 1 Press and hold down the button 2 see figure of programmed remot...

Страница 7: ......

Страница 8: ...our company and believe that you will be satisfied with its quality For information on purchasing distribution and servicing contact DoorHan central office at Kralovsky VRCH 2018 Kadan 43201 Czech Rep...

Отзывы: