PS17-TD2 

- 1 - 

Overview:

PS17-TD2 is a power supply that converts 115VAC, 60Hz input into two individually PTC protected 12VDC or 24VDC outputs (see specifi-
cations) and provides time delays to conform with both Delayed Egress and Access-Controlled Egress provisions of the U.S. model building 
codes. It is intended for use in applications requiring UL listing for Access Controls (UL294) and applications requiring an interface with Fire 
Alarm Control Panels. It must be installed in accordance with National and Local Electrical Codes and Regulations.

Specifications:

Requirements For Delayed Egress:

An audible alarm shall be provided that shall activate upon initiation of the delayed timing process and continue signaling until the 

door lock is released. Follow wiring diagram on pg. 3 for hookup. Please make sure the operating voltage of the sounding device matches 

the preset outout of power supply. Use 12V devices for 12V setting and 24V devices for 24V setting.
Special locking device interconnected with the power supply shall be plainly marked on the hardware assembly: “Controlled Egress 
Equipment and Systems”or “Delayed Egress Equipment and Systems”.
For delayed egress locking devices, the programmed time delay duration shall be plainly marked on the hardware assembly.

Requirements For Controlled Egress:

Activation of a fire alarm signal or fire sprinkler signal shall release the door latching mechanism to allow egress in a time frame 

not to exceed two seconds. The door shall remain unlocked until the fire alarm control unit has been reset.

Connect [TRIG1] and [TRIG2] terminals to Normally closed Fire alarm contact (fig. 3, pg. 5).
Special locking device interconnected with the power supply shall be plainly marked on the hardware assembly: “Controlled Egress 
Equipment and Systems”or “Delayed Egress Equipment and Systems”.
Equipment and systems shall be provided with a means to release door latches upon activation of a manual release switch intended to be 
installed within 5 feet of the door. Activation of this manual release switch shall cause the door to remain unlocked for 30 seconds Activate 
TRG and GND Input by means of NO dry contact. Follow wiring diagrams and DIP switch settings for proper hookup.
Equipment and systems utilizing an electromagnetic locking mechanism shall be capable of being operated with one hand. 
The releasing mechanism shall interrupt the power to the electromagnetic lock to unlock the door.

Requirements For Fire Exit and Panic Applications:

Equipment and systems designed as fire exit or panic hardware shall comply with the Standard for Panic Hardware, UL 305. 

Interruption of power shall cause the locking mechanism to unlock/release in less than 2 seconds. Do not use battery backup.
Activation of a fire alarm signal or fire sprinkler signal shall release the door latching mechanism to allow egress in a time frame not to 
exceed two seconds. The door shall remain unlocked until the fire alarm control unit has been reset. Connect [TRIG1] and [TRIG2] termi-
nals to Normally closed Fire alarm contact (fig. 3, pg. 5).
A means to release door latches upon activation of a manual release switch shall occur within two seconds following initiation of TRG and 
GND Input by means of NO dry contact. Follow wiring diagrams and DIP switch settings for proper hookup.

Agency Listings:

•  UL Listed for Access Control Systems (UL294*),
 

* ANSI/UL 294 7th Ed. Access Control Performance Levels: 

  Destructive Attack - I; Endurance - N/A; Line Security - I; 

  Stand-by Power - I, II.
•   cUL Listed - CSA Standard C22.2 No.205-M1983, 
  Signal Equipment.

Input:

•  Input 115VAC/60Hz, 0.6A.

Output:

•  Switch selectable 12VDC or 24VDC power-limited output.
•  1.75A continuous supply current @ 12VDC or 24VDC.
•  Filtered and electronically regulated output.
•  Outputs are overload protected by PTCs.
•  Delay timing is reset (before, during, or after a delay) by 
  dry contact closure (RES & G).
•  An output is provided for unlocking devices (electric strikes).
•  An auxiliary output is provided which is not affected by the 
  Fire Alarm Relay Terminals
  (1.25A @ 12VDC/24VDC for UL Installations).

Supervision:

•  AC Fail relay (Form “C” 1A @ 28VDC) indicates 
  AC is powering unit.
•  Output relay (Form “C” 1A @ 28VDC) indicates the [DC Lock+]
  terminal is powered and not the [] terminal, or vice versa.

LED Indicators:

•  A green LED also indicates the AC is powering unit.
•  A red LED indicates the DC outputs are powered.

Delayed Egress:

•  Field selectable: Delayed egress, Access-controlled egress or 
  No delays (a standard power supply).
•  Delay for delayed egress applications is 15 or 30 sec 
  field selectable.
•  Delayed egress has field selectable none or 1 sec nuisance delay.
•  Delayed egress has alarm relay to switch on alarm power.
•  Delay for access-controlled applications is 30 or 45 sec 
  field selectable.
•  Delays are triggered by a dry contact closure (TR & G).
•  Delay timing is reset (before, during, or after a delay) by 
  removal a dry contact closure (RES & G).

Enclosure Dimensions 

(H x W x D)

  8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).

Door Controls International

PS17-TD2

Access Control Power Supply/Charger

Содержание PS17-TD2

Страница 1: ...etic lock to unlock the door Requirements For Fire Exit and Panic Applications Equipment and systems designed as fire exit or panic hardware shall comply with the Standard for Panic Hardware UL 305 Interruption of power shall cause the locking mechanism to unlock release in less than 2 seconds Do not use battery backup Activation of a fire alarm signal or fire sprinkler signal shall release the do...

Страница 2: ...Fail supervisory outputs marked NC C and NO C is closed to NC when AC power is connected C is closed to NO when AC power is off 7 When a delay is to be used install a NO Momentary Reset switch across terminals marked RESET GND 8 When a delay is to be used install a NO Momentary Triggering Switch across terminals marked TRIG INPUT GND 9 For monitoring the output relay governing terminals marked Loc...

Страница 3: ...when TRG1 and TRG2 are shorted together and are typically used to power electromagnetic locks Two locks may be connected in parallel on LOCK and COM fig 2 pg 4 STRIKE This terminal provides DC output voltage when TRG1 and TRG2 are unshorted and are typically used to power Electric Strikes NC NO C adjoining TRG1 TRG2 Isolated dry Form C contacts Shortening TRG1 and TRG2 together causes these contac...

Страница 4: ...MODE 4 SWITCH SELECTS SHORT DELAY OF 15 SECS OR LONG DELAY OF 30 SECS AND 2 SWITCH SELECTS NONE OR A 1 SEC NUISANCE DELAY 3 OFF ACCESS CONTROLLED EGRESS IN THIS MODE 4 SWITCH SELECTS SHORT RELOCK DELAY OF 30 SEC OR LONG RELOCK DELAY OF 45 SECS 2 SWITCH IS DISABLED TR GND RES GND TRG1 TRG2 C NC NO ALARM NO C NC C NO NC AC FAIL 1 2 3 4 AC SW5 ON 24V OFF 12V SW5 ON VR1 DC BAT AC AC AUX FACP LOCK STRI...

Страница 5: ...CK TO OPTIONAL LED THESE ARE CODE SPECIFIC TERMS ONE OR MORE OF THESE RELAYS REQUIRED UNDER EVERY U S MODEL BUILDING CODE TO REMOTE ANNUNCIATOR NEMA 1 ENCLOSURE 24V SHOWN MONITOR AS DESIRED MONITOR AS DESIRED 4 OFF LONG DELAY 4 ON SHORT DELAY 3 OFF ACCESS CONTROLLED EGRESS 3 ON DELAYED EGRESS 2 OFF NUISANCE DELAY 2 ON NO NUISANCE DELAY TR GND RES GND TRG1 TRG2 C NC NO ALARM NO C NC C NO NC AC FAIL...

Страница 6: ...VDC 2 Dip SW4 OFF 45 sec relock ON 30sec relock 3 Dip SW3 ON Delayed Egress 4 Dip SW2 Any has no effect 5 Jumper RES to G FOR VOLATILE MEMORY IF REQUIRED TRANSFORMER FIRE PROTECTIVE SIGNALING SYSTEM FIRE ALARM SYSTEM FIRE COMMAND CENTER AUTOMATIC SPRINKLER SYSTEM AUTOMATIC SMOKE DETECTION SYSTEM AND OR AUTOMATIC FIRE DETECTION SYSTEM RELAYS 24V SHOWN TR GND RES GND TRG1 TRG2 C NC NO ALARM NO C NC ...

Страница 7: ...ed output Fig 6 Typical mag lock with fire alarm tie in using aux output installation PS17 TD2 1 PS17 TD2 2 Application Diagrams when used as a typical power supply not using delay features FACP MAG LOCK DOOR STRIKE PROX CARD READER ACCESS CONTROL DEVICE LOCK STRIKE TRG2 TRG1 AUX AUX COM FACP MAG LOCK ACCESS CONTROL DEVICE AUX FACP AUX FACP MAG LOCK MAG LOCK ACCESS CONTROL DEVICE LOCK STRIKE TRG2 ...

Страница 8: ... 6mm 1 125 28 6mm 6 05 153 7mm 0 6 15 2mm 0 6 15 2mm 1 25 31 8mm 1 25 4mm 6 05 153 7mm 0 6 15 2mm 1 25 4mm 0 6 15 2mm 1 25 4mm 1 25 4mm 5 25 133 4mm 3 5 88 9mm 1 25 4mm 2 50 8mm 2 50 8mm 8 125 206 4mm 1 25 31 8mm Door Controls International 2362 Bishop Circle East Dexter MI 48130 Tel 800 742 3634 Fax 800 742 0410 www doorcontrols com IIPS17 TD2 Rev 032420 ...

Отзывы: