background image

 

PS17-TD2 

- 5 - 

TRANSFORMER

FIRE - PROTECTIVE SIGNALING SYSTEM ,

FIRE ALARM SYSTEM ,

FIRE COMMAND CENTER ,

AUTOMATIC SPRINKLER SYSTEM ,

AUTOMATIC SMOKE - DETECTION SYSTEM, AND/OR

AUTOMATIC FIRE - DETECTION SYSTEM RELAYS

ELECTRIC

LOCK(S)

115 VAC IN

ALARM SOUNDS UNTIL RESET

FOR ALARM TO CEASE

WITH DOOR RELEASE

MOVE JUMPER ON AUX + TO LOCK +

TO

OPTIONAL

LED

THESE ARE CODE - SPECIFIC TERMS.
ONE OR MORE OF THESE RELAYS REQUIRED
UNDER EVERY U. S. MODEL BUILDING CODE.

TO REMOTE

ANNUNCIATOR

NEMA - 1 ENCLOSURE

24V SHOWN

MONITOR

AS DESIRED

MONITOR

AS DESIRED

4 OFF  LONG DELAY 

4 ON 

SHORT DELAY

3 OFF  ACCESS - CONTROLLED EGRESS 

3 ON 

DELAYED EGRESS

2 OFF  NUISANCE DELAY 

2 ON 

NO NUISANCE DELAY

 TR 
GND 

RES 
GND 

TRG1 

TRG2 


NC 
NO

ALARM  NO  C  NC  C  NO  NC  AC FAIL

  1  2  3  4

AC

    

ON

DC

+    BAT  ---            AC          AC

AUX  ---

FACP

LOCK  + STRIKE  +

AUX  +

COM  --

SW5 ON - 24V

OFF -  12V

ON

Typical Delayed Egress System:

Fig. 3

Содержание PS17-TD2

Страница 1: ...etic lock to unlock the door Requirements For Fire Exit and Panic Applications Equipment and systems designed as fire exit or panic hardware shall comply with the Standard for Panic Hardware UL 305 Interruption of power shall cause the locking mechanism to unlock release in less than 2 seconds Do not use battery backup Activation of a fire alarm signal or fire sprinkler signal shall release the do...

Страница 2: ...Fail supervisory outputs marked NC C and NO C is closed to NC when AC power is connected C is closed to NO when AC power is off 7 When a delay is to be used install a NO Momentary Reset switch across terminals marked RESET GND 8 When a delay is to be used install a NO Momentary Triggering Switch across terminals marked TRIG INPUT GND 9 For monitoring the output relay governing terminals marked Loc...

Страница 3: ...when TRG1 and TRG2 are shorted together and are typically used to power electromagnetic locks Two locks may be connected in parallel on LOCK and COM fig 2 pg 4 STRIKE This terminal provides DC output voltage when TRG1 and TRG2 are unshorted and are typically used to power Electric Strikes NC NO C adjoining TRG1 TRG2 Isolated dry Form C contacts Shortening TRG1 and TRG2 together causes these contac...

Страница 4: ...MODE 4 SWITCH SELECTS SHORT DELAY OF 15 SECS OR LONG DELAY OF 30 SECS AND 2 SWITCH SELECTS NONE OR A 1 SEC NUISANCE DELAY 3 OFF ACCESS CONTROLLED EGRESS IN THIS MODE 4 SWITCH SELECTS SHORT RELOCK DELAY OF 30 SEC OR LONG RELOCK DELAY OF 45 SECS 2 SWITCH IS DISABLED TR GND RES GND TRG1 TRG2 C NC NO ALARM NO C NC C NO NC AC FAIL 1 2 3 4 AC SW5 ON 24V OFF 12V SW5 ON VR1 DC BAT AC AC AUX FACP LOCK STRI...

Страница 5: ...CK TO OPTIONAL LED THESE ARE CODE SPECIFIC TERMS ONE OR MORE OF THESE RELAYS REQUIRED UNDER EVERY U S MODEL BUILDING CODE TO REMOTE ANNUNCIATOR NEMA 1 ENCLOSURE 24V SHOWN MONITOR AS DESIRED MONITOR AS DESIRED 4 OFF LONG DELAY 4 ON SHORT DELAY 3 OFF ACCESS CONTROLLED EGRESS 3 ON DELAYED EGRESS 2 OFF NUISANCE DELAY 2 ON NO NUISANCE DELAY TR GND RES GND TRG1 TRG2 C NC NO ALARM NO C NC C NO NC AC FAIL...

Страница 6: ...VDC 2 Dip SW4 OFF 45 sec relock ON 30sec relock 3 Dip SW3 ON Delayed Egress 4 Dip SW2 Any has no effect 5 Jumper RES to G FOR VOLATILE MEMORY IF REQUIRED TRANSFORMER FIRE PROTECTIVE SIGNALING SYSTEM FIRE ALARM SYSTEM FIRE COMMAND CENTER AUTOMATIC SPRINKLER SYSTEM AUTOMATIC SMOKE DETECTION SYSTEM AND OR AUTOMATIC FIRE DETECTION SYSTEM RELAYS 24V SHOWN TR GND RES GND TRG1 TRG2 C NC NO ALARM NO C NC ...

Страница 7: ...ed output Fig 6 Typical mag lock with fire alarm tie in using aux output installation PS17 TD2 1 PS17 TD2 2 Application Diagrams when used as a typical power supply not using delay features FACP MAG LOCK DOOR STRIKE PROX CARD READER ACCESS CONTROL DEVICE LOCK STRIKE TRG2 TRG1 AUX AUX COM FACP MAG LOCK ACCESS CONTROL DEVICE AUX FACP AUX FACP MAG LOCK MAG LOCK ACCESS CONTROL DEVICE LOCK STRIKE TRG2 ...

Страница 8: ... 6mm 1 125 28 6mm 6 05 153 7mm 0 6 15 2mm 0 6 15 2mm 1 25 31 8mm 1 25 4mm 6 05 153 7mm 0 6 15 2mm 1 25 4mm 0 6 15 2mm 1 25 4mm 1 25 4mm 5 25 133 4mm 3 5 88 9mm 1 25 4mm 2 50 8mm 2 50 8mm 8 125 206 4mm 1 25 31 8mm Door Controls International 2362 Bishop Circle East Dexter MI 48130 Tel 800 742 3634 Fax 800 742 0410 www doorcontrols com IIPS17 TD2 Rev 032420 ...