Installations Instructions:

The unit should be installed in accordance with article 760 of The National Electrical Code and NFPA 72, as well as all applicable Local Codes.
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. 
 

Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the 

 

two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and 

 

install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and 

 

make sure to tighten all screws (Enclosure Dimensions, pg. 8). Secure enclosure to earth ground. 

2.  Connect 115VAC to the black and white flying leads of the transformer. Secure wire lead to earth ground. 
 

Green “AC” LED on power supply board will turn on. This light can be seen through the LED lens on the door of the enclosure.

3.  Turn the SW5 ON for 12VDC output, turn the SW5 OFF for 24VDC output. 
4.  Measure output voltage before connecting devices to ensure proper operation of equipment. 
 

This helps avoiding potential damage.

5.  Jumper TRGI and TRG2, unless continuity is provided through a fire alarm circuit.
6.  Connect appropriate signaling notification devices to AC Fail supervisory outputs marked [NC, C, and NO].
 

[C] is closed to [NC] when AC power is connected. [C] is closed to [NO] when AC power is off.

7.  When a delay is to be used, install a NO Momentary Reset switch across terminals marked [RESET - GND].
8.  When a delay is to be used install a NO Momentary Triggering Switch across terminals marked [TRIG INPUT - GND].
9.  For monitoring the output relay governing terminals marked [Lock + and ] use the [C, NC and NO] terminals next to 
 

[TRGI and TRG2]. [C] will be closed to [NC] when [Lock +] is powered.

10.  When a Delayed Egress is used, an alarm is required by all Codes. The alarm relay is used to switch on the alarm. 
 

[C] will close to [NC] when the alarm should sound: immediately at triggering with no nuisance delay, or after one continuous 

 

second of trigger with nuisance delay. If moderate power is required for the alarm, it can be obtained by jumping [AUX+] to [C] 

 

on the Alarm relay; and [NC] on the Alarm relay and [AUX –] to the alarm.

11.  See diagrams on following pages for wiring suggestions.

+    BAT  ---                  AC          AC

AUX ---

XFMR

Black Lead

One Punchout

for AC Entry Only.

All other wires

may be grouped

in other punchouts.

White Lead 

Green Lead 

 Input

115VAC 60Hz,

0.6A

Stand-by

Battery

To Electric

Locks and

Request to

Exit Switches

Auxiliary Output

FACP

LOCK  + STRIKE  +

AUX  +

COM---

AC

DC

 TR       G            RES   GND                    TRG1  TRG2    C      NC      NO

NO      C       NC      C      NO     NC AC FAIL

ALARM

ALARM
(FOR DELAYED
EGRESS ONLY)

AC FAIL
MONITOR IF DESIRED

SW5

OFF - 12V

ON - 24V

*4 OFF  LONG DELAY 

ON  SHORT DELAY

*3 OFF  ACCESS - CONTROLLED EGRESS 

ON  DELAYED EGRESS

*2 OFF  NUISANCE DELAY 

ON  NO NUISANCE DELAY

ON

OFF

  1  2  3  4

ON

Fig. 1

Содержание PS17-TD2

Страница 1: ...etic lock to unlock the door Requirements For Fire Exit and Panic Applications Equipment and systems designed as fire exit or panic hardware shall comply with the Standard for Panic Hardware UL 305 Interruption of power shall cause the locking mechanism to unlock release in less than 2 seconds Do not use battery backup Activation of a fire alarm signal or fire sprinkler signal shall release the do...

Страница 2: ...Fail supervisory outputs marked NC C and NO C is closed to NC when AC power is connected C is closed to NO when AC power is off 7 When a delay is to be used install a NO Momentary Reset switch across terminals marked RESET GND 8 When a delay is to be used install a NO Momentary Triggering Switch across terminals marked TRIG INPUT GND 9 For monitoring the output relay governing terminals marked Loc...

Страница 3: ...when TRG1 and TRG2 are shorted together and are typically used to power electromagnetic locks Two locks may be connected in parallel on LOCK and COM fig 2 pg 4 STRIKE This terminal provides DC output voltage when TRG1 and TRG2 are unshorted and are typically used to power Electric Strikes NC NO C adjoining TRG1 TRG2 Isolated dry Form C contacts Shortening TRG1 and TRG2 together causes these contac...

Страница 4: ...MODE 4 SWITCH SELECTS SHORT DELAY OF 15 SECS OR LONG DELAY OF 30 SECS AND 2 SWITCH SELECTS NONE OR A 1 SEC NUISANCE DELAY 3 OFF ACCESS CONTROLLED EGRESS IN THIS MODE 4 SWITCH SELECTS SHORT RELOCK DELAY OF 30 SEC OR LONG RELOCK DELAY OF 45 SECS 2 SWITCH IS DISABLED TR GND RES GND TRG1 TRG2 C NC NO ALARM NO C NC C NO NC AC FAIL 1 2 3 4 AC SW5 ON 24V OFF 12V SW5 ON VR1 DC BAT AC AC AUX FACP LOCK STRI...

Страница 5: ...CK TO OPTIONAL LED THESE ARE CODE SPECIFIC TERMS ONE OR MORE OF THESE RELAYS REQUIRED UNDER EVERY U S MODEL BUILDING CODE TO REMOTE ANNUNCIATOR NEMA 1 ENCLOSURE 24V SHOWN MONITOR AS DESIRED MONITOR AS DESIRED 4 OFF LONG DELAY 4 ON SHORT DELAY 3 OFF ACCESS CONTROLLED EGRESS 3 ON DELAYED EGRESS 2 OFF NUISANCE DELAY 2 ON NO NUISANCE DELAY TR GND RES GND TRG1 TRG2 C NC NO ALARM NO C NC C NO NC AC FAIL...

Страница 6: ...VDC 2 Dip SW4 OFF 45 sec relock ON 30sec relock 3 Dip SW3 ON Delayed Egress 4 Dip SW2 Any has no effect 5 Jumper RES to G FOR VOLATILE MEMORY IF REQUIRED TRANSFORMER FIRE PROTECTIVE SIGNALING SYSTEM FIRE ALARM SYSTEM FIRE COMMAND CENTER AUTOMATIC SPRINKLER SYSTEM AUTOMATIC SMOKE DETECTION SYSTEM AND OR AUTOMATIC FIRE DETECTION SYSTEM RELAYS 24V SHOWN TR GND RES GND TRG1 TRG2 C NC NO ALARM NO C NC ...

Страница 7: ...ed output Fig 6 Typical mag lock with fire alarm tie in using aux output installation PS17 TD2 1 PS17 TD2 2 Application Diagrams when used as a typical power supply not using delay features FACP MAG LOCK DOOR STRIKE PROX CARD READER ACCESS CONTROL DEVICE LOCK STRIKE TRG2 TRG1 AUX AUX COM FACP MAG LOCK ACCESS CONTROL DEVICE AUX FACP AUX FACP MAG LOCK MAG LOCK ACCESS CONTROL DEVICE LOCK STRIKE TRG2 ...

Страница 8: ... 6mm 1 125 28 6mm 6 05 153 7mm 0 6 15 2mm 0 6 15 2mm 1 25 31 8mm 1 25 4mm 6 05 153 7mm 0 6 15 2mm 1 25 4mm 0 6 15 2mm 1 25 4mm 1 25 4mm 5 25 133 4mm 3 5 88 9mm 1 25 4mm 2 50 8mm 2 50 8mm 8 125 206 4mm 1 25 31 8mm Door Controls International 2362 Bishop Circle East Dexter MI 48130 Tel 800 742 3634 Fax 800 742 0410 www doorcontrols com IIPS17 TD2 Rev 032420 ...