Installation, Operation and Maintenance manual
11
WSO Flex
Installation and assembly
a. Ceiling mounting
When ceiling mounting the WSO Flex mist collector, you must first calculate the
total mist collector weight including material being collected, ductwork and any
auxiliary equipment that is attached to the unit.
Option 1
1. Remove the lifting eyebolts.
2. Use four threaded M10/M12* rods (quality 12.9) for hanging the unit. Thread an
M10/M12 (DIN 934) nut onto the threads of each rod for at least 25 mm.
3. Apply MS polymer sealant around the existing mounting holes on the top of the
unit.
4. Place an M10/M12 lock washer and an M10/M12 flat washer on each rod before
threading the rod into the mounting holes.
5. Thread the rods into the holes and tighten nuts.
6. Use the connection at the ceiling, not at the mist collector, to level the unit in
all directions.
* WSO Flex MMA = M10
WSO Flex MMB = M12
300 mm clearance required above mist collector for exhaust air.
Level the unit before tightening any hardware.