19

Donaldson Company, Inc.

Split Taper™ Bushing Mounting Instructions

Many fans are furnished with split taper bushings for 

mounting the impeller to the shaft. When properly 

assembled, the bushings grip the hub with a positive 

clamping action.
1.  Bushel barrel and bore of impeller are tapered to 

ensure concentric mounting and a true running 

propeller.

2.  Capscrews, when tightened, lock bushing in 

propeller. Use special plated capscrews and nylock 

nuts.

Bushing No.

Bolt Size

Torque Ft-Lbs

QT/QH/L/H

1/4-20

7-1/2

3.  Bushing is split so that when the locking capscrews 

force bushing into tapered bore, the bushing grips 

the shaft with a positive clamping fit. This will 

withstand vibration and heavy loads without being 

loosened.

4.  Impeller and bushing assembly is keyed to the shaft 

and held in place by compression, which adds 

driving strength. 

Before assembly, ensure shaft 

and keyway are clean and 

smooth. Check key size with both shaft and 

bushing keyway.

5.  To assemble, insert the capscrews through the 

clearance holes in the bushing and install bushing 

loosely into the impeller. Do not press or drive. Start 

capscrews by hand, turning them just enough to 

engage threads in the nylock nut.  Do not use a 

wrench at this time. The bushing should be loose 

enough in the propeller to move freely. Slide impeller 

and bushing assembly onto shaft, allowing adequate 

clearance for shaft end play to prevent friction. Fit 

key into keyway. Do not force impeller and bushing 

onto shaft. If it does not go on easily, check shaft, 

bushing, and key sizes once again.

 

Tighten capscrews gradually and evenly with wrench 

similar to mounting an automobile wheel. Rotate a 

quarter turn on each capscrew successively until 

 

all capscrews are tight.  These capscrews force the 

taper bushing into the hub, which in turn compresses 

the bushing onto the shaft. This makes a positive 

clamping fit. The torque must not exceed the value 

specified in the table. 

Do not attempt to pull bushing 

flange flush with hub end. 

There should be a clearance which varies 

approximately 3/16-in to 1/4-in with the bushing 

size when tightened. This is not a locating 

dimension.

Impeller Assembly Removal 

1.  Remove all capscrews from impeller and hub 

assembly.

2.  Insert capscrews into the threaded holes in the 

bushing flange.

3.  Tighten each bolt in quarter of a turn increments to 

push the impeller off the bushing.  This forces the 

bushing loose from the propeller hub and releases 

the compression so that the entire assembly will 

slide from the shaft.

4.  Pull the bushing off the shaft.  

If the assembly has been in place 

sometime it may be necessary 

to use a wheel puller to remove the bushing. 

Never use a wheel puller on the impeller.

Split Taper

Bushing

C

A

E

D B

A.  External key, except G, H and Idler Bushings

B.  Bushing barrel and Product bore are tapered

C.  Bushing cap screws

D.  Bushing barrel is split (except idler bushings)

E.  Removal holes are threaded, installation holes are not

Hub of blower wheel

or pulley

Spilt Taper Bushing Installation

Browning

®

 is a registered trademark and Split Taper™ is a trademark of Emerson Power Transmission Manufacturing, L.P.

Содержание Downflo Oval DFO 1-1

Страница 1: ...ngs in this manual DO NOT operate or perform maintenance on this collector until you have read and understood the instruction and warnings contained within this manual Downflo Oval DFO 1 1 2 2 and 3 3...

Страница 2: ...ipment This manual has been supplied to assist with the installation operation and maintenance for the collector purchased Please read the manual before installing operating or performing maintenance...

Страница 3: ...Wiring 9 Control Panel and Motor Wiring 10 Control Panels and Solenoid Specifications 13 10 Gallon Pail Pack 14 25 Gallon Dust Bin 14 Exhaust Damper 14 Preliminary Start Up Check 15 Maintenance Infor...

Страница 4: ...r control Donaldson does not provide engineering consulting services related to process or dust hazard analyses or code and standard compliance Complying with applicable codes and standards and managi...

Страница 5: ...ifications Hygroscopic dust such as fertilizer salt and sugar should be handled under a controlled low humidity environment Flammable or explosive dust may require customized collector design options...

Страница 6: ...es through the clean air outlet Filter cleaning is completed using pulse jet technology An air diaphragm valve aligned to each filter provides the pulse cleaning Either a manual push button valve or e...

Страница 7: ...collector will compromise collector performance Inspect collector to ensure all hardware is properly installed and tight prior to operating collector Installation Use proper equipment and adopt all s...

Страница 8: ...or and accessories separately and assemble after collector is in place Hoisting Information Failure to lift the collector correctly can result in severe personal injury and or property damage Use appr...

Страница 9: ...Downflo Oval DFO 1 1 to 3 3 6 Typical Installation Typical Installation...

Страница 10: ...models It is prewired to the motor and filter cleaning is completed using a separate manual push button valve located next to the motor starter Downtime Cleaning Option Primarily used for intermittent...

Страница 11: ...plate and shims grout Embedment depth suitable for the physical properties of the foundation Collector Anchoring Anchors must comply with local code requirements and must be capable of supporting dead...

Страница 12: ...erforming service or maintenance work Do not install in classified hazardous atmospheres without an enclosure rated for the application Electrical Wiring All electrical wiring and connections includin...

Страница 13: ...valve regulator compressed air supply bleed type air filter automatic condensate valve power supply disconnect switch motor starter customer supplied Turn power off and lock out electrical power sour...

Страница 14: ...cable Downtime Cleaning without Motor Starter G ground lug TR1 L N N N FU1 PS1 N L G 120 Volt AC Delta P Cleaning with Motor Starter L3 L2 L1 1L3 1L2 1L1 ground lug PE PE 1L1 1L2 3 Phase OL M1 fused...

Страница 15: ...elay outputs located inside the control panel Delta P Cleaning Wire 120 Volt AC power directly to the control panel two point terminal block located on the 3 pin timer subpanel Solenoid Connection Wir...

Страница 16: ...y set at 200 milliseconds Pulse OFF Time Factory set at 10 seconds The pulse OFF time can only be adjusted by modifying the parameters contained in the microprocessor software Contact your representat...

Страница 17: ...bin and clamp down with draw latches Exhaust Damper Adjustment 10 Gallon Pail Pack hopper flexible hose hose clamp 10 gallon pail pail cover hex bolt flat washer hex nut sealant cover clamp adapter c...

Страница 18: ...ads on the motor junction box Do not look into fan outlet to determine rotation View the fan rotation through the back of the motor Check that the exhaust plenum is free of tools or debris before chec...

Страница 19: ...Maintenance Information Operational Checklist 1 Monitor the physical condition of the collector and repair or replace any damaged components Routine inspections will minimize downtime and maintain op...

Страница 20: ...yoke Note Insert the filter gasket end first 2 Wipe cover gaskets clean and replace covers by attaching cover to yoke hook and firmly latching cover handle Replace access covers carefully by securing...

Страница 21: ...Downflo Oval DFO 1 1 to 3 3 18 Filter Access Cover Removal Side View access cover yoke latched unlatched removal access cover cover handle filter cartridge yoke Filter Removal and Installation...

Страница 22: ...ing onto shaft If it does not go on easily check shaft bushing and key sizes once again Tighten capscrews gradually and evenly with wrench similar to mounting an automobile wheel Rotate a quarter turn...

Страница 23: ...gallon dust container is secured to the adapter collar with a band clamp similar to the standard 10 gallon dust container 1 Apply sealant to the adapter collar mounting flange toward the inside edge...

Страница 24: ...o seal the dust container To install on an existing collector 1 Remove the cover and clamp from the dust container 2 Remove the dust container and set aside 3 Remove the flexible duct and adapter coll...

Страница 25: ...reating a pressure drop The Delta P Controller measures the pressure drop and provides a visual display in inches water gauge or metric SI units of daPa Filter Cleaning When the pressure drop across t...

Страница 26: ...1 Lift collector approximately 24 in with a crane or forklift 2 Position the swivel caster assembly under the front filter access end of the collector Align bolt holes and secure using the 3 8 16 x 5...

Страница 27: ...in the roof panel using a 0 266 in diameter drill bit 5 Apply 1 4 in diameter rope type sealant toward the inside of bolt pattern 6 Position the HEPA mounting frame on the top panel aligning the bolt...

Страница 28: ...he mounting adapter on the roof panel aligning the bolt holes from the bolts removed in Step 1 with the bolt pattern on the mounting adapter Note The bolt pattern of the mounting adapter is not symmet...

Страница 29: ...4 in flat washer 1 4 in lock washer 1 4 20 hex nut mounting adapter inlet flange Extraction Arm Ex Arm Installation Extraction Arm Installation Lift the Ex Arm into position over the mounting adapter...

Страница 30: ...ng of an explosion must be safely directed outdoors away from areas occupied by personnel to reduce risk of personal injury and or property damage The risk of personal injury and or property damage ca...

Страница 31: ...perly Check airflow in duct Adjust damper control until proper airflow is achieved and the blower motor s amp draw is within the manufacturer s rated amps Electrical circuit overload Check that the po...

Страница 32: ...wiring diagram inside the control panel Replace if necessary Display on Delta P Controller does not read zero when at rest Out of calibration Recalibrate as described in Delta P Maintenance Manual Wit...

Страница 33: ...wiring Check wiring between the Delta P Control and the timer board and between the timer board and solenoid valve coils Defective solenoids Check all solenoid coils for proper operation Timer board n...

Страница 34: ...__________________________________________________________ Dust Properties Kst_______________Pmax______________MIE____________MEC_________________ Accessories__________________________________________...

Страница 35: ...foregoing warranty on services Products manufactured by a third party Third Party Product may constitute contain be contained in incorporated into attached to or packaged together with the goods Buye...

Страница 36: ...Many factors beyond the control of Donaldson can affect the use and performance of Donaldson products in a particular application including the conditions under which the product is used Since these...

Отзывы: