background image

Downflo Oval, DFO 2-4 and 3-6

 36

Problem

Probable Cause

Remedy

Insufficient airflow 
continued

Lack of compressed air

See Rating and Specification Information for 
compressed air supply requirements.

Pulse cleaning not energized

Use a voltmeter to check the solenoid valves in the 
control panel. Check pneumatic lines for kinks or 
obstructions.

Dust storage area overfilled or 
plugged

Clean out dust storage area.  See Dust Disposal.

Pulse valves leaking 
compressed air

Lock out all electrical power to the unit and bleed 
the compressed air supply. Check for debris, valve 
wear, pneumatic tubing fault, or diaphragm failure by 
removing the diaphragm cover on the pulse valves. 
Check for solenoid leaks or damage. If pulse valves 
or solenoid valves and tubing are damaged, replace.

Solid-State timer failure

Using a voltmeter, check supply voltage to the timer 
board. Check and replace the fuse on the timer 
board if necessary.  If the fuse is good and input 
power is present but output voltage to the solenoid 
is not, replace the timer board. See Solid-State Timer 
Installation.

Solid-State timer out of 
adjustment

See Solid-State Timer and Solid-State Timer Wiring 
Diagram.

No display on the Delta P 
Controller

No power to the controller

Use a voltmeter to check for supply voltage.

Fuse blown

Check the fuse in the control panel. See wiring 
diagram inside the control panel. Replace if 
necessary.

Display on Delta P 
Controller does not read 
zero when at rest

Out of calibration

Recalibrate as described in Delta P Maintenance 
Manual.

With collector discharging 
outside, differential pressure is 
present from indoor to outdoor

Recalibrate with the pressure tubing attached as 
described in the Delta P Maintenance Manual.

Delta P Controller ON, 
but cleaning system does 
not start

Pressure tubing disconnected, 
ruptured, or plugged

Check tubing for kinks, breaks, contamination, or 
loose connections.

Not wired to the timing board 
correctly

Connect the pressure switch on the timer board to 
Terminals 7 and 8 on TB3.

Faulty relay

Using a multimeter, test relay for proper closure. 
Replace if necessary.

Содержание DFO 2-4

Страница 1: ...2...

Страница 2: ...bility or liability for the suitability of any fire and or explosion mitigation strategy or any items incorporated into a collector as part of an owner operators hazard mitigation strategy Improper op...

Страница 3: ......

Страница 4: ...rsatility of the unit standard options include top front and abrasion resistant inlets HEPA and ASHRAE afterfilter packs Checker board control panel and various dust removal options Purpose and Intend...

Страница 5: ......

Страница 6: ...ng system diaphragm valve compressed air supply hopper Filter Cleaning Operation dirty air inlet clean air outlet clean air outlet filter cartridges clean air plenum Normal Operation dirty air inlet o...

Страница 7: ...the unit will compromise unit performance Inspect unit to ensure all hardware is properly installed and tight prior to operating collector Installation Site suitability must account for wind seismic...

Страница 8: ...e capacity Allow only qualified crane operators to lift the equipment Refer to applicable OSHA regulations and local codes when using cranes forklifts and other lifting equipment Lift unit and accesso...

Страница 9: ...binet 2 Apply sealant to hopper flange 3 Fasten hopper to cabinet 4 Assemble legs and cross braces 5 Lift unit and hopper into position over legs and lower slowly 6 Fasten legs to unit securely 7 Lift...

Страница 10: ...hopper following these instructions 1 Stand the hopper on the discharge end 2 Apply 1 4 in diameter rope type sealant around the top flange toward the inside edge of the bolt pattern 3 Lift the colle...

Страница 11: ...abinet and hopper assembly into position over the legs and lower slowly 3 Use drift pins to align the holes in the collector with the holes in the legs Attach each leg as shown using the hardware supp...

Страница 12: ......

Страница 13: ...o manifold solenoid electrical connection manifold solenoid enclosure diaphragm valve hopper blower fan Magnehelic gauge 120 Volt blower motor starter solid state timer safety exhaust valve Notes 1 No...

Страница 14: ......

Страница 15: ......

Страница 16: ...upply Turn electrical power OFF at source and switch any two leads on the motor junction box Do not interchange a power lead with the ground wire Severe damage or personal injury may result 3 All acce...

Страница 17: ...Downflo Oval DFO 2 4 and 3 6 14 This Page Intentionally Left Blank...

Страница 18: ...lications Periodically check the compressed air components and replace compressed air filters Drain moisture following the manufacturer s instructions With the compressed air supply ON check the clean...

Страница 19: ......

Страница 20: ...pinching Check that access covers are seated and seal properly Gaskets must be compressed to ensure an airtight seal 3 Turn electrical power and compressed air supply ON before starting unit Dust Dis...

Страница 21: ...Downflo Oval DFO 2 4 and 3 6 18 This Page Intentionally Left Blank...

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ...a forklift or pallet jack If a pallet is used the length of flexible hose may need to be shortened 1 Place 1 4 in diameter rope type sealant between the hopper flange and the drum cover mounting flang...

Страница 26: ...cludes a 5 gallon pail and provides easy access for dust removal and storage 1 Apply sealant to the hopper flange or the pail cover mounting plate flange toward the inside edge of the bolt pattern 2 F...

Страница 27: ...in the clean air plenum 1 Choose a convenient accessible location on or near the unit for mounting that provides the best visual advantage 2 Plug the pressure ports on the back of the gauge using two...

Страница 28: ...in the right hand side of the mounting bracket Tighten screws 3 On the back of the gauge remove four 6 32 x 5 16 in screws and plastic enclosure Set aside Add two jumper wires supplied by customer Re...

Страница 29: ...n 1 8 in NPT male adapter NPT male adapter static pressure tee dirty air plenum pressure tap location 1 8 in NPT male adapter plastic tubing two 1 8 in NPT adapters low pressure port high pressure por...

Страница 30: ......

Страница 31: ...Drop Off and Alarm The first two High Pressure Drop On and Low Pressure Drop Off control the filter cleaning system The third Alarm provides a relay output to activate an external alarm supplied by o...

Страница 32: ...ling screws supplied 5 Loosen the wing nut on the damper and adjust from 30 to 50 closed Backward Inclined 1 Apply sealant around the inside edge of the bolt pattern on the power pack outlet 2 Fasten...

Страница 33: ...omponents as described in Power Pack Assembly on Page 12 6 Attach the plenum silencer to the base using self threading bolts with washers 7 Route rigid or flexible conduit from the junction box on the...

Страница 34: ...g align bolt holes and fasten securely in place using hardware supplied with the power pack 5 Assemble the remaining power pack components as described in Power Pack 6 Apply sealant to the inside peri...

Страница 35: ...sion Resistant Inlet Collar 1 Remove the unit s front cover plate Remove excess sealant from opening 2 Apply 1 4 in sealant around the opening toward the inside edge of the bolt pattern 3 Align the ho...

Страница 36: ...to deliver heat to the large pulse valves This kit is customer installed and detailed installation instructions are provided 1 Install the power connection kit on the heat cable following the manufac...

Страница 37: ......

Страница 38: ...operly Check airflow in duct Adjust damper control until proper airflow is achieved and the blower motor s amp draw is within the manufacturer s rated amps Electrical circuit overload Check that the p...

Страница 39: ...d input power is present but output voltage to the solenoid is not replace the timer board See Solid State Timer Installation Solid State timer out of adjustment See Solid State Timer and Solid State...

Страница 40: ...keys to not work Improper operation Press and hold one of the three setpoint keys to use arrow keys Programming keys disabled Remove the Program Disable jumper from Terminals 3 and 4 on TB2 Cleaning...

Страница 41: ...Downflo Oval DFO 2 4 and 3 6 38 Service Notes Date Service Performed Notes...

Страница 42: ...39 Donaldson Company Inc Service Notes Date Service Performed Notes...

Страница 43: ......

Страница 44: ...se The terms of this warranty may be modi ed only by a special warranty document signed by a Director General Manager or Vice President of Donaldson Failure to use genuine Donaldson replacement parts...

Отзывы: