Delta P Plus Control

 10

Problem

Probable Cause

Remedy

Delta P Plus arrow keys 
do not work

Improper operation

Press MENU and choose a parameter, then press 
SET prior to using the arrow keys.

Programming keys disabled

Remove the Program Disable jumper from Terminals 
3 and 4 on TB2.

Cleaning light is ON, 
but cleaning system not 
functioning

Improper wiring

Check wiring between the Delta P Plus Control and 
the timer board, and between the timer board and 
solenoid valve coils.

Defective solenoids

Check all solenoid coil for proper operation.

Timer board not powered

Check power ON light on timer board’s LED display. If 
not illuminated, check the supply voltage to the timer 
board. Check the fuse on the timer board. Replace if 
necessary.

Timer board defective

If LEd is iluminated, observe the output display. Install 
a temporary jumper across the pressure switch 
terminals. Output LED’s should flash in sequence. 
Check ouput using a multimeter set to 150 VAC range, 
measure from SOL COM to a solenoid output. The 
needle will deflect when LED flashes for that output 
if voltage is present. If LEDs do not flash, or if no 
voltage is present at output terminals during flash, 
replace the board.

Downtime cleaning 
too long or too short 
duration

Parameter setup

Reset the value in Parameter P10.

Pressure display changes 
value up and down 
rapidly

Parameter setup

Reset the value in parameter P12.

Содержание Delta P Plus

Страница 1: ...roperty of the owner Leave with the unit when set up and start up are complete Donaldson Company reserves the right to change design and specifications without prior notice Illustrations are for refer...

Страница 2: ...ach of these responsibilities are met As a manufacturer and supplier of Industrial Filtration Products Donaldson can assist process owners operators in the selection of filtration technologies However...

Страница 3: ..._______ Other_________________________________________________________________________________ DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNIN...

Страница 4: ...taining the differential pressure drop in a specified range then initiating a down time cleaning cycle when the differential pressure drop approaches zero The downtime cleaning function can be toggled...

Страница 5: ...al and local codes Turn power off and lock out electrical power sources before performing service or maintenance work Do not install in classified hazardous atmospheres without an enclosure rated for...

Страница 6: ...e differential pressure drop value used to start the pulse cleaning cycle 4 0 w g is a typical initial value 3 Press the MENU key three times AL appears Press the set key and the current value appears...

Страница 7: ...e set as the High Set Point Hi before the downtime feature is enabled P 10 Downtime Cleaning Time 1 999 10 Minutes The amount of time the downtime cleaning will continue once the time set in P 9 expir...

Страница 8: ...th a short length of tubing 3 Use the Menu key to select PAS 4 Press SET then use the arrow keys to display 4 press SET again 5 Press the MENU key repeatedly until you reach P 14 6 Press SET then use...

Страница 9: ...Delta P Plus Control 6 high pressure port low pressure port clean air plenum dirty air plenum Delta P Plus Control Installation...

Страница 10: ...switch Closing the switch turns the alarm OFF Internal Alarm Disable J5 To disable the alarm internally remove the jumper on MODE Jumper Block J5 located on the lower right quadrant of the circuit boa...

Страница 11: ...R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14 Cleaning Alarm CP3 U3 C...

Страница 12: ...the pressure switch on the timer board to Terminals 7 and 8 on TB3 Faulty relay Using a multimeter test relay for proper closure Replace if necessary Pressure tubing disconnected ruptured or plugged...

Страница 13: ...mer board s LED display If not illuminated check the supply voltage to the timer board Check the fuse on the timer board Replace if necessary Timer board defective If LEd is iluminated observe the out...

Страница 14: ...reset 3 4 5 6 R26 R28 R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14...

Страница 15: ......

Страница 16: ...to corrosion abrasion normal wear and tear product modification or product misapplication Donaldson also makes no warranty whatsoever as to any goods manufactured or supplied by others including elec...

Отзывы: