5

Donaldson Company, Inc.

Delta P Plus Control Calibration

The only user calibration is the zero adjustment of the 
display. Due to slight changes in electronic components 
over time or pressure within the plant environment, the 
display may read something other than 0.0 while at rest. 
Use the following procedure to recalibrate the operating 
system. 
1.   Turn power to the Delta P Plus Control ON for a 

minimum of 30-minutes to stabilize the operating 
temperature.

2.   Disconnect the pressure tubing, either leaving it to 

atmosphere, or connecting the two barbed fittings 
together with a short length of tubing.

3.  Use the Menu key to select PAS.

4.   Press SET, then use the arrow keys to display “4”, 

press SET again.

5.   Press the MENU key repeatedly until you reach P 14.
6.   Press SET, then use the arrow keys to display “1”, 

press SET again.

7.   After 10 seconds with no further button action, the 

display will return to reading the pressure.

8.  Connect one section of tubing from the control 

enclosure’s high-pressure port to the pressure tap on 
the dirty-air plenum. Connect the remaining section 
of tubing from the control enclosure’s low-pressure 
port to the pressure tap on the clean-air plenum.

menu

increase 

setpoint

indicates closed 

alarm relay

3-digit display

indicates closed 

cleaning relay

downtime clean

decrease

setpoint

set

Delta P Plus Control Display Panel 

Содержание Delta P Plus

Страница 1: ...roperty of the owner Leave with the unit when set up and start up are complete Donaldson Company reserves the right to change design and specifications without prior notice Illustrations are for refer...

Страница 2: ...ach of these responsibilities are met As a manufacturer and supplier of Industrial Filtration Products Donaldson can assist process owners operators in the selection of filtration technologies However...

Страница 3: ..._______ Other_________________________________________________________________________________ DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNIN...

Страница 4: ...taining the differential pressure drop in a specified range then initiating a down time cleaning cycle when the differential pressure drop approaches zero The downtime cleaning function can be toggled...

Страница 5: ...al and local codes Turn power off and lock out electrical power sources before performing service or maintenance work Do not install in classified hazardous atmospheres without an enclosure rated for...

Страница 6: ...e differential pressure drop value used to start the pulse cleaning cycle 4 0 w g is a typical initial value 3 Press the MENU key three times AL appears Press the set key and the current value appears...

Страница 7: ...e set as the High Set Point Hi before the downtime feature is enabled P 10 Downtime Cleaning Time 1 999 10 Minutes The amount of time the downtime cleaning will continue once the time set in P 9 expir...

Страница 8: ...th a short length of tubing 3 Use the Menu key to select PAS 4 Press SET then use the arrow keys to display 4 press SET again 5 Press the MENU key repeatedly until you reach P 14 6 Press SET then use...

Страница 9: ...Delta P Plus Control 6 high pressure port low pressure port clean air plenum dirty air plenum Delta P Plus Control Installation...

Страница 10: ...switch Closing the switch turns the alarm OFF Internal Alarm Disable J5 To disable the alarm internally remove the jumper on MODE Jumper Block J5 located on the lower right quadrant of the circuit boa...

Страница 11: ...R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14 Cleaning Alarm CP3 U3 C...

Страница 12: ...the pressure switch on the timer board to Terminals 7 and 8 on TB3 Faulty relay Using a multimeter test relay for proper closure Replace if necessary Pressure tubing disconnected ruptured or plugged...

Страница 13: ...mer board s LED display If not illuminated check the supply voltage to the timer board Check the fuse on the timer board Replace if necessary Timer board defective If LEd is iluminated observe the out...

Страница 14: ...reset 3 4 5 6 R26 R28 R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14...

Страница 15: ......

Страница 16: ...to corrosion abrasion normal wear and tear product modification or product misapplication Donaldson also makes no warranty whatsoever as to any goods manufactured or supplied by others including elec...

Отзывы: