5.  Wire all remaining auxiliary connections at this time.  

See the Optional Settings and Connections section 
for a list of these options. 

6.  Thirty-five feet of plastic tubing is supplied with the 

control and must be cut in two sections. Connect 
one section of tubing from the control enclosure’s 
high-pressure port to the pressure tap on the dirty-
air plenum. Connect the remaining section of tubing 
from the control enclosure’s low-pressure port to 
the pressure tap on the clean-air plenum. Additional 
tubing can be ordered from your representative.

7.  Apply power to the control. Set the high- and low-

pressure setpoints to start and stop the cleaning 
cycle.  Set the alarm setpoint to activate the alarm 
display. See Control Calibration section.

Setpoint Adjustment

Quick Start Instructions

1.   Press the MENU key, Lo appears. Press the SET key 

and the current value appears in the display. Use the 
arrow keys 

p

 

to change this value. Press SET 

again, and the display will blink twice, indicating that 
the new set point has been accepted. 

 

The Lo setting selects the differential pressure drop 
value used to stop the pulse cleaning cycle, 2.0” w.g. 
is a typical initial value.

2.   Press the MENU key twice, Hi appears. Press the 

SET key and the current value appears in the display. 
Use the arrow keys 

p

 

q

 to change this value. Press 

SET again, and the display will blink twice, indicating 
that the new set point has been accepted. 

 

The Hi setting selects the differential pressure drop 
value used to start the pulse cleaning cycle, 4.0” w.g. 
is a typical initial value.

3.   Press the MENU key three times, AL appears. Press 

the set key and the current value appears in the 
display. Use the arrow keys 

p

 

q

 to change this 

value. Press SET again, and the display will blink 
twice, indicating that the new setpoint has been 
accepted. 

 

The AL setting selects the differential pressure drop 
value used to close the Alarm relay and turn on the 
Alarm pilot light on the display.

4.   Press the DOWNTIME CLEAN key, and the display 

will read either On or Off. Pressing the same key 
again will toggle the reading [On to Off or Off to On]. 
Press the SET key to lock in your choice. 

Adjustments

1.   Pressing the MENU key repeatedly scrolls through 

the following programming choices:

 

Lo — Low set point

 

Hi — High set point

 

AL — Alarm set point

 

rtn — Return to reading current conditions

 

PAS — Password (for access to secured functions)

3.  The SET key shows current value and locks in values 

after adjustments.

4.  The DOWNTIME Clean button toggles the function on 

and off when available.

5.   Not pressing any buttons for 10 seconds allows the 

control to return to monitoring the filter system. 

Password Protected Settings

To reach the password protected settings, press the 
MENU key 5 times, the display will show PAS. 
Press the SET key, use the up arrow key 

p

 to set the 

value to “4”, press set again. 
When the display blinks twice, press the MENU key 
repeatedly until you reach the parameter you wish to 
change. 
Once you have selected a parameter, use the arrow 
keys 

p

 

q

 to change the value within the setting range  

shown in the table. 
Press the SET key to lock in the value.

Содержание Delta P Plus

Страница 1: ...roperty of the owner Leave with the unit when set up and start up are complete Donaldson Company reserves the right to change design and specifications without prior notice Illustrations are for refer...

Страница 2: ...ach of these responsibilities are met As a manufacturer and supplier of Industrial Filtration Products Donaldson can assist process owners operators in the selection of filtration technologies However...

Страница 3: ..._______ Other_________________________________________________________________________________ DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNIN...

Страница 4: ...taining the differential pressure drop in a specified range then initiating a down time cleaning cycle when the differential pressure drop approaches zero The downtime cleaning function can be toggled...

Страница 5: ...al and local codes Turn power off and lock out electrical power sources before performing service or maintenance work Do not install in classified hazardous atmospheres without an enclosure rated for...

Страница 6: ...e differential pressure drop value used to start the pulse cleaning cycle 4 0 w g is a typical initial value 3 Press the MENU key three times AL appears Press the set key and the current value appears...

Страница 7: ...e set as the High Set Point Hi before the downtime feature is enabled P 10 Downtime Cleaning Time 1 999 10 Minutes The amount of time the downtime cleaning will continue once the time set in P 9 expir...

Страница 8: ...th a short length of tubing 3 Use the Menu key to select PAS 4 Press SET then use the arrow keys to display 4 press SET again 5 Press the MENU key repeatedly until you reach P 14 6 Press SET then use...

Страница 9: ...Delta P Plus Control 6 high pressure port low pressure port clean air plenum dirty air plenum Delta P Plus Control Installation...

Страница 10: ...switch Closing the switch turns the alarm OFF Internal Alarm Disable J5 To disable the alarm internally remove the jumper on MODE Jumper Block J5 located on the lower right quadrant of the circuit boa...

Страница 11: ...R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14 Cleaning Alarm CP3 U3 C...

Страница 12: ...the pressure switch on the timer board to Terminals 7 and 8 on TB3 Faulty relay Using a multimeter test relay for proper closure Replace if necessary Pressure tubing disconnected ruptured or plugged...

Страница 13: ...mer board s LED display If not illuminated check the supply voltage to the timer board Check the fuse on the timer board Replace if necessary Timer board defective If LEd is iluminated observe the out...

Страница 14: ...reset 3 4 5 6 R26 R28 R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14...

Страница 15: ......

Страница 16: ...to corrosion abrasion normal wear and tear product modification or product misapplication Donaldson also makes no warranty whatsoever as to any goods manufactured or supplied by others including elec...

Отзывы: