background image

KRA Refrigeration System Installation, Operation & Maintenance Manual

 

L-3571 ENGLISH

5

C

ONDENSING

 U

NIT

All units have an R-404A compressor, air-and-water-cooled or water-cooled only titanium condenser, a receiver/dryer, and a 
sight glass. 

The KRA condensing unit comes in an enclosed, painted aluminum box. It is available with a 1/3 HP or 1/2 HP compressor. 
There are no service valves. The unit includes low-loss quick-connect couplings, a moisture indicating sight glass, a receiver 
and filter/dryer and a sufficient charge of R-404A for almost all applications. Condenser cooling is either air-and-water-cooled 
(slanted-top models) or water-cooled only (flat-top model). 

Air cooling is beneficial because the unit can operate even with the boat out of water. 

However, the unit suffers a 

drop in performance in ambient temperatures above 100°F/38°C where the unit is located, and the compressor 
may be damaged.

Water-cooled units are not affected by ambient temperature and do not need ventilation. Water flow should be a 
minimum of 1.5 GPM for the KRA 433X, and 2.0 GPM for the KRA 450X.

The combination air-and-water-cooled units provide the best of both applications.

E

VAPORATOR

The evaporator will be either stainless steel plate(s), or a wrapped box in which the evaporative tubing is located against the 
outside surface of the box. See Figure 2: Various Flat-Plate Evaporators, page 16 and Figure 3: Wrapped-Box Evaporator, 
page 16.

Stainless plates should be designed to cover about 30% to 40% of the box’s interior surface area for good freezer performance. 
For instance, a box that is 36" long, 16" deep and 20" wide (92 cm x 41 cm x 51 cm), should use plates that are about 36" x 16" 
(92 cm x 41 cm). This calculates to about 35% of the box’s interior surface area. Less plate area is needed for a box that is to be 
only a refrigerator.

Box design is extremely important and requires considerations that are mostly outside the scope of this manual. For the power 
boat industry, where constant power is available, evaporators must have a minimum of 2" (5 cm) of insulation (R7 per inch) for a 
freezer. When power availability is not constant, 4" (10 cm) of R7 insulation is required. It is best to use as much insulation as is 
practical. Call the Dometic Applications Department for advice on larger sized boxes, or if you are unsure.

S

UCTION

 L

INE

The suction line returns refrigerant gas from the evaporator to the condenser and should be fully insulated.

L

IQUID

 L

INE

The liquid line is the bare, 1/4" (7 mm) copper line. You must install the filter dryer assembly (packaged with the unit) at the KRA 
unit on the liquid line female quick-connect fitting or the warranty will be voided.

R

EFRIGERANT

 M

ETERING

 D

EVICE

Refrigerant metering is handled by a thermostatic expansion valve (TXV) that is externally equalized. This is used to 
compensate for varying installations. The TXV regulates the refrigerant flow into the evaporator depending on load. The valve is 
either set at the factory or at installation, and does not require further adjusting. A valve which has been severely misadjusted 
can damage the condensing unit, and will void warranty. 

The metering valve must be insulated airtight! 

The TXV has a sensing bulb that must be firmly attached and thoroughly 

insulated to the suction line leaving the box. Bulb placement is important. Place at 3:00 to 9:00 o’clock on the side of the suction 
line.

The TXV controls the flow rate of liquid refrigerant entering the evaporator in response to the superheat of the refrigerant gas 
leaving the evaporator. It keeps the entire evaporator active, without permitting unevaporated refrigerant liquid to be returned 
through the suction line to the compressor. The function on the TXV is to feed liquid into the evaporator coils at a rate that will 
keep liquid evaporating in all the coils, and to control that feed so that only vapor will reach the outlet (return line to the 
compressor).

T

HERMOSTAT

A thermostat controls the operation of the condensing unit, based on box temperature. An easy-to-use digital Dometic 
thermostat control is required for the installation, and digital input must be enabled (see “Parameter Programming” on page 11). 
No controls other than the Dometic digital control should be used; other controls are not supported.

WARNING

Do not drill through the inside of a wrapped box evaporator. If the refrigerant tubing is punctured by doing so, it will 
not be covered under warranty.

Содержание KRA 433X 1161

Страница 1: ...ery precaution has been taken in the preparation of this manual to ensure its accuracy However Dometic assumes no responsibility for errors and omission Neither is any liability assumed for damages re...

Страница 2: ...Condensing Unit 10 THERMOSTAT OPERATION 10 Operating the Dometic Control 10 Parameter Programming 11 Modbus Addresses for Dometic STIIC Interface 12 SERVICING YOUR REFRIGERATION SYSTEM 12 REFRIGERANT...

Страница 3: ...s NEC in the U S CEC in Canada 3 Open the electrical disconnect switch es before electrically connecting the unit 4 Before operating the unit be certain it is properly grounded 5 The units contain ref...

Страница 4: ...refrigerant expansion valve externally equalized expansion valve thermostat and seawater system for water cooled titanium condensers WARNING To avoid possible explosion death or injury practice safe h...

Страница 5: ...s not constant 4 10 cm of R7 insulation is required It is best to use as much insulation as is practical Call the Dometic Applications Department for advice on larger sized boxes or if you are unsure...

Страница 6: ...eded for the installation UNPACKING AND INSPECTION Units are securely packed in shipping containers approved by the International Safe Transit Association Upon arrival carefully check all items agains...

Страница 7: ...ce then add the minimum free area to get the minimum free area total for all of the units This also applies to the space airflow For example if a KRA 433X and a KRA 450X unit are in an enclosed space...

Страница 8: ...ould be in good thermal contact with the refrigerant tubing Attach it to the closest straight piece of tubing exiting the last box If either the expansion valve or its sensing bulb is located outside...

Страница 9: ...ons will extend the compressor s run time significantly resulting in shortened unit life To set the thermostat see Thermostat Operation on page 10 Thermostat bulb or thermistor should be mounted one t...

Страница 10: ...n off the first box turn on the other one Wait approximately 10 minutes Turn all boxes on and check for frost on box plate surfaces If not fully frosted check subcool 3 Follow procedures for Starting...

Страница 11: ...UP or DOWN buttons to change it then press the SET button to temporarily save it and display the the parameter code again 6 Repeat steps 4 and 5 to set other parameters if needed 7 TO PERMANENTLY SAV...

Страница 12: ...t temperature This will expedite the recovery of the refrigerant but is not necessary EVACUATE REFRIGERANT 1 Connect manifold gauges to both high and low side ports Attach center line of gauge set to...

Страница 13: ...NANCE SEAWATER SYSTEM Check the seawater strainer daily Remove any debris If you are in waters where jellyfish or other debris are a problem you may find it necessary to add a strainer on the outside...

Страница 14: ...y See technician for service 3 Low refrigerant charge Check for a refrigerant leak and repair Evacuate system and recharge with the correct amount of R 404A 4 TXV Mechanical failure Have technician co...

Страница 15: ...temperature introduce cooler air into compartment that houses the condensing unit High water temperature while you cannot remedy this problem you can help by introducing cooler air into the compartme...

Страница 16: ...S Figure 1 KRA Cabinet Type Condensing Units Figure 2 Various Flat Plate Evaporators Figure 3 Wrapped Box Evaporator Figure 4 Flat Plate Evaporator Designs Figure 5 Digital Thermostat Dometic Control...

Страница 17: ...TION PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRITTEN CONSENT FROM DOMETIC CORPORATION SHALL BE...

Страница 18: ...ory Insulated REV DATE APR DWG REVISION DESCRIPTION PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRI...

Страница 19: ...N DOMETIC APR BY DWG BY SCALE DATE REV DWG PART NUMBER PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT...

Страница 20: ...REV DWG PART NUMBER PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRITTEN CONSENT FROM DOMETIC CORPO...

Страница 21: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 21 Figure 10 Refrigerant Pressure Temperature Chart...

Страница 22: ...22 L 3571 ENGLISH Figure 11 Wiring Diagram for KRA 433X Unit with 1 Box...

Страница 23: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 23 Figure 12 Wiring Diagram for KRA 433X Unit with 2 Boxes...

Страница 24: ...RPORATION SHALL BE CONSIDERED UNLAWFUL AND CAN BE CONTESTED IN A COURT OF LAW PART NUMBER DWG REV DATE SCALE DWG BY APR BY DOMETIC REVISION DESCRIPTION DWG APR DATE REV 339501 C 339501 KRA 450X KRA 1...

Страница 25: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 25 Figure 14 Wiring Diagram for KRA 450X Unit with 3 Boxes...

Страница 26: ...26 L 3571 ENGLISH NOTES...

Страница 27: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 27 NOTES...

Страница 28: ...rineSales dometic com 24 7 TECH SUPPORT FOR UNITED STATES AND CANADA 8 00 AM to 5 00 PM Eastern Time 1 800 542 2477 After hours and weekends 1 888 440 4494 INTERNATIONAL SALES AND SERVICE Europe and t...

Отзывы: