background image

 

4

L-3571 ENGLISH

D

RAWINGS

 

AND

 D

IAGRAMS

Some equipment may be shipped with specific installation sheets or wiring diagrams that may supersede the information 
located in this manual.

REFRIGERATION BASICS

The instructions in this manual apply to all R-404A KRA refrigeration units. Any variations are noted in the text.

Slanted-top KRA condensing units are combination air-and-water-cooled, and the flat-top KRA condensing unit is water-cooled 
only. The evaporator section of the refrigeration system may consist of stainless steel plates installed in an insulated box, or 
may be copper tubing wrapped around the box, and then insulated.

The system works by removing heat from the refrigerator/freezer compartment (box) and transferring that heat to the outside air 
or seawater (depending on the condenser). Removing heat from the box reduces its temperature. However, whenever the 
compartment’s door is opened, more heat is introduced into the box from the warmer outside air thus increasing the box 
temperature. This added heat must be removed. Heat is also transferred through the walls of the box; proper insulation will 
reduce this heat transfer and keep the box cooler for longer periods of time.

The refrigerant used is R-404A. It is EPA approved, but is illegal to vent to the atmosphere. See previous notice.

SYSTEM COMPONENTS

The system consists of two main parts; the condensing unit, and the evaporator section (refrigerator/freezer box). They are 
connected by copper lines or flexible hoses. Other parts include the refrigerant expansion valve (externally equalized expansion 
valve), thermostat, and seawater system for water-cooled titanium condensers.

WARNING

To avoid possible explosion, death, or injury, practice safe handling of refrigerants.

WARNING

Refrigerants are heavier than air. They can “push out” the oxygen in your lungs or in any enclosed space. To avoid 
possible death or difficulty breathing:

Never sniff a refrigerant.

Never purge refrigerant into an enclosed room or space. All refrigerants must, BY LAW, be reclaimed.

If an indoor leak is suspected, thoroughly ventilate the area before beginning work.

Liquid refrigerant can be very cold. To avoid possible frostbite or blindness, avoid contact and wear gloves and 
goggles. If liquid refrigerant does contact your skin or eyes, get medical help immediately.

Never burn refrigerant, as poisonous gas will be produced.

Always follow EPA regulations. 

WARNING

To avoid possible explosion:

Never apply flame or steam to a refrigerant cylinder. If you must heat a cylinder for faster charging, partially immerse it 
in warm water.

Never fill a cylinder more than 80% full of liquid refrigerant.

Never add anything other than R-404A to an R-404A cylinder. Service equipment used must be listed or certified for 
R-404A.

Store cylinders in a cool, dry place. Never use a cylinder as a platform or a roller.

WARNING

To avoid possible explosion, use only returnable (not disposable) service cylinders when removing refrigerant from a 
system.

Ensure the cylinder is free of damage which could lead to a leak or explosion.

Ensure the hydrostatic test date does not exceed 5 years.

Ensure the pressure rating meets or exceeds standard specification of DOT-4BA400.

When in doubt, do not use the cylinder.

Содержание KRA 433X 1161

Страница 1: ...ery precaution has been taken in the preparation of this manual to ensure its accuracy However Dometic assumes no responsibility for errors and omission Neither is any liability assumed for damages re...

Страница 2: ...Condensing Unit 10 THERMOSTAT OPERATION 10 Operating the Dometic Control 10 Parameter Programming 11 Modbus Addresses for Dometic STIIC Interface 12 SERVICING YOUR REFRIGERATION SYSTEM 12 REFRIGERANT...

Страница 3: ...s NEC in the U S CEC in Canada 3 Open the electrical disconnect switch es before electrically connecting the unit 4 Before operating the unit be certain it is properly grounded 5 The units contain ref...

Страница 4: ...refrigerant expansion valve externally equalized expansion valve thermostat and seawater system for water cooled titanium condensers WARNING To avoid possible explosion death or injury practice safe h...

Страница 5: ...s not constant 4 10 cm of R7 insulation is required It is best to use as much insulation as is practical Call the Dometic Applications Department for advice on larger sized boxes or if you are unsure...

Страница 6: ...eded for the installation UNPACKING AND INSPECTION Units are securely packed in shipping containers approved by the International Safe Transit Association Upon arrival carefully check all items agains...

Страница 7: ...ce then add the minimum free area to get the minimum free area total for all of the units This also applies to the space airflow For example if a KRA 433X and a KRA 450X unit are in an enclosed space...

Страница 8: ...ould be in good thermal contact with the refrigerant tubing Attach it to the closest straight piece of tubing exiting the last box If either the expansion valve or its sensing bulb is located outside...

Страница 9: ...ons will extend the compressor s run time significantly resulting in shortened unit life To set the thermostat see Thermostat Operation on page 10 Thermostat bulb or thermistor should be mounted one t...

Страница 10: ...n off the first box turn on the other one Wait approximately 10 minutes Turn all boxes on and check for frost on box plate surfaces If not fully frosted check subcool 3 Follow procedures for Starting...

Страница 11: ...UP or DOWN buttons to change it then press the SET button to temporarily save it and display the the parameter code again 6 Repeat steps 4 and 5 to set other parameters if needed 7 TO PERMANENTLY SAV...

Страница 12: ...t temperature This will expedite the recovery of the refrigerant but is not necessary EVACUATE REFRIGERANT 1 Connect manifold gauges to both high and low side ports Attach center line of gauge set to...

Страница 13: ...NANCE SEAWATER SYSTEM Check the seawater strainer daily Remove any debris If you are in waters where jellyfish or other debris are a problem you may find it necessary to add a strainer on the outside...

Страница 14: ...y See technician for service 3 Low refrigerant charge Check for a refrigerant leak and repair Evacuate system and recharge with the correct amount of R 404A 4 TXV Mechanical failure Have technician co...

Страница 15: ...temperature introduce cooler air into compartment that houses the condensing unit High water temperature while you cannot remedy this problem you can help by introducing cooler air into the compartme...

Страница 16: ...S Figure 1 KRA Cabinet Type Condensing Units Figure 2 Various Flat Plate Evaporators Figure 3 Wrapped Box Evaporator Figure 4 Flat Plate Evaporator Designs Figure 5 Digital Thermostat Dometic Control...

Страница 17: ...TION PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRITTEN CONSENT FROM DOMETIC CORPORATION SHALL BE...

Страница 18: ...ory Insulated REV DATE APR DWG REVISION DESCRIPTION PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRI...

Страница 19: ...N DOMETIC APR BY DWG BY SCALE DATE REV DWG PART NUMBER PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT...

Страница 20: ...REV DWG PART NUMBER PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRITTEN CONSENT FROM DOMETIC CORPO...

Страница 21: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 21 Figure 10 Refrigerant Pressure Temperature Chart...

Страница 22: ...22 L 3571 ENGLISH Figure 11 Wiring Diagram for KRA 433X Unit with 1 Box...

Страница 23: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 23 Figure 12 Wiring Diagram for KRA 433X Unit with 2 Boxes...

Страница 24: ...RPORATION SHALL BE CONSIDERED UNLAWFUL AND CAN BE CONTESTED IN A COURT OF LAW PART NUMBER DWG REV DATE SCALE DWG BY APR BY DOMETIC REVISION DESCRIPTION DWG APR DATE REV 339501 C 339501 KRA 450X KRA 1...

Страница 25: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 25 Figure 14 Wiring Diagram for KRA 450X Unit with 3 Boxes...

Страница 26: ...26 L 3571 ENGLISH NOTES...

Страница 27: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 27 NOTES...

Страница 28: ...rineSales dometic com 24 7 TECH SUPPORT FOR UNITED STATES AND CANADA 8 00 AM to 5 00 PM Eastern Time 1 800 542 2477 After hours and weekends 1 888 440 4494 INTERNATIONAL SALES AND SERVICE Europe and t...

Отзывы: