10

L-3571 ENGLISH

9.

Confirm that thermostat sensing bulb is mounted in the correct area of the box, and that it is secure.

10. Make sure that the thermostatic expansion valve bulb is mounted correctly and securely and insulated.

11.

Make sure that frequently accessed parts are easily accessible, i.e. TXV, thermostat, quick connects, 
condensing unit

.

12. Check the seals on the box lid to make sure that they have good contact to the box top.

S

TARTING

 T

HE

 S

YSTEM

1.

Turn on the designated circuit breaker on the boat’s electrical panel.

2.

For units with a water-cooled condenser, first open the seacock. If pump is shared with another system, ensure that 
pump circuit breaker is on.

3.

Set thermostat to desired temperature.

4.

Watch the sight glass to make sure that refrigerant is flowing.

5.

Confirm that water (if used) is flowing out of overboard discharge (see note below).

6.

Confirm that condenser fan is running (if applicable).

7.

Approximately 5-10 minutes after startup, open the box top to visually confirm frost is forming on wall of box or plate.

8.

After 30 minutes of run time, check the sight glass to make sure the element inside is green (no moisture 
contamination). 

9.

Watch for a temperature decrease at the corresponding box thermostat.

S

YSTEM

 W

ITH

 2 

OR

 3 E

VAPORATORS

 

AND

 1 C

ONDENSING

 U

NIT

1.

Check all wiring to confirm that each thermostat brings on the corresponding box and the condensing unit and pump 
(optional).

2.

To check pressures and refrigerant charge, if necessary, follow these instructions:

Turn on only one box. Make sure that box works correctly. Wait approximately 10 minutes.

Turn off the first box, turn on the other one. Wait approximately 10 minutes.

Turn all boxes on, and check for frost on box/plate surfaces. If not fully frosted, check subcool.

3.

Follow procedures for “Starting The System” on page 10.

T

HERMOSTAT

 O

PERATION

For operational reference, see Figure 5: Digital Thermostat (Dometic Control), page 16. For error codes, see Table 6: 
Thermostat Display Error Messages (digital Dometic control), page 15.

O

PERATING

 

THE

 D

OMETIC

 C

ONTROL

Powering On The System

1.

When the control is powered up (breaker on), the Dometic control display will light up showing all the icons and 888. 
That is followed by a display of r5.2 then - - -. 

2.

After - - - displays, depending on the mode it was in when it was last powered OFF, the display could flash between 
OFF and the box temperature, or start the cooling process by flashing the compressor delay icon 

 for approximately 

3 minutes, then the compressor will start and cooling will begin.

3.

If the KRA unit was in the OFF mode, the control display alternates between OFF and the temperature reading. To turn 

on the compressor, press and hold the upper right power button 

 for 2-3 seconds.

4.

The control display will change from OFF and alternating temperature display to a constant temperature display. If the 
temperature setpoint is lower than the box temperature now displayed, the compressor icon 

 will flash indicating a 

call for cooling, and there will be a 3-minute delay before starting the compressor. If compressor icon is on but not 

NOTE

The seawater pump will cycle automatically whenever the compressor is running. Regularly check for seawater flow 
by observing the overboard discharge when the system is first turned on. If you do not observe steady water flow, turn 
off the system and check for obstructions in the seawater cooling system.

Содержание KRA 433X 1161

Страница 1: ...ery precaution has been taken in the preparation of this manual to ensure its accuracy However Dometic assumes no responsibility for errors and omission Neither is any liability assumed for damages re...

Страница 2: ...Condensing Unit 10 THERMOSTAT OPERATION 10 Operating the Dometic Control 10 Parameter Programming 11 Modbus Addresses for Dometic STIIC Interface 12 SERVICING YOUR REFRIGERATION SYSTEM 12 REFRIGERANT...

Страница 3: ...s NEC in the U S CEC in Canada 3 Open the electrical disconnect switch es before electrically connecting the unit 4 Before operating the unit be certain it is properly grounded 5 The units contain ref...

Страница 4: ...refrigerant expansion valve externally equalized expansion valve thermostat and seawater system for water cooled titanium condensers WARNING To avoid possible explosion death or injury practice safe h...

Страница 5: ...s not constant 4 10 cm of R7 insulation is required It is best to use as much insulation as is practical Call the Dometic Applications Department for advice on larger sized boxes or if you are unsure...

Страница 6: ...eded for the installation UNPACKING AND INSPECTION Units are securely packed in shipping containers approved by the International Safe Transit Association Upon arrival carefully check all items agains...

Страница 7: ...ce then add the minimum free area to get the minimum free area total for all of the units This also applies to the space airflow For example if a KRA 433X and a KRA 450X unit are in an enclosed space...

Страница 8: ...ould be in good thermal contact with the refrigerant tubing Attach it to the closest straight piece of tubing exiting the last box If either the expansion valve or its sensing bulb is located outside...

Страница 9: ...ons will extend the compressor s run time significantly resulting in shortened unit life To set the thermostat see Thermostat Operation on page 10 Thermostat bulb or thermistor should be mounted one t...

Страница 10: ...n off the first box turn on the other one Wait approximately 10 minutes Turn all boxes on and check for frost on box plate surfaces If not fully frosted check subcool 3 Follow procedures for Starting...

Страница 11: ...UP or DOWN buttons to change it then press the SET button to temporarily save it and display the the parameter code again 6 Repeat steps 4 and 5 to set other parameters if needed 7 TO PERMANENTLY SAV...

Страница 12: ...t temperature This will expedite the recovery of the refrigerant but is not necessary EVACUATE REFRIGERANT 1 Connect manifold gauges to both high and low side ports Attach center line of gauge set to...

Страница 13: ...NANCE SEAWATER SYSTEM Check the seawater strainer daily Remove any debris If you are in waters where jellyfish or other debris are a problem you may find it necessary to add a strainer on the outside...

Страница 14: ...y See technician for service 3 Low refrigerant charge Check for a refrigerant leak and repair Evacuate system and recharge with the correct amount of R 404A 4 TXV Mechanical failure Have technician co...

Страница 15: ...temperature introduce cooler air into compartment that houses the condensing unit High water temperature while you cannot remedy this problem you can help by introducing cooler air into the compartme...

Страница 16: ...S Figure 1 KRA Cabinet Type Condensing Units Figure 2 Various Flat Plate Evaporators Figure 3 Wrapped Box Evaporator Figure 4 Flat Plate Evaporator Designs Figure 5 Digital Thermostat Dometic Control...

Страница 17: ...TION PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRITTEN CONSENT FROM DOMETIC CORPORATION SHALL BE...

Страница 18: ...ory Insulated REV DATE APR DWG REVISION DESCRIPTION PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRI...

Страница 19: ...N DOMETIC APR BY DWG BY SCALE DATE REV DWG PART NUMBER PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT...

Страница 20: ...REV DWG PART NUMBER PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRITTEN CONSENT FROM DOMETIC CORPO...

Страница 21: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 21 Figure 10 Refrigerant Pressure Temperature Chart...

Страница 22: ...22 L 3571 ENGLISH Figure 11 Wiring Diagram for KRA 433X Unit with 1 Box...

Страница 23: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 23 Figure 12 Wiring Diagram for KRA 433X Unit with 2 Boxes...

Страница 24: ...RPORATION SHALL BE CONSIDERED UNLAWFUL AND CAN BE CONTESTED IN A COURT OF LAW PART NUMBER DWG REV DATE SCALE DWG BY APR BY DOMETIC REVISION DESCRIPTION DWG APR DATE REV 339501 C 339501 KRA 450X KRA 1...

Страница 25: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 25 Figure 14 Wiring Diagram for KRA 450X Unit with 3 Boxes...

Страница 26: ...26 L 3571 ENGLISH NOTES...

Страница 27: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 27 NOTES...

Страница 28: ...rineSales dometic com 24 7 TECH SUPPORT FOR UNITED STATES AND CANADA 8 00 AM to 5 00 PM Eastern Time 1 800 542 2477 After hours and weekends 1 888 440 4494 INTERNATIONAL SALES AND SERVICE Europe and t...

Отзывы: