13
Installation
Fig. 14
Minimum height of ventilation
LS300
LS300
H
Installation of lower and upper ventilation
grilles LS300.
Correct mounting of the lower ventilation gril-
le facilitates access to the connections and
functional parts during maintenance.
An installation other than described will
reduce the cooling capacity and jeopardi-
se the manufacturer's warranty/product
liability.
CAUTION!
Minimum height of ventilation
H
1.
☺
☺☺
☺☺
☺
☺
☺☺
☺☺
☺
Roof exhaust R500
1250 mm
Lower vent grille LS300
2.
☺
☺☺
☺
☺
☺☺
☺
Upper vent grille LS300
1400 mm
Lower vent grille LS300
Fig. 13
4.3.2 Height of ventilation
Minimum height of ventilation
R500
LS300
H
The ventilation grilles must have an open
cross-section of at least 400cm².
This is
achieved by using the Dometic LS 300 absor-
ber ventilation and air extraction system
which has been tested and approved for this
purpose.
Installation of roof exhaust R500 and lower
ventilation grille LS300.
289 0318-20_EN_RMD8xxx-Installation_N2.qxp 03.07.2012 13:07 Seite 13